| 1 | L1₹8.8 LAccepted-Finance | L1 | Accepted-Finance ok | |
| 2 | L2₹10.5 L+₹1.7 L (18.9%)Accepted-Finance | L2 | Accepted-Finance ok | |
| 3 | L3₹11.0 L+₹2.2 L (24.8%)Accepted-Finance | L3 | Accepted-Finance ok | |
| 4 | Rejected-Technical 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA | MEERUT | UTTAR PRADESH | 250103 | - | Rejected-Technical Rejected , as confirmed from manufacturer, specification of their ACB does not meet the NIT BOQ specification. |
Tender Value
Refer Docs
EMD Value
₹26,000
Closing Date
26 Sept 2022, 2:00 pmClosed
EE EnM HP I
OFFICE OF THE CHIEF ENGINEER WW THROUGH EE EnM HP I DELHI JAL BOARD GOVT OF NCT OF DELHI HAIDERPUR WATER WORKS DELHI 110085
Replacement of 1000 AMP. Air Circuit Breakers Installed in LT panel at Raw Water Pump House Ph I, HPWW I.
2022_DJB_229660_8
NIT 13
Open Tender
Miscellaneous Works
Works
60 days
Haiderpur WTP
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Delhi Jal Board
₹26,000
19 Nov 2022
20 Sept 2022
26 Sept 2022
20 Sept 2022
26 Sept 2022
20 Sept 2022
Dismantling the existing complete outgoing ACBs of 1000 Amp from the chambers of the main L T Panel including their cradles and disconnecting the bus bar connections with the main bus bars, disconnecting the outgoing cables etc. Dismantling the ACBs in the complete shut down and safe conditions.
Supply of Air Circuit Breaker (ACB) of Rating 1000 Amperes,3 Pole, 415V AC,EDO type, with Thermal Magnetic Release, 50 KA or more with under voltagetrip / release. Make- L&T/BCH/Schneider/DJB Approved
Installation of the cradle of the ACB as above at the panel in proper alignment for making the connections after proper cleaning of the chamber for removing any carbon etc. including modification / making mounting arrangement for fixing of new ACBs.
Fixing the ACB in the cradle in proper drawable condition including checking the movement along with making control connections as suitable for operating the new ACBs
Connecting the main bus bars of the panel and the incoming sides of new 1000 Amp ACBs by rearrangement/ modification / extension / addition of Bus Bar lengths in Aluminium construction of similar cross section as per existing as required for retrofitting of ACB and making the required joints including bending / cutting / shaping of the bus bars as required including providing of material, other consumables and tools and tackles as per site requirement.
Making the outgoing cable connections provisions at outgoing sides of new 1000 Amps ACB by rearrangement/ modification / extension / addition of Bus Bar lengths in Aluminium construction of similar cross section as per existing and making required the joints including bending / cutting / shaping of the bus bars as required. Connecting the existing cables to the ACBs after checking and restoration of the end terminations including providing of material, other consumables and tools and tackles as per site requirement.
Making the required connections with the IDMT tripping relays and with new ACBs and Making the required connections for the electrical operation of the new ACBs and with providing required wiring and providing required switches and other material / consumables as per site requirement.
Dismantling the existing doors of the outgoing 1000 Amp ACBs. Fabrication, supply and fixing of the new door of suitable size and provisions for the operation of the ACBs made with CRCA Sheet duly painted complete with all accessories as required.
Testing and commissioning of the 1000 ACB for operations first at NO load and then at ON load including operation, testing of charging system, testing for the electrical operations etc. as per the satisfaction of the engineer in charge.
TIMEX ENTERPRISES
Gupta Brothers
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .