Loading…
Loading…
Tender Value
₹3.7 Cr
EMD Value
₹7.3 L
Closing Date
17 Aug 2026, 4:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
ELECT.G
17 conditions · 5 needing a document upload
Financial Eligibility Criteria: (Ref: RB letter No. 2022/CE- I/CT/GCC2022/POLICY : Advance Correction Slip No.-1 dt 14.07.2022) The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The intending tenderers should possess a valid electrical contractor license at the time of opening of tender, issued by any state government & same should be submitted along with tender documents by all bidders including working contractors of this unit otherwise offer shall be summarily rejected....... IT SHOULD BE NOTED BY THE TENDERER THAT ELECTRICAL LICENSE UNDER RENEWAL AT THE TIME OF TENDER OPENING WILL NOT BE CONSIDERED AND OFFER WILL BE SUMMARILY REJECTED. IT IS THE RESPONSIBILITY OF TENDERER TO UPLOAD VALID ELECTRICAL CONTRACTOR LICENSE ON THE DATE OF TENDER OPENING.
All requisite documents mentioned in clause 3.7 of the tender document attached pertaining to constitution of firm/concern. (As applicable).
36 conditions · 4 needing a document upload
The rate to be quoted by tenderer shall be inclusive of all state/central taxes including GST. THE TENDERER SHOULD UPLOAD VALID GST REGISTRATION CERTIFICATE ALONG WITH THE OFFER.
The tender shall comply with General Condition of contract (GCC),2022 of Indian Railways (file attached). and its latest amendment, if any. The tenderer shall submit the offer after duly satisfying himself/herself with the GCC,2022 in general.
Tenderers are required to upload the Bank details as per Annexure-XII (Real Time Gross Saving (RTGS)/National Electronic Fund Transfer (NEFT) Model Mandate Form)of tender document.
Tenderers are required to upload requisite details as per Annexure-VIIB (DETAILS OF CONTRACTUAL PAYMENT RECEIVED IN LAST THREE FINANCIAL YEARS AND CURRENT FINANCIAL YEAR) without which the offer is liable to be rejected.
Tenderers are compulsorily required to upload Affidavit as per Annexure-XXIV along with tender document, without which the offer will be considered incomplete and will be rejected summarily.
All requisite documents/credentials mentioned in clause 3.5 of the tender document attached pertaining to his/their technical and financial eligibility. (As applicable).
All requisite documents mentioned in clause 3.7 of the tender document attached pertaining to constitution of firm/concern. (As applicable).
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
No post tender correspondence for submission of additional documents shall be entertained after opening of the Technical & Commercial offers. Even suo-moto post tender letters of the tenderer/s shall be treated as Null & Void.
This tender complies with Public Procurement Policy (Make in India) Order 2017, dated 15/06/2017, issued by Department of Industrial Promotion and Policy, Ministry of Commerce, circulated vide Railway Board letter no. 2015/RS(G)/779/5 dated 03/08/2017 and 27/12/2017.
IF ANY DISCREPANCY IS FOUND IN THE TENDER DOCUMENT, NAMELY SOR ITEM DESCRIPTION, SPECIAL TENDER CONDITION ETC., CLARIFICATION CAN BE SOUGHT FROM THE OFFICE OF SRDEE/G/DLI, DRM OFFICE, STATE ENTRY ROAD, NEW DELHI.
This tender complies with Railway Board instructions for Startups (recognized by Department of Industrial Policy and Promotion, Ministry of Commerce and Industry) for exemption from payment of Bid Security as detailed in GCC 2022 as amended from time to time. Such Startup firms may note that no other exemption is applicable to them in this particular tender.
On account payment, contractor shall submitted indemnity bond with validity up to the completion/extended period in the prescribed format (please refer Annexure-XXVIII) at the contractor's cost, vesting the ownership of such material with the railways.
This tender shall also complies with "Indian Railways Standard General Conditions of Contract, April 2022 (Advance Correction Slip No. 11)" vide Railway Board letter No. 2022/CE-I/CT/GCC- 2022/POLICY/Pt.I (E-3320424), dated: 13.03.2026 (attached)
The rate to be quoted by tenderer shall be inclusive of all state/central taxes including GST. tenderer shall submit GST certificate along with the offer.
All disputes or differences of any kind whatsoever arising out of or in connection with this contract, whether during its execution or after completion, termination, or breach thereof, shall be subject to the exclusive jurisdiction of the competent courts at New Delhi only.
The issues not covered under the tender document shall be governed by General conditions of Contract (GCC) 2022 or its latest amendments if any during entire period of contract. If any contradiction in Tender Document and GCC is observed then GCC shall prevail.
Defective parts shall only be replaced with OEM's spares. Proper invoices/delivery challan /warranty certificate etc. shall be provided by the firm to prove genuineness of spare parts.
Strengthening of Power Supply distribution system with replacement of old and obsolete LT panel/Feeder pillar with other associated works at Old Delhi station.
89-SRDEE-G-DLI-2026-27
89-SRDEE-G-DLI-2026-27
Open
Works - General
6 Months
Delhi, Delhi
₹0
₹7.3 L
17 Aug 2026
24 Jul 2026
3 Aug 2026
76 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | Above/ 34963932.00 Below/P | ||
| Design, Supply, fixing, testing and commissioning of LT panel IP 42, conforming to IS/IEC 61439 Part 1&2, Edition-3 2020 or latest, Form of separation-3B, body made of CRCA sheet steel with anti-corrosion treatment (ACB - Incoming & ACB/ MCCB - Outgoing), Make: ABB, Siemens, LK, Schneider, Legrand or equivalent conforming to IEC 60947-2 or latest with digital measuring instrument & CU bus-bar arrangement as per relevant IS, IE rules and site requirement & as per explanatory note. a) 1600A ACB 4P with microprocessor MDO type having Breaking capacity 50 KA = 02 Nos. (Incoming). b) 3200A ACB 4P with microprocessor release MDO type having Breaking capacity 50 KA =01 Nos. for (bus coupler). c) 800A ACB 4P with microprocessor release MDO type having Breaking capacity 50 KA =05 Nos. (Outgoing). d) 4P MCCB 400Amps 36 KA with adjustable thermal & fixed magnetic release = 08 Nos. (Outgoing). e) 4P MCCB 250Amps 36 KA with adjustable thermal & fixed magnetic release = 10 Nos. (Outgoing). | — | — | — | 54,98,202 | |
| Design, Supply, fixing, testing and commissioning of LT panel IP 42, conforming to IS/IEC 61439 Part 1&2, Edition-3 2020 or latest, Form of separation-3B, body made of CRCA sheet steel with anti-corrosion treatment (ACB - Incoming & ACB/ MCCB - Outgoing), Make: ABB, Siemens, LK, Schneider, Legrand or equivalent conforming to IEC 60947-2 or latest with digital measuring instrument & CU bus-bar arrangement as per relevant IS, IE rules and site requirement & as per explanatory note. a) 800A ACB 4P with microprocessor MDO type having Breaking capacity 50 KA having = 02 Nos. (Incoming). b) 1600A ACB 4P with microprocessor release MDO type having Breaking capacity 50 KA =01 Nos. for (bus coupler). c) 4P MCCB 400Amps 36 KA with adjustable thermal & fixed magnetic release = 02 Nos. (Outgoing). d) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release =08 Nos. (Outgoing). e) 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release =04 Nos. (Outgoing). | — | — | — | 65,92,104 | |
| Design, Supply, fixing, testing and commissioning of LT panel IP 42, conforming to IS/IEC 61439 Part 1&2, Edition-3 2020 or latest, Form of separation-3B, body made of CRCA sheet steel with anti-corrosion treatment (ACB - Incoming & ACB/ MCCB - Outgoing), Make: ABB, Siemens, LK, Schneider, Legrand or equivalent conforming to IEC 60947-2 or latest with digital measuring instrument & CU bus-bar arrangement as per relevant IS, IE rules and site requirement & as per explanatory note. a) 630A ACB 4P with microprocessor MDO type having Breaking capacity 50 KA = 02 Nos. (Incoming). b) 1250 A ACB 4P with microprocessor release MDO type having Breaking capacity 50 KA = 01 Nos. for (bus coupler). c) 4P MCCB 400Amps 36 KA with adjustable thermal & fixed magnetic release = 02 Nos. (Outgoing). d) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release =04 Nos. (Outgoing). e) 4P MCCB 125Amps 36 kA with adjustable thermal & fixed magnetic release =06 Nos. (Outgoing). | — | — | — | 36,93,252 | |
| — | 12.00 | — | — | ||
| Supply, fixing, testing and commissioning of LT distribution board confirming to IEC 61439-1&3, surface/recessed mounting, double door out door type, IK-09, IP 54, made up of CRCA sheet steel, with anti corrosion treatment, phosphatised powder painted/coated, 100A Cu Bus bar, with neutral bar/s, shroud/s, earth bar/s, sticking saddles, Din rail. MCBs Make- ABB, Siemens, LK, Schneider, Legrand or equivalent confirming to IEC 60898, IE rules and site requirement. It should include well dressing and color-coded interconnecting wire set, cable ties and circuit identifications labels. It should also be rodent entry proof, reversible door, cement spill protection, detechable gland at top and bottom and short link for MCBs. Complete DB should be RoHs & REACH complaince & as per explanatory note. 63 A 4P RCBO 100 mA= 01 No. (Incoming), 6-32A MCB SP "C" Series =18 Nos. (Outgoing) | — | — | — | 2,28,240 | |
| — | 10.00 | — | — | ||
| Supply, fixing, testing and commissioning of LT distribution board confirming to IEC 61439-1&3, surface/recessed mounting, double door out door type, IK-09, IP 54, made up of CRCA sheet steel, with anti corrosion treatment, phosphatised powder painted/coated, 100A Cu Bus bar, with neutral bar/s, shroud/s, earth bar/s, sticking saddles, Din rail. MCBs Make- ABB, Siemens, LK, Schneider, Legrand or equivalent confirming to IEC 60898, IE rules and site requirement. It should include well dressing and color-coded interconnecting wire set, cable ties and circuit identifications labels. It should also be rodent entry proof, reversible door, cement spill protection, detechable gland at top and bottom and short link for MCBs. Complete DB should be RoHs & REACH complaince & as per explanatory note. 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release= 01 No. (Incoming) 6-32A MCB SP "C" Series =25 Nos. (Outgoing). | — | — | — | 5,35,700 | |
| Supply, fixing, testing and commissioning of 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release with enclosure with surface mounting/ recessed double door out door type made up of CRCA sheet steel with anti corrosion treatment and suitable, IP 54 phosphatised powder painted complete with neutral link, earth point, Din rail and prewired confirming to IEC 60947 & IEC 61439 or latest, Make- ABB, Siemens, L&T, Schneider, Legrand or equivalent & as per explanatory note. | — | — | — | 1,00,470 | |
| Supply, fixing, testing and commissioning of 4P MCCB 250 Amps 36 kA with adjustable thermal & fixed magnetic release with enclosure with surface mounting/ recessed double door out door type made up of CRCA sheet steel with anti corrosion treatment and suitable, IP 54 phosphatised powder painted complete with neutral link, earth point, Din rail and prewired confirming to IEC 60947 & IEC 61439 or latest, Make- ABB, Siemens, L&T, Schneider, Legrand or equivalent & as per explanatory note. | — | — | — | 3,25,752 | |
| — | 11.00 | — | — | ||
| Design, Supply, fixing, testing and commissioning of front operated double door type weather proof feeder pillar, IP 55 conforming to IS/IEC 61439 Part 1&2, Edition-3 2020 or latest, Form of separation-3B ,body made of CRCA sheet steel with anti-corrosion treatment, (MCCB - Incoming & MCCB - Outgoing) comprising with the following MCCB's fixed in it of make: ABB, Siemens, LK, Schneider, Legrand or equivalent conforming to IEC 60947-2 or latest with digital measuring instrument & Al bus-bar arrangement as per relevant IS, IE rules and site requirement & as per explanatory note. a) 4P MCCB 250Amps with adjustable thermal & fixed magnetic release =02 No.(Incoming). b) 4P 250 Amps on load change over switch(COS) =01 No. c) 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release =02 Nos.(Outgoing). d) 4P MCCB 63 Amps 36kA with adjustable thermal & fixed magnetic release =04 Nos.(Outgoing). | — | — | — | 24,24,510 | |
| Design, Supply, fixing, testing and commissioning of front operated double door type weather proof feeder pillar, IP 55 conforming to IS/IEC 61439 Part 1&2, Edition-3 2020 or latest, Form of separation-3B ,body made of CRCA sheet steel with anti-corrosion treatment, (MCCB - Incoming & MCCB - Outgoing) comprising with the following MCCB's fixed in it of make: ABB, Siemens, LK, Schneider, Legrand or equivalent conforming to IEC 60947-2 or latest with digital measuring instrument & Al bus-bar arrangement as per relevant IS, IE rules and site requirement & as per explanatory note. a) 4P MCCB 400Amps with adjustable thermal & fixed magnetic release =02 No.(Incoming). b) 4P 400 Amps on load change over switch(COS) =01 No. c) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release =03 Nos.(Outgoing). d) 4P MCCB 125Amps 36kA with adjustable thermal & fixed magnetic release =03 Nos. (Outgoing). | — | — | — | 15,41,004 | |
| Design, Supply, fixing, testing and commissioning of front operated double door type weather proof feeder pillar body made of polycarbonate having IP 65 protection (IEC 60529) (MCCB - Incoming & MCCB - Outgoing) comprising with the following MCCB's fixed in it of make: ABB, Siemens, LK, Schneider, Legrand or equivalent conforming to IEC 60947-2 or latest with digital measuring instrument & Al bus-bar arrangement conforming to IS/IEC 61439 Part 1&2, Edition-3 2020 or latest and as per IS, IE rules and site requirement. It should be dust proof, rodent entry proof and vermin proof, proper polyamide cable gland with IP65 protection & should suit the number, type and size of power cables for both incoming and outgoing cables. It should have proper canopy made of CRCA sheet and ground clearance as per IS/IEC rules and approval of competent authority & as per explanatory note. a) 4P MCCB 400Amps with adjustable thermal & fixed magnetic release = 01 No.(Incoming). b) 4P 400 Amps on load change over switch(COS) = 01 No. c) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release = 04 Nos.(Outgoing). d) 4P MCCB 125Amps 36kA with adjustable thermal & fixed magnetic release =04 Nos. (Outgoing). | — | — | — | 9,67,782 | |
| — | 1000.00 | — | — | ||
| Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required conforming to IS/IEC 61537: 2024 and CPWD DSR (E&M) 2022 or latest & as per explanatory note. 150 mm width X 50 mm depth X 1.6 mm thickness | — | — | — | 7,79,000 | |
| — | 1500.00 | — | — | ||
| Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required conforming to to IS/IEC 61537: 2024 and CPWD DSR (E&M) 2022 or latest & as per explanatory note. 300 mm width X 50 mm depth X 1.6 mm thickness | — | — | — | 13,86,000 | |
| — | 300.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016), IS 732:2019 or latest including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 35 cm and depth- 75 to 100 cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Upto 35 sq. mm | — | — | — | 1,14,300 | |
| — | 960.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016), IS 732:2019 or latest including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 35 cm and depth- 75 to 100 cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 35 sq. mm and upto 95 sq. mm | — | — | — | 4,27,200 | |
| — | 600.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016), IS 732:2019 or latest including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 35 cm and depth- 75 to 100 cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 95 sq. mm and upto 185 sq. mm | — | — | — | 2,82,000 | |
| — | 1080.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016), IS 732:2019 or latest including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 35 cm and depth- 75 to 100 cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 185 sq. mm and upto 400 sq. mm | — | — | — | 5,62,680 | |
| — | 100.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016), IS 732:2019 or latest in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 55 cm and depth-(75-100) cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Upto 35 sq. mm | — | — | — | 29,600 | |
| — | 320.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016), IS 732:2019 or latest in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 55 cm and depth-(75-100) cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note. Above 35 sq. mm and upto 95 sq. mm | — | — | — | 1,00,480 | |
| — | 200.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016), IS 732:2019 or latest in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 55 cm and depth-(75-100) cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 95 sq. mm and upto 185 sq. mm | — | — | — | 66,800 | |
| — | 360.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016), IS 732:2019 or latest in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 55 cm and depth-(75-100) cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 185 sq. mm and upto 400 sq. mm | — | — | — | 1,41,120 | |
| — | 100.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required as per IS 1255 (reviewed 2016), IS 732:2019 or latest. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Upto 35 sq. mm (clamped with 1mm thick saddle) | — | — | — | 6,000 | |
| — | 320.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required as per IS 1255 (reviewed 2016), IS 732:2019 or latest. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) | — | — | — | 45,760 | |
| — | 200.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required as per IS 1255 (reviewed 2016), IS 732:2019 or latest. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) | — | — | — | 33,600 | |
| — | 360.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required as per IS 1255 (reviewed 2016), IS 732:2019 or latest. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 185 sq. mm and upto 400 sq. mm (clamped with 25/40x3mm MS flat clamp) | — | — | — | 89,640 | |
| — | 200.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade(HT) of following size direct in ground including excavation(upto 75-100 cm depth and not less than 35 cm wide),sand cushioning, protective covering and refilling the trench etc. as required as per detail drawing approved by competent authority and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR(E&M)2025 and IS 1255 (Reviewed in 2016) or latest, IS 732:2019 or latest & as per explanatory note.Above 120 sq. mm and upto 400 sq. mm | — | — | — | 1,32,600 | |
| — | 65.00 | — | — | ||
| Earthing with 40 mm dia. GI pipe class 'B' 4.5 meter long earth electrode as per IS:3043 (latest version) including construction of masonry enclosures with hinged cover plate of cast iron with locking arrangement (approx. size 400 mm x 400 mm) on top, and water pipe etc. with charcoal/coke and salt as required and provision of earth plate, connections from earth electrode to switch gear/pole as per drawing & as per explanatory note. | — | — | — | 3,86,360 | |
| — | 325.00 | — | — | ||
| Supplying and laying 25 mm X 5 mm G.I strip confirming to relevant IS as per IS:3043 (latest version), fixing on surface or as per site condition, clamping or fixing with suitable arrangement as per site requirement, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required & as per explanatory note. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm) | — | — | — | 51,025 | |
| Earthing with 600x600x3mm thick copper plate earth electrode as per IS 3043 (Latest version), to achieve earth resistance less than one ohm, including construction of masonry enclosure with hinged cover plate of cast iron with locking arrangement (Approx. size 600x600 mm) on top, watering pipe, connections from earth plate to top with 40x6mm copper strip in 50 mm dia. pipe class ' B' provision of earth plate as per drawing & as per explanatory note. | — | — | — | 23,462 | |
| — | 10.00 | — | — | ||
| Supplying and laying 40 mm X 6 mm copper strip at 0.3 metre below ground as strip earth electrode confirming to relevant IS as per IS:3043 (Latest version), including connection/ terminating with nut, bolt, spring, washer etc. as required & as per explanatory note. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) | — | — | — | 19,580 | |
| — | 1000.00 | — | — | ||
| Supply, Laying, Testing and Commissioning of 160 mm dia HDPE pipe (PE-100, PN-6) conforming to IS:4984 or latest, for cable laying by trenchless Horizontal Directional Drilling (HDD) method as per IS:1255 or latest, IE Rules, CPWD and Indian Railways specifications, including detailed route survey, marking of alignment, pilot drilling, reaming, supply and laying of pipe by pull-back method with butt fusion/electrofusion jointing, use of suitable drilling fluid, and maintaining required depth and alignment (generally 1.5 m to 3.5 m or as directed). The work shall include preparation and submission of complete HDD report comprising route alignment drawings with chainage and coordinates of entry/exit points, section-wise details of HDD lengths, depth profile graphs (depth vs chainage), HDD logs, and photographic records, as per site requirements. The item also includes testing, quality assurance, protection of existing utilities, disposal of slurry, restoration of site, and all incidental works complete in all respects as directed by Engineer-in-Charge & as per explanatory note. | — | — | — | 11,56,000 | |
| Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 150 sq mm size of 3 core, XLPE aluminium conductor cable of 11KV grade as required as per IS 13573:2011(Reviewed in 2024) or latest & other relevant IS/IEC standard and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR(E&M)2022 or latest & as per explanatory note. | — | — | — | 85,796 | |
| Supply, laying, fixing and commissioning of HT straight through joints heat shrinkable type along with loop of cable of size 70-185 sq. mm as per IS 7093, 13573:2021 or latest IS/IEC, IE rules & as per explanatory note. | — | — | — | 37,326 | |
| Supply, Laying, fixing and commissioning of LT straight through joints along with loop of cable of following sizes as per IS:7093 or latest, IE rules and site requirement and satisfaction to the Railway representative & as per explanatory note. 50-95 sq. mm | — | — | — | 24,756 | |
| — | 12.00 | — | — | ||
| Supply, Laying, fixing and commissioning of LT straight through joints along with loop of cable of following sizes as per IS:7093 or latest, IE rules and site requirement and satisfaction to the Railway representative & as per explanatory note. 120-185 sq. mm | — | — | — | 55,788 | |
| — | 10.00 | — | — | ||
| Supply, Laying, fixing and commissioning of LT straight through joints along with loop of cable of following sizes as per IS:7093 or latest, IE rules and site requirement and satisfaction to the Railway representative & as per explanatory note. 240-400 Sq. mm | — | — | — | 48,990 | |
| — | 20.00 | — | — | ||
| Supply, erection, testing and commissioning of End termination of 2.0 C / 4.0 C X 70 to 240 sq.mm. LT XLPE cable as per specification & as per explanatory note. (One set means lugs in R-Y-B-N) conforming to IS:13573-1(2011) or latest. | — | — | — | 8,880 | |
| — | 300.00 | — | — | ||
| Supplying and fixing of FRP Fencing rust proof, shock proof, anti-corrosive, self extinguishing, ultraviolet stabilized, FVO-UL94, weather proof, flame retardant, environment friendly, installed at electrical installations with necessary concreting for grouting vertical post, hardware, accessories, fitting etc. of 2000mm height above the ground and minimum 300 mm grouting in ground i.e. total height will be 2.3 meter along with 1 number of FRP almirah type double door gates with necessary hardware accessories like stainless steel heavy duty L-Drop, hinges, screws, nut and bolt, lock fittings etc. with double door openable-lockable provision for top ceiling arrangement with appropriate cut for high mast pole/CSS/FTU alongwith pad lock, hinges for the same of suitable length, width & height with vertical post of size 50x50x3mm, sub-frame of 50x25x3mm, pickets of size 38x15mm, hollow section size of not more than 5x5 inch and also providing 1 number danger plate of size 250x200x2mm, 1 number name plate of property of N. Railways and sponsors name as per site requirement & as per explanatory note. | — | — | — | 3,98,100 | |
| — | 35.00 | — | — | ||
| Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 meters lead as per direction of Engineer - in - charge for making trench for cable laying, as per explanatory note. Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) | — | — | — | 75,880 | |
| — | 35.00 | — | — | ||
| Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 meters lead as per direction of Engineer - in- charge for making trench for cable laying, as per explanatory note. | — | — | — | 1,10,705 | |
| — | 35.00 | — | — | ||
| Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 Cement : 2coarse sand (zone- III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) & as per explanatory note. | — | — | — | 2,78,460 | |
| — | 35.00 | — | — | ||
| Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:2:4 (1cement : 2 coarse sand (zone-III)derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) & as per explanatory Note. | — | — | — | 3,00,370 | |
| Carrying out GPR (Ground Penetrating Radar) Survey for Underground utility services and route using GPR and EPL & as per explanatory note. Location- Koriya Pul Substation to New Proposed LT switch room (Behind Main Hall Old Delhi Railway Station) and New Proposed CSS (Adjacent RPF Thana near PF-1) to New Proposed LT switch room | — | — | — | 68,000 | |
| Design, Supply, installation, testing and commissioning of package type 11 kV/433 V outdoor substation, 630 KVA made from GI enclosure complete as required conforming to IEC 62271- 202 only and relevant IS, specification and Technical Specification as applicable for the rating, internal arc of 21 KA/1 sec. IAC A & B on HT compartment. 630 KVA 11 KV/433 V DYN oil type, hermetically sealed energy efficiency level 2 transformer (BEE star Rated 2) with corrugated wall, without conservator, type of design & Top Bushing for HT & LT with off load tap switch of rating +5% to -5% @ 2.5%. 11 kV 630 A 21 KA/3 sec Non extensible Ring main unit compact switchgear consisting of 3 no. fixed motorized VCB module in SF6 insulated stainless steel enclosure (2.5 mm thick, SS304 grade) and with Bus PT metering module. Incomer from transformer : 800 Amps 433 V 4P 50 Hz 50 KA fixed motorized type Air circuit breaker (ACB)- 01 No. 400 A MCCB 4P 36 KA with adjustable thermal & fixed magnetic release = 02 Nos.(Outgoing). 200/250 A MCCB 4P 36 KA with adjustable thermal & fixed magnetic release = 02 Nos.(Outgoing) | — | — | — | 53,14,158 | |
| — | 4900.00 | — | — | ||
| Laying, dressing, terminating, and testing of 1-core, 16 sq.mm to 120 sq.mm, 1.1 kV grade, PVC/ XLPE insulated, armoured/unarmoured Aluminium/ copper conductor cable for TN-S earthing system, laid in the same trench/HDPE pipe/Cable Tray along with power cables (laying mentioned in S. No. 13 to 24) as per IS 732:2019 or latest, providing and fixing of cable identification tags, supply and fixing of suitable size brass/compression glands, crimping type Aluminium/copper lugs, jointing (if required), insulating tapes, ferrules, and making proper end terminations and connections to equipment and earth bus/bar, complete as required & as per explanatory note. | — | — | — | 4,16,500 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocument.pdf
ATTACHMENT
SpecialConditionsofContract.pdf
ATTACHMENT
TechSpecofCSS.pdf
ATTACHMENT
ModifiedExplanatoryNote.pdf
ATTACHMENT
GCC-2022-ACS10_merged.pdf
ATTACHMENT
GCCAdvanceCorrectionSlipNo.11.pdf GCC ACS No 11
ATTACHMENT
GCCAdvanceCorrectionSlipNo.11.pdf
ATTACHMENT
ModifiedTenderDocument.pdf
CORRIGENDUM
ModifiedTenderDocument.pdf
CORRIGENDUM
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .