RequiredOEM Authorization Certificate Diesel Generators- DG Sets ( 1 ) Technical Specifications * As per GeM Category Specification Specification Specification Name Values Bid Requirement (Allowed Values) OUTPUT CAPACITY RATING/PHASE Nominal Rated Capacity (KVA) 15 * No of Phase - Single phase
RequiredThree Phase ENGINE Make of Engine - * Model Number of Engine - * Capacity of Engine (cc) - * Engine Power (kWm) - * ISI Marking to IS :10001 for engine Yes * 1/4 BIS license No
Requiredif applicable - * Type of Engine cooling Air Cooled Air Cooled
RequiredLiquid Cooled Type of governer Mechanical Mechanical
RequiredElectronic Or higher Class of governer A1 A0
RequiredA1
RequiredA2 Or higher Number of cylinders (nos) 2 * No of Strokes (nos) 4 * Rated RPM of Engine (RPM) - 1500
Required3000 Overload capacity for one hour for every 11 hours continuous running at full load (%) 10 * Specific Fuel Consumption (gm/kWh) - * Starting voltage (volt) 12 * ALTERNATOR AC GENERATOR(ALTER NATOR) Make - * AC GENERATOR(ALTER NATOR) model Number - * Rating of AC Generator (KVA) 15 * Power Factor of AC generator 0.8 * Efficiency at rated Power factor at 75% of full Load 89.6 * Compliance of Alternator to IS:13364(part-1) Yes * Type of alternator Brushless * Voltage Regulation Grade VG 3 * Alternator IP Rating IP 23 * Class of Insulation H * CONTROL PANEL Control Panel Manual Manual
RequiredAMF IP Rating of Control Panel IP 53 * ACOUSTIC ENCLOSURE Sheet Thickness 1.6 1.6
Required1.8
Required2
Required1.2 Or higher Thickness of Foam 20 * 2/4 Density of Foam for sound insulation 28 * Noise level at 1 meter (dB) 75 * BATTERY Battery Type & Specification Low Maintenance free to IS: 14257 for high cranking performance * Battery capacity (Ah) - * No of batteries 1 * TEST REPORTS Availability of Type test report for Engine from Central govt/NABL/ILAC accredited laboratory Yes * Test Report number and date(Engine) - * Name and address of laboratory(Engine) - * Availability of Type test report for Alternator from Central government/NABL/ILAC accredited laboratory Yes * Test Report number and date(Alternator) - * Name and address of laboratory(Alternator) - * DG set meet requirements of Enviro nmental(Protection) Rules 1986
Requiredin respect of noise and emission norms
Requiredas described in STC Yes * WARRANTY INSTALLATION & COMMISSIONING Warranty 2 Any applicable numeric value Installation & Commissioning With Installation With Installation
RequiredWithout Installation Agreed to STC of the Product Yes * * Bold specifications are the golden parameters.