| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.7 LAccepted-AOC 1ST FLOOR PRABHA SHOPPING COMPLEX OLD PAHARGAON DOLLYGUNJ PORT BLAIR SOUTH ANDAMAN ANDAMAN NICOBAR 744103 UDYAM AN 01 0000143 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744103 | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹16.4 L+₹1.6 L (10.5%)Rejected-AOC | L2 | Rejected-AOC NOT BEING L1 | |
| 3 | L3₹16.6 L+₹1.8 L (12.1%)Rejected-AOC MES WORKS SITE CARNICOBAR ANDAMAN NICOBAR ISLAND PIN 744301 | CARNICOBAR | NICOBAR | ANDAMAN AND NICOBAR ISLANDS | 744301 | L3 | Rejected-AOC NOT BEING L1 |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
4 Mar 2022, 6:00 pmClosed
GE P NORTH PORTBLAIR
GE P NORTH MINNIEBAY, JUNGLIGHAT P.O, PORTBLAIR
REPAIRS TO MAINTENANCE OF HT INSTALLATION, WATER SUPPLY INSTALLATION,UG CABLES,PIPE LINES, EXTERNAL E/M SERVICES AT PANCHU TIKREY AT HUT BAY
2022_MES_505652_1
8126
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
HUTBAY ANDAMANS
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE P NORTH PORTBLAIR
₹30,000
Yes
16 Apr 2022
3 Feb 2022
11 Mar 2022
3 Feb 2022
4 Mar 2022
18 Feb 2022
Amount
Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth and getting out in in any type of soil for laying of pipes, cables etc all as directed by Engr-in-Charge.
Returning filling in , excavated soil including spreading, leveling and well ramming in layers not exc 25cms each any type of soil.
Removing the excavated materials not exc 50mtr and depositing where directed at a level not exceeding 1.5 mtr above the staring point all as directed by Engr - in- Charge.
M&L for sand cushioning by spreading in trenches fine dry river sand by gently by punning down manually as in cable protection all as specified and as directed by EIC. Note : Sand after punning down will be measured
Supply and laying precast concrete cable cover class LV type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified.
Laying only precast concrete cable cover class LV type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified. Note :- The rate quoted is deemed to include for removing the existing cable cover segregating the servicable covers and relaying after laying cables and sand cushioning. Unservicable covers shall be issued under credit.
Supply & Lay XLPE insulated, heavy duty 1100 volt grade electric LT UG cable with aluminium conductor of size 6 Sqmm 2 Core in trenches/along the wall/including making all connections complete with lugs, suitable cable glands as required at site and as directed by Engr-in-Charge - Make - Polycab/Plaza/Havells
Supply & Lay XLPE insulated, heavy duty 1100 volt grade electric LT UG cable with multistranded aluminium conductor of size 10 Sqmm 4 Core in trenches/along the wall/including making all connections complete with lugs, suitable cable glands as required at site including taking down existing unserviceable cable of any type and as directed by Engr-in-Charge - Make - Polycab/Plaza/Havells
Supply & Lay XLPE insulated, heavy duty 1100 volt grade electric LT UG cable with multistranded aluminium conductor of size 35 Sqmm 3.5 Core in trenches/along the wall/including making all connections complete with lugs, suitable cable glands as required at site and including taking down existing unserviceable cable of any type as directed by Engr-in-Charge - Make - Polycab/Plaza/Havells
Supply & Lay XLPE insulated, heavy duty 1100 volt grade electric LT UG cable with multistranded aluminium conductor of size 50 Sqmm 3.5 Core in trenches/along the wall/including making all connections complete with lugs, suitable cable glands as required at site including taking down existing unserviceable cable of any type and as directed by Engr-in-Charge - Make - Polycab/Plaza/Havells
Supply & Lay XLPE insulated, heavy duty 11000 volt grade electric LT UG cable with multistranded aluminium conductor of size 95 Sqmm3 Core in trenches/along the wall/including making all connections complete with lugs, suitable cable glands as required at site and as directed by Engr-in-Charge - Make - Polycab/Plaza/Havells
S & F in repairs out door heat shrink type end termination cable jointing kit for 11 KV (Earthed) grade cable complete with and including jointing materials, accessories and thimbles etc suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm & 95 Sqmm, complete all as specified and directed.
M&L for cutting existing road/hard standing not exc 45x45 cm in wide & depth getting out excavated material for laying GI tube ;returning filling & well rammaing watering finish suraface 10 cm from top using PCC 1:3:6, including removal of surplase soil all as directed
M&L for Straight through heat shrink joint complete type LT XLPE cable upto 1.1 KV complete with all accessories. NOTE: Excvation & Earth work shall be mesured & paid sepreately in respective item of this sch.
4 Core 10 Sq mm.
3 1/2 core 35/50 Sqmm
3 1/2 core 70/95 Sqmm
M&L for preparation of old painted surfaces of pre-stressed concrete pole upto 9 mtr long by scarping old paint and applying two coats of cement base paint including numbering of pole with black oil paint painting the base of the pole in alternate black and yellow stripes each 30 Cm apart up to 1.5mtr height all as directed by Engineer in Charge
Taking down old unserviceable street light fittings from the street light poles and replacement of burnt/worn out accessories and refixing the same in existing position including testing after repair complete all as directed by Engineer in charge . Note :- (i) Major Spares such drivers for repairs and replacement shall be measured and paid separately under respective items of this schedule' (ii) Minor Spares such as insulation tape, Lamp Holder, Connectors, Screws, nuts, bolts, washers, T & P, Ladder etc are deemed to be included in the quoted rate.
Supply only LED Driver 25 Watts Suitable for street light fitting taken down vide item no 9, driver Shall Conform to Cat no S0DRIVES - 36-600-25 W of Crompton or Equivalent from Philips/Bajaj
M&L for PCC 1:2:4 type B-1 using 20 mm graded stone agrregates as in pedestal of pole/ strut and in copping including necessary form work and finishing exposed faces of concrete even and smooth using extra cement all as directed by engineer in charge .
S& F in replacement of GI steel tubing medium grade 40mm dia for laying in ground, along the pole in coping, road crossing etc for cabe protection including necessary fittings , clamps for supports, etc all as directed by Engineer in charge Make - Tata/Jindal/Surya Prakash
Supply and fix in replacement of FRP looping box of size 140 X 140 X 95 mm or nearest size with heavy duty four pole bakelite connector of 63 amps rating with terminals and connectors, MCB 6 Amps, Din Rail, GI clamps made out of GI flat of size 25mm X 3 mm channel and including providing cable glands and lugs for existing cables and making connections all as specified and directed by Engineer –in –Charge.Make - National / Sintex .
Supply and fix in replacement of FRP looping box of size 103 X 103 X 73 mm or nearest size with heavy duty four pole bakelite connector of 63 amps rating with terminals and connectors, MCB 6 Amps, Din Rail, GI clamps made out of GI flat of size 25mm X 3 mm channel and including providing cable glands and lugs for existing cables and making connections all as specified and directed by Engineer –in –Charge.Make - National / Sintex .
Taking down old unserviceable wiring cable and supply & lay 3 Core 1.5 Sq mm size multistranded copper conductor PVC unsheathed 650 / 1100 Volt Grade As per IS 694 with and including 20 mm dia PVC conduit and passing through PVC conduit with necessary saddle, clamps, bolts & nuts, copper lugs all For interconnection of cable looping box to Street Light Fitting, Post Top Lantern etc All as Directed. Make :- POLYCAB / HAVELLS/FINOLEX.
M&L for Fixing , testing of contactor ML-2, 3pole, 415 volt coil voltage 230 volt complete as in street light timer panel including removing of old unserviceable contactor Make L & T/Siemens
M&L in repairs DIN type astronomical programmable street light timer with current rating 16 amps, backup for 6 years and one change over all as directed by Engr-in - Charge. Make : Cat no TDA45163 of Indo Asian or equivalent from Legrand/L&T
Material & labour for opening cover of garden light checking connections, repacing of lamps LED tye 5 Watts, 230 volts suitable and including batten holder for garden light fitting of Make - Crompton, Bajaj, Philips
Supply and fix in replacement street light fittings in street light poles/Buildings the fitting shall be of LED type 45 Watts complete with and including drivers, pressure die cast aluminium housing, prewired complete. The fitting shalll conform to cat No - LSTS-45-CDL-1 of Crompton or Equivalent from Philips/Bajaj
Supply and fix in replacement flood light fittings in street light poles/Buildings the fitting shall be of LED type 120 Watts complete with and including drivers, pressure die cast aluminium housing, prewired complete in including additional brackets made of angle iron of size 45mm X 45mm X 5 mm for mounting the fiting in poles/steel truss etc. The fitting shalll conform to cat No -LFLN-120-CDL/60 of Crompton or Equivalent from Philips/Bajaj
Supply & fix post top lantern LED 40 watts in gate post complete including drivers, die cast aluminium housing complete including fixing bolts. The fitting shall confirm to Cat no - LPTO 40 CDL of crompton or Equivalent from Philips/Bajaj
Supply, installation, testing and commissioning outdoor LT feeder Distribution Panel suitable for 3 phase, 4 wire, 415 volts to Hz supply made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 2mm thick CRCA sheet, double door with front and back openable with locking arrangement, including bus bar having current rating of 1.5 times of incomer MCCB, including wiring a) MCCB TP 100 Amps, 16 KA 415 Volts- 1 Nos b) MCCB TP 40 Amps, 10 KA 230 Volts - 3 Nos c) MCB TPN 40 Amps, 10 KA 415 Volts - 1 Nos d) MCB SPN 40 Amps - 1 No e) LED Panel indicators for R, Y & B Phase - 1 Set
M & L for Filtration and dehydration of transformer oil using ON-LINE filtartion plant to remove moistrure and carbon contents to achieve dielectric strength of oil not less than 50KV in 2.5 mm gap, Oil samples of each transformer are to be tested before and after filtration test, results to be recorded on a printed format and also painting the date of test on the equipment with synthetic enamel paint all as specified and directed and also including disconnecting the HT and LT cables and cleaning the bus bar surfaces and reconnecting the cables by providing copper washers, bolts, nuts, replacing of silica gel breather etc all as specified and directed. Notes:- (i) Oil required for topping up for filtration will be measured and paid separately under respective item of BOQ . (ii) The quoted rates shall also be deemed to include for proper cleaning of the tank surfaces to make the same free from sludge etc. (iii) The rate is deemd to be inclusive of trasportation of contractor's own Oil filteration machine to Hut Bay
Supply only and filling of Transformer insulation oil as per IS 335-1993 having die electric strength minimum 50 KV in 2.5 mm gap for topping up in transformer, OCB, OFS etc all as specified and directed, Make: Savita/Power Oil/APAR.
Material and labour for scrapping of old paint from the exposed steel surfaces and applying two coats of Aluminium paint over a coat of Red oxide primer on 11 KV two pole structure including GOD & operating rod, greasing & applying petroleum gelly to current carrying contacts etc, complete all as specified and directed.
Supply & Lay 63 mm graded stone coarse aggregate inside GOD fencing, levelling
upply & fix PVC water tank of capacity 250 ltrs including tank nipple, hoisting in position, connecting up with pipes, securing tank acess covers
Supply and lay/fix, connect and testing steel water tubing medium grade of dia 25 mm, galvanised with screwed and socketed joints, in any length, including all fittings, ISI marked conforming to IS-1239 and fixed to wall/ceiling or laid in trenches/floors complete including taking down existing unserviceable pipe all as specified and directed by Engineer-in-charge
Supply and fix gun metal globe or gate valve of dia 25 mm with iron wheel head screwed both ends for iron pipe and fixing complete conforming to IS -778 with ISI mark grade-1 alongwith one no of union including taking down existing unservicable gate valve complete all as specified and directed
Supply & fix 25 mm dia ball valves high pressure PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and including fittings such as cockets and nipples etc including taking down existing unservicable ball valve
Supply & fix brass foot valve of 50 mm dia including making threading in suction pipes including taking down existing unservicable foot valve
Supply only Chlorine Dioxide (CLO2) (SCS10 K) for treating drinking watercomplete all as specified and directed. Make Bharati Waters
M&L for taking down of centrifugal monoblock pump set of capacity 3/5 HP, overhauling including dismantling/opening of body, cleaning of slots & body, replacing of bearing, gland packing etc, oiling, greasing, reassembling complete, painting by two coats of synthetic enamel paint, and installing and testing complete all as directed by Engineer-in-Charge. Note - Rate is inclusive of all spares required for smooth operation of the pump set.
Supplying and laying of 25 mm dia CPVC pipes SDR 11 & including Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors, including taking down of unserviceable pipe complete all as specified.
Supplying and laying of 50 mm dia CPVC pipes SDR 11 & & including Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors, including taking down of unserviceable pipe complete all as specified.
Cleaning of underground sump of capacity 10000 ltrs by pumping out water from U/G sump by pump set as directed at site and taking out the remaining water at bottom by buckets manually as required, cleaning internal surfaces of the sump with wire brush, removing scale and dirt . Taking out soil, sand and mud settled at the bottom and finally cleaning with bleaching powder and marking date of cleaning on outslide with synthetic paint and size of letters not less than 100mm all as directed by Engineer in Charge of the following Capacity
Supply & lay PPR Pipe line of dia 50 mm with fittings, including taking down of old pipe line
Supply & lay PPR Pipe line of dia 40 mm with fittings, including taking down of old pipe line
Supply and fixing Framed work such as grills, gratings, etc. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work con-forming to Fe.290.Gde-E-165PVC. (For Four Pole and Transformer fencing) including taking down existing unservicable structures any type.
Supply only Chain link MS galvanisd fencing, any size or type (For Fencing of Four pole structure and Transformer).
Taking down existing unserviceable fencing any type and fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provission of binding wire. Note :- Supply only chain link fencing will be measured and paid seperately.
M & L Brickwork with subclass ‘B’ bricks, straight or curved on plan exc 6m mean radius built in 1:6 Cement Mortar all as specified and directed including demolition of existing brick work of fencing any type.
M & L Rendering 10mm thick in CM (1:6) on fair faces of brick work or concrete surfaces and other all as specified finished even and fair without using extra cement
M&L for PCC 1:2:4 type B-2 using 40 mm graded stone agrregates as in foundation, filing and mass concrete all as directed by engineer in charge. Including demolition of existing foundation any type and removal
Supply and Fixing in repairs 3 pole MCCB 63 Amp, 415 V with rupturing capacity 16 KA complete all as specified and directed Make : Indo Asian /Havells/L&T
Supply and Fixing in reparis 3 pole MCCB 100 Amp, 415 V with rupturing capacity 16 KA complete all as specified and directed Make : Indo Asian /Havells/L&T
Supply and Fixing in reparis 3 pole MCCB 160 Amp, 415 V with rupturing capacity 25 KA complete all as specified and directed Make : Indo Asian /Havells/L&T
Supply and Fixing in reparis 3 pole MCCB 200 Amp, 415 V with rupturing capacity 25 KA complete all as specified and directed Make : Indo Asian /Havells/L&T
Supply and Fixing 2 pole pin type insulator, 11 KV for 02 mpole structure complete all as specified and directed.
M & L for carrying out routine checks of silent type DG Set of 125 KVA Stamford make alternator coupled with cummins engine, including checking of coolant level and supply and top up of colant, draining out & supply and refilling of Engine oil(Including supply of oil), replacing of fan belts, replaing of lube oil filter, fuel filter & fuel water seperator, checking of level of distelled water in battery & top up of water. Note- Make of Engine Oil, Coolant Oil, fan belt, filters etc shall be as per specified of OEM of DG set and as approved by Engineer-in-charge.
M & L for carrying out routine checks of silent type DG Set of 10 KVA Kirloskar, including checkingof coolant level supply and top up of collant, draining out supply & refilling of Engine oil(Including supply of oil), replacing of fan belts, replaing of lube oil filter, fuel filter & fuel water seperator, checking of level of distelled water in battery & top up of water. Note : (As per item No 57).
M & L for servicing of Split type Air conditioner 1.0/1.5/2.0 TR capacity of Voltas/LG make inverter type AC including taking down the out door and indoor units, takong out cooling coil and washing complete with water and caustic soda, cleaning of cooling coil, fan/blower drumand air filter with air blower, oiling greasing to mechanical parts and checking all connections of electrical parts, checking leakage in pipe line, arresting leakage in gas pipe line etc all as directed at site. Note - The quoted rate shall be deemed to be inclusive of disconnecting of copper tubing and brazing while refixing.
M & L for taking down of unserviceable capacitor 2.5 to 4 mfd for split AC 1 TR/1.5 TR/2 TR and supply & fix new capacitor of rating 2.5 to 4 mfd.
Taking down of unserviceable PC board complete of 1 TR/1.5 TR/2 TR capacity and supply and fix new PC board complete
Taking down unserviceable out door unit fan/blower fan motor of AC and fixing new blower fan motor suitable for existing 1 TR/1.5 TR/2 TR Voltas make inverter type AC of model 185VJZJR32.
Taking down unserviceable out door unit fan blade for split type AC of and fixing new fan blade suitable for existing 1 TR/1.5 TR/2 TR Voltas make inverter type Aco fmodel 185VJZJR32.
Supply & Fill refrigerant gas R32 in split type AC 1 TR/1.5 TR/2 TR complete all as specified and directed, Note - (i) Payment shall be made for Net weight of gas. (ii) The contractor shall ensure no leakage of gas
Supply & Fix Four Pole contactor 200 Amps rating, 415 Volts 50 HZ, connecting with bus bar & cables and including add on blocks taking down of old contactor of model MCX 33 of L & T or Equivalent from Siemens/ABB
M&L for earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground (earth pit not less than 2.25mtr deep below GL) with top edge of earth plate not less than 1.5 mtr below normal ground level, including provision of galvanized earth strip 25X4 mm, earth plate surrounded from all sides by with 15cm thick packed layer of charcoal dust and common salt filling in alternate layer and electrode connection by using galvanized earth strip 25 X 4 mm connected by mean of bolt ,nut,chck nut & washer of galvanised iron, provision of 40 mm dia GI pipe medium grade for protection of gi strip & 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) , type C1 chamber,ms funnel ,wire gauge, 50mmthick RCC 1:2:4 TMT bars on both ways including necessary excavation in any type of soil rturning filling in removal of surplus soil to distance n.exc 50mrts complete all as shown in electrical plat no 3 of schedule part-1 2009 all as specified and directed and testing on completion
N Rathinam
ASHOK BISWAS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .