Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.4 LAccepted-AOC FLAT NO 10 S NO 98 PLAT NO 78 SAI SAYAJI PARK A RIGHT BHUSARI COLONY KOTHRUD PUNE 411 038 | PUNE | MAHARASHTRA | 411038 | L1 | Accepted-AOC L1 | |
| 2 | L2₹40.6 L+₹1.2 L (3.12%)Rejected-Finance GALI BAWARI WALI NOHARIA BAZAAR SIRSA 125055 HARYANA | SIRSA | HARYANA | 125055 | L2 | Rejected-Finance Other than L1 | |
| 3 | Rejected-Technical CC III 28A JANTA BHAWAN ROAD SIRSA HARYANA 125055 | SIRSA | HARYANA | 125055 | - | Rejected-Technical Not enlisted in appropriate Cat. Also not executed any similar work. |
Tender Value
₹42.7 L
EMD Value
₹85,400
Closing Date
20 Jan 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) SIRSA
GE (AF) SIRSA, HARYANA-125055
GE/SRA/T-59/2024-25
2024_MES_690696_1
GE/SRA/T-59/2024-25
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (AF) SIRSA
PLEASE REFER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (AF) SIRSA
₹85,400
Yes
13 Feb 2025
27 Dec 2024
21 Jan 2025
27 Dec 2024
20 Jan 2025
8 Jan 2025
Amount
Supply, installation, testing & commissioning of Fire Alarm Control Panel 500mm x 500mm x 195mm (H x W x D), complying with BS EN 54, FIVE loop Addressable type with capacity to connect 99 detectors & 99 Modules and up to 200 detectors & 200 modules with loop card . The panel shall have 160 character LCD display and provide min 1000 event logs, Operating Voltage 230V, AC, 50Hz, Maximum PSU rating 8.6A total, comprised of 2.25A min @ 35V (loop supply) 1.66 min @12V (printing supply) 2.2A min charging current , loop load 460 mA per loop maximum with standby SMF battery 2 x 12V 12AH operating in 24 hrs normal and 10 mins in alarm condition, & inbuild battery charger up to 38AH complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: ZX5SE or equivalent model in other makes specified in tender) NOTE: Quoted rate shall be deemed to be inclusive of all types of cards and accessories required for satisfactory installation and commissioning of the fire alarm control panel. No claim shall ne entertained during currency of work.
Supply, installation, testing & commissioning of Fire Alarm Control Panel 400mm x 400mm x 135mm (H x W x D), complying with BS EN 54, Two loop Addressable with capacity to connect 99 detectors & 99 Modules and up to 200 detectors & 200 modules with loop card. The panel shall have 160 character LCD display and provide min 1000 event logs, Operating Voltage 230V, AC, 50Hz, Maximum PSU rating 4.2A total, comprised of 2.5A min @ 25V (Panel & loop supply) 1.75A min charging current , loop load 460 mA per loop maximum with standby SMF battery 2 x 12V 12AH operating in 24 hrs normal and 10 mins in alarm condition, & inbuild battery charger up to 38AH complete as per specification complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: ZX2SE or equivalent model in other makes specified in tender) NOTE: Quoted rate shall be deemed to be inclusive of all types of cards and accessories required for satisfactory installation and commissioning of the fire alarm control panel. No claim shall ne entertained during currency of work.
Supply, installation, testing & commissioning of Network Repeater Panel compatible with Morley IAS intelligent multi protocol fire Alarm control panel, connect ability with RS 485 peripheral bus with active or passive options, back lit adjustable alphanumeric display & controls for reset, accept, mute, silence alarms and self test (active repeater only) complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: ZXRE-709-601-001 or equivalent model in other makes specified in tender) NOTE: Quoted rate shall be deemed to be inclusive of all types of cards and accessories required for satisfactory installation and commissioning of the fire alarm control panel. No claim shall ne entertained during currency of work.
Supply, installation, testing & commissioning of Conventional beam detector with reflector, suitable for protecting open area with high ceiling area where other methods of smoke detection are difficult to install complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: BEAM1224S or equivalent model in other makes specified in tender)
Supply, installation, testing & commissioning of addressable Fault isolator module capable of monitoring shorted loop circuit and automatically restore communications when shorted conditions are corrected complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: MI/DISO or equivalent model in other makes specified in tender)
Supply, installation, testing & commissioning of addressable Control module, capable of providing DPDT contact rated at 24V DC, 2A. (For hooter/strobe) complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: MI/DCMO or equivalent model in other makes specified in tender)
Supply, installation, testing & commissioning of addressable Monitor module for monitoring the field devices & capable of providing DPDT contact rated complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: MI/DMMI or equivalent model in other makes specified in tender)
Supply, installation, testing & commissioning of addressable Control relay module for AHU/CSU units tripping, access door release and capable of providing DPDT contact rated at 240V AC, 2A complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: MI/D24CMO or equivalent model in other makes specified in tender)
Supply, installation, testing & commissioning of Manual Call Point including necessary back box / junction box for mounting Lever Pull Type complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: HM/MCP/GLASS or equivalent model in other makes specified in tender)
Supply and Fixing Response indicator for above ceiling detector complete all as specified and directed. (MAKE: HONEYWELL, MODEL NO: RI/007H or equivalent model in other makes specified in tender)
Supply, installation, testing & commissioning of LOOP SOUNDER Hooter cum strobe dual tone type with suitable M.S.CRCA housing and wiring circuit, with powder coated finish of approved colour complete all as specified and as directed. (MAKE: HONEYWELL, MODEL NO: WSO-PR-N05 + MI/B501AP/IV or equivalent model in other makes specified in tender)
Supply, Laying and testing of FRLS, XLPE insulated, PVC sheathed, galvanised steel strip or wire armoured electric power cable 1100 Volts grade with stranded copper conductor of size 1.5 sqmm 2 core, laid in trench or fixed to wall/passing through pipe/pole incl necessary thimbles, jointing and testing complete all as specified and directed. (Note :- Necessary earth work to be measured and paid separately.
Supply & Fixing circuit/submain wiring with 2x1.5 sqmm FRLS PVC insulated copper conductor, single core cable, surface mounted in and including ERW steel conduit 20mm dia (excluding junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. as required complete all as specified and as directed NOTES: (i) Two runs of 1.5 sqmm wire and one run of ERW conduit shall be measured as one unit.
S&F MS junction box, screw type, suitable for 20 mm OD MS ERW pipe complete all as specified and directed for the following types :-
Excavating in Trenches, not exc. 1.50 Metre Wide and Depth not exc. 1.50 Metre for taking out/up and laying of Water Main /Pipe, etc., Forming Surfaces to required Foundation, etc. and getting out as in Soft/Loose Soil, complete all as specified and as directed.
Returning, Filling in including Spreading, Levelling, Watering, Well Ramming in Layers not exc. 25 Cm, Surplus Soil providing in Heaps along the Route of the Pipe Line in Soft/Loose Soil, complete all as specified and as directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed.
Supply & Laying HDPE pipes, conforming to IS-4984, 40 mm OD, PN 10 with all fittings, laid in trenches for protection of cable complete all as specified and as directed
Material and Labour for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized steel earth wire 4 mm dia (up to 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing complete all as shown in Figure 15A of IS 3043 :1987, complete all as specified and directed.
GENERAL NOTES FOR THE WHOLE WORK:- (1) The Contractor shall employ the services of the designated Fire Alarm Specialist Supplier for the design, supply and commissioning of the fire alarm system. It shall consist of fire alarm sounders, break-glass units, heat and smoke detectors and control units. (2) After commencement of work, the contractor shall be provided with layout plan of the designated building. The Fire Alarm Specialist Supplier shall supply and install a fire zone chart showing plans of the building with all fire alarm control and indicating equipment clearly indicated. Each fire compartment/zone shall be easily identified by means of clearly marked colour codes. The fire zone chart shall be as a minimum sized A3, coloured and suitably framed to be handed over on completion of the works. (3) The Contractor shall arrange for the complete commissioning of the fire alarm system by the specialist fire alarm supplier. (4) The whole of the fire alarm installation should be inspected, tested and commissioned in accordance with clause 26 of BS 5839 part 1 and as further described. Commissioning shall be carried out in accordance with Clause 26.5 of BS 5839 part 1 which shall include:- (i) An audibility test of the alarm devices. Audibility level readings shall be taken in each room. Any sound levels found to be lower than 65 dba shall be reported to the Engineer-in-charge in writing. (ii) All trigger devices i.e. manual call points, heat and smoke detectors shall be tested for correct operation, (iii) A mains failure test shall be carried out to verify correct operation of the backup battery system. (5) Prior to commissioning, the Contractor shall provide a certificate of installation and cable test certificates of the system to the EIC. contd.....
(6) After commissioning of the fire alarm system, the contractor shall get the fire alarm system inspected and certified from State Government Fire Inspector under his own arrangement. Completion certificate shall be issued by GE only after satisfactory certification by Fire Inspector. (7) The provisions/requirements mentioned here-in-before are in brief and shall be read in conjunction with particular specifications provided in this tender, relevant paras of SSR Part-I, 2009 and Indian Standards. The contractor is liable to complete the work as per latest guidelines of fire safety issued by Central/State Government. Rates quoted by the contractor shall be deemed to be inclusive of all the above aspects. No claims, whatsoever shall be admissible during currency of work. (8). Around 948 RM of 40mm OD HDPE pipe has been laid by the previous contractor under BOQ Item No 20 and is available on site. Requisite items for excavation in trenches and partial returning filling has also been carried out. These quantities have not been considered in BOQ. The contractor shall utiliste the ibid items and complete the work in totality keeping in consideration the above aspect. He may, also visit the site with prior permission of AGE E/M (AF) Sirsa during office hours. No claim shall be entertained during currency of work.
YESH BUILDERS (BID ID -3212461)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .