Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.2 LAccepted-AOC H NO 29 DEVILAL COLONY TCP 2 HISAR CANTT HARYANA | HISAR | HISAR | HARYANA | 125006 | ₹21.2 L Quoted ₹22.3 L | L1 | Accepted-AOC Being L1 Bidder |
| 2 | L2₹23.5 L+₹1.1 L (5.14%)Rejected-Finance | ₹23.5 L+₹1.1 L (5.14%) | L2 | Rejected-Finance Being L2 bidder |
| 3 | Rejected-Technical | - | - | Rejected-Technical due to not enisted with required cat |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
18 Apr 2025, 6:00 pmClosed
GE (W)
GE(W) HISAR HISAR MIL STN
GE (W)/HSR-82/2024-25 REPAIR/ANNUAL MAINT OF CENTRAL AIR CONDITIONING PLANT OF DOT AUDITORIUM AND DAY TO DAY MAINT OF ELECTRIC FITTING AT ZONE A AT HISAR MIL STN UNDER GE (W) HISAR
2025_MES_701138_1
GE (W)/HSR-82/2024-25
Open Tender
Civil Works
Item Rate
270 days
HISAR
Please refer tender documents
8 documents required · 8 mandatory
₹500
GE (W) HISAR
₹60,000
GE (W) HISAR
9 Jun 2025
12 Mar 2025
21 Apr 2025
12 Mar 2025
18 Apr 2025
4 Apr 2025
13 Mar 2025 - 20 Mar 2025
20 Mar 2025
Amount
Provide annual maintenance for 2x150 TR , Model: LCW2-160xx01536201, WC R134A screw compressor type water cooled chilling machines shall check and render preventive maintenance service to all the equipment every 3 months i.e three times during the currency of the contract complete all as specified and directed. Operation Parametres : Chiller : Water Temperature IN - 54 F, Water Temperature OUT - 44 F , Fouling Factor - 0.0005 FPS Condenser : Water Temperature IN - 90 F , Water Temperature OUT - 97.5 F , Fouling Factor - 0.001 FPS IKW/TR should not exceed 0.70 at full load , COP value should not exceed as mentioned in latest ECBC guidelines. Note :- Each service will include the following deemed to be included in the quoted rate and the work shall be carried out by OEM i.e Blue Star Limited at Plant only. (a) Dismantling /transporations and refixing /installation. (b) Checking the functioning of chiller unit & It's controls and all such equipment. (c) Free replacing of defective/worn out parts with new or repaired parts for compressor/thermostat/cut outs based. (d) Repairng of equipment as listed in the equipment list at plant as the case may be. (e) Descaling of condensers with chemical replacement of pre filters based on assessment and working parameters of the plant. (f) Replenishing refrigerant gas and compressor oil in the system arising out of system defect. (g) checking of compressor for its proper working. (h) Annual pumping - down and restarting as and when required. (j) Checking of Microprocessor control panel, control boards, transducers of chiller unit for their correctness and replace if necessary. (k) Replacing of parts due to normal wear and tear.
M&L for re-winding of electric motor 15 to 20 HP, 415 volts 3 phase, 50 Hz with super enamelled copper wire of superior quality as per existing gauge incl varnishing insulating material complete and replacement of defective bearing, greasing, oiling etc incl re-assembling, transporting, fixing in position, making connection, commissioning & testing complete all as specified and directed.
Description all as per item No 2.00 above but 7.5 to 10 HP Motor.
Description all as per item No 2.00 but 3 to 5 HP Motor.
S&F in replacement of fan blade assembly suitable for 3 to 10 HP motor complete all as specified and directed.
Description all as per item No 5.00 above but for 15 to 20 HP motor.
Cleaning of sheet metal sectionalised construction draw thru type in Double Skin construction AHUs for auditorium of cooling coil & filter of AC plant MEC solution including rubbing with brush complete all as specified and directed.
S & F in replacement of V belt type A-40/1016(IS) for AHU suitable for blower motor complete all as specified and directed. Make : Fenner / Unigrip / Delta premium or equivalent.
S&F in replacement of Mercury in Glass type thermometers for condenser & chiller line of size 1/2" dia complete all as specified and directed.
S&F in replacement of proportional type cooling and heating thermostats for the various Air Handling Units complete with required control wiring complete all as specified and directed.
S & F in replacement of oil pressure transducer (sensor) for Voltas make : Micro Processor of 150 TR chilling unit complete all as specified and directed.
S & F in replacement of suction pressure transducer (sensor) for Voltas Make : Micro Processor of 150 TR chilling unit complete all as specified and directed.
S & F in replacement of discharge pressure transducer (sensor) for Voltas complete all as specified and directed. Make : Micro Processor of 150 TR chilling unit
S & F in replacement of thermostatic expansion valve for 150TR chilling unit of voltas complete all as specified and directed. Make : Sporlon/Danfoss
S & F in replacement of high flow HEPA filter in aluminium frame as per existing of size 24"x24" complete all as specified and directed. Make : Athletic or thermo dyne
S & F in replacement of butter fly valve of size 100mm ISI marked including testing complete all as specified and directed. Make : Castle / CGR
S & F in replacement of butter fly valve of size 80mm ISI marked including testing complete all as specified and directed. Make : Castle / CGR
S & F in replacement of NRV valve 100mm dia for chiller line and condenser line complete all as specified and directed. Make : Castle/ CGR
S & F in replacement of NRV valve 80mm dia for chiller line and condenser line complete all as specified and directed. Make : Castle/ CGR.
S & F in replacement of coupling tyre, type TC-011 suitable for 20 HP motor coupling with 150TR condenser pump central AC plant complete all as specified and directed. Make : Unique QE or equivalent.
S & F in replacement of MCCB with fixed thermal magnetic setting, 415 volts, rupturing cap 25KA of capacity 200 Amps 3 pole complete all as specified and directed. Make : Schneider(MG) /ABB/L&T or equivalent of makes as mentioned in Appx 'C' here-in-after.
S & F in replacement of MCCB with fixed thermal magnetic setting, 415 volts, rupturing cap 25KA of capacity 160 Amps 3 pole complete all as specified and directed. Make : Schneider(MG) / ABB/L&T or equivalent of makes as mentioned in Appx 'C' here-in-after.
S & F in replacement of MCCB with fixed thermal magnetic setting 415 volts, rupturing cap 25KA of capacity 100 Amps 3 pole complete all as specified and directed. Make : Schneider / ABB/L&T or equivalent of makes as mentioned in Appx 'C' here-in-after.
S & F in replacement of MCCB with fixed thermal magnetic setting 415 volts, rupturing cap 16KA of capacity 63 Amps 4 pole as per existing complete all as specified and directed. Make : Schneider /ABB/L&T or equivalent of makes as mentioned in Appx 'C' here-in-after.
S & F in replacement PVC/ poly carbonate type insulated connector aluminium with lugs suitable for XLPE cable size for 16 Sqmm to 50 Sqmm size complete all as specified and directed.
S & F in replacement PVC/ poly carbonate type insulated connector aluminium with lugs suitable for XLPE cable size for 70 Sqmm to 95 Sqmm size complete all as specified and directed.
M & L for painting AC plant of capacity 1 x 150 TR including preparation/scraping of old painted surface and repainting with two coats of synthetic enamel paint (superior quality) Blue colour complete all as specified and directed by Engr in charge.
S&F in replacement of shaft seal assembly as per existing (150 TR) complete all as specified and directed.
S&F in replacement of shaft seal cover plate as per existing (150 TR) complete all as specified and directed.
S&F in replacement of seal end bearing washer as per existing (150 TR) complete all as specified and directed.
S&F in replacement of seal end thrust washer as per existing (150 TR) complete all as specified and directed.
S&F in replacement Time dealy relay of range 0-30 min complete all as specified and directed. Make : L&T/ Siemens.
M & L Refrigerant gas charging all as per plant requirement complete all as specified and directed.
S&F in replacement of power contactor type MNX12 Aux to MNX 20 contact 1 No for, 415 volts 3 pole complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in replacement of power contactor type MNX25 to MNX32 Aux contact 1 No for, 415 volts 3 pole complete all as specified and directed. Make : Siemens/L&T/C&S/BCH.
S&F in replacement of power contactor type MNX 40 Aux contact 1 No for, 415 volts 3 pole complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in replacement overload relay of range 14 to 23 Amps type, complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in replacement overload relay of range 6 to 10 Amps type complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in replacement overload relay of range 3 to 5 Amps complete all as specified and directed. Make : Siemens/L&T/C&S/BCH.
S&F in replacement over Voltage relay all as per existing complete all as specified and directed. Make : Siemens/L&T/C&S/BCH.
Draining out old used oil and supply & filling new compressor oil recommended grade for Voltas make reciprocating type compressor complete all as specified and directed.
M & L for PCC 1:2:4 type B1 using 20 mm graded stone aggregate as in broken coping / Foundation including slightly rounded or chamfered complete all as specified and directed.
S & F in replacement of electric heater for heating compressor oil suitable for 150 TR compressor complete all as specified and directed. Make : L&T/GE/Schneider.
M&L for cross arms, bracing supports clamps and back plate fabricated from structural steel section including bolts, nuts, washers and welding, bending, cold or hot drilling holes for bolts,ERW pipe fittings in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint including dismantling old cross arms, bracing supports clamps complete all as specified and directed.
S&F in replacement Flow Switch suitable for 150 TR plant complete all as specified and directed.
S&F in replacement VLRP Single suitable for 150 TR plant complete all as specified and directed.
S&F in replacement MVPD Single suitable for 150 TR plant complete all as specified and directed.
Dehydration, compressor/condensor re-fixing,pressure testing,vaccumising & chiller tube repairing of condensor of 150 TR plant complete all as specified and directed.
S&F condensor safety valve suitable for 150 TR AC plant Make Voltas complete all as specified and directed.
Supply and fixing cooling coil air filter (all curtain change) of 5 micron at 99% with TEFC of AHUs of AC plant MEC solution incl rubbing with brush complete all as specified and directed.
Repairing and painting of 150TR AC Plant operating pannel such as wiring and cleaning and change the door lock, RYB light and other necessary item which is reqd on site complete all as specified and directed.
Repairing AHU door of 150 TR AC Plant & operating pannel such as wiring and cleaning and change the door lock, RYB light and other necessary item which is reqd on site complete all as specified and directed.
M&L for repair/maintenance of cooling tower of any capacity make a foundation inside of cooling tower with help of iron angle and change all UPVC pipe in any size, remove all the PVC fins as honey comb & refitted the honey comb which is workable and other new fitted complete all as specified and directed. Note: New honeycomb fins will be measured and paid seperately under the relevant item of BOQ supply only and New UPVC pipes are included in the unit rate item.
Supply only PVC fills as honey comb of size 600x300x150mm suitable for cooling tower of make 80 TR capacity complete testing of flow of water upto the requirement of temperature, limit for discharge pressure maintain complete all as specified and directed.
Taking out centrifugal mono block pump set, discharge capacity 640 GPM of 20 HP, from foundation with the help of special tools, opening the pump completely and remetling/ grinding pump shaft, replacement of defective bearing and gun metal bush, gasket packing etc, overhauling and re-assembling complete including CI welding of pump housing for fixing gland plate complete all as specified and directed.
S&F CI split gland plate capacity suitable for 5/7.5/1015/20 HP pump complete all as specified and directed.
S&F Replacement of heating strip of 3 KW capacity with stand complete all as specified and directed.
Repair a foundation of 10HP/15HP/20HP motor of any AC plant make with iron angle and fixed with nuts and bolt size of motor and make a hole in wall and fixed a metal pipe from motor to wall out side suitable for water drain system if motor gland leakage than it water go out side complete all as specified and directed.
M&L fo repair of duct remove the all cable and cleaning the dust and particle and including filling up fine river sand upto 30 cm with cables make as per existing and including refixing the iron cover complete all as specified and directed.
Supply, laying, jointing and testing XLPE insulated armoured heavy duty LT under ground electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 35 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc including taking out existing u/s cable complete all as specified and directed. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for pipe line in soft/loose soil, & getting out complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed.
M & L for sand cushioning with dry coarse sand to under ground cable 23 cm thick, 8 cm thick below the cable and 15 cm thick after laying the cable complete all as specified and directed. Note : Thickness after punning shall be considered for payment.
M & L for brick protection with old size sub class 'B' bricks laid flat , length of bricks across the route of underground cable complete all as specified and directed.
Taking down carefully copper/aluminium point wiring from existing conduit (light, fan, socket or power) complete, fittings such as switches, ceiling roses, pendants, regulator, sockets and DBs,MCBs,Sub main wiring etc) and making good disturbed surfaces of walls, floor etc of exist point complete all as specified and directed.
Taking down carefully copper/aluminium Submain wiring from battan /conduit from DBs,MCBs, etc) and making good to disturbed surfaces of walls, floor etc complete all as specified and directed.
Point wiring with 1.5 sq mm, single core ,PVC insulated but unsheathed, FRLS cable, 1100 volts grade IS -694 marked, with multistandard copper conductors and earth continuity wire with similar 1.5 Sq mm cable (incl connecting to earth dolly) drawn through in existing concealed rigid PVC conduit and conduit accessories existing concealed type in walls/ceilings and also including chnage of new sunk type pressed steel terminal box and 3 mm thick plastic laminated sheet top covers for the following all as per Engineer in charge :-
One light /bell / fan/Ext Fan point controlled by one nos, one way switch complete all as specified and directed.
One three pin 5 Amp socket outlet point on independent board controlled by one nos, one way switch on independent board complete all as specified and directed.
One three pin 5 Amp socket outlet point on same board controlled by one nos, one way switch on same board complete all as specified and directed.
Description all as per item No 67.00 above but point wiring with 2.5 sq mm single core FRLS cables and earth continuity wire with 2.5 Sq mm single core cable for one 3 pin 15 Amps socket out let point controlled by one nos, one way switch on independent board complete all as specified and directed.
M&L for Point wiring with 1.5 sq mm, single core ,PVC insulated but unsheathed, FRLS cable, 1100 volts grade IS -694 marked, with multistandard copper conductors and earth continuity wire with similar 1.5 Sq mm cable (incl connecting to earth dolly) drawn through rigid PVC casing caping accessories in walls/ceilings and also incl change of new sunk type pressed steel terminal box and 3 mm thick plastic laminated sheet top covers for the following all as per Engineer in charge :-
One light /bell / fan/Ext Fan point controlled by one nos, one way switch complete all as specified and directed.
One three pin 5 Amp socket outlet point on independent board controlled by one nos, one way switch on independent board complete all as specified and directed.
One three pin 5 Amp socket outlet point on same board controlled by one nos, one way switch on same board complete all as specified and directed.
Description all as per item No 69.00 above but point wiring with 2.5 sq mm single core FRLS cables and earth continuity wire with 2.5 Sq mm single core cable for one 3 pin 15 Amps socket out let point controlled by one nos, one way switch on independent board complete all as specified and directed.
M&L for Point wiring with 1.5 sq mm, single core ,PVC insulated but unsheathed, FRLS cable, 1100 volts grade IS -694 marked, with multistandard copper conductors and earth continuity wire with similar 1.5 Sq mm cable (incl connecting to earth dolly) drawn through and including rigid PVC conduit and conduit accessories / fittings, fixed / laid in concealed in walls and surface on ceilings(including cutting chases in wall) and also including sunk in type pressed steel terminal box and 3 mm thick plastic laminated sheet top covers for the following:-
One light /bell / fan/Ext Fan point controlled by one nos, one way switch complete all as specified and directed.
One three pin 5 Amp socket outlet point on independent board controlled by one nos, one way switch on independent board complete all as specified and directed.
One three pin 5 Amp socket outlet point on same board controlled by one nos, one way switch on same board complete all as specified and directed.
Description all as per item No 71.00 above but point wiring with 2.5 sq mm single core FRLS cables and earth continuity wire with 2.5 Sq mm single core cable for one 3 pin 15 Amps socket out let point controlled by one nos, one way switch on independent board complete all as specified and directed.
Supply & fixing switch piano 5 Amps, single pole, AC, 230 Volts, flush type, complete all as specified and directed.
Supply & fixing switch piano 15 Amps, single pole, AC, 230 Volts, flush type, complete all as specified and directed.
Supply and Fixing of Bell with Bell Push, 230 Volts, flush type, single pole complete 5 Amps, complete all as specified and directed.
Supply & fixing Socket 5A-2/3 pin, single pole, AC, 230 Volts, flush type, complete all as specified and directed.
Supply & fixing Socket 15-2/3 pin, single pole, AC, 230 Volts, flush type, complete all as specified and directed.
Sub main wiring with under mentioned runs/size of single core PVC insulated but unsheathed FRLS cable size with multi stranded copper conductors, 1100 volts grade, IS-694 marked, with the specified runs/size of earth continuity conductor of similar type cable, all drawn-through and including suitable size rigid PVC conduit and fittings / accessories, all fixed to concealed in walls/ceiling complete all as specified. (The under mentioned specified runs of single core cables and specified runs of earth continuity conductors and the relevant conduit with accessories shall be measured as one run length) in repair complete all as specified and directed.
Two runs of 6 Sq mm size main cable and one run of 6 Sq mm size earth continuity conductor
Sub main wiring with under mentioned runs/size of single core PVC insulated but unsheathed FRLS cable size with multi stranded copper conductors, 1100 volts grade, IS-694 marked, with the specified runs/size of earth continuity conductor of similar type cable, all drawn-through PVC Casing caping complete all as specified. (The under mentioned specified runs of single core cables and specified runs of earth continuity conductors and the relevant casing Caping with accessories shall be measured as one run length) in repair complete all as specified and directed.
Two runs of 4 Sq mm size main cable and one run of 4 Sq mm size earth continuity conductor
Two runs of 6 Sq mm size main cable and one run of 6 Sq mm size earth continuity conductor
Attending of complaints pertaining to faulty/Non-functional/working state of all accessories pertain to internal Electrification / through telephone or in person round the clock on detailment by MES Service centre for JCOs/ORs Md/OTM Accn of Zone A Hisar Mil Stn by deploying electrician and locating and rectifying the fault from Elect Meter/DB onwards in respect of Sub Main /Point wiring including fixtures for power and light, socket, fan, bell point including security light fitted in bldgs etc complete and carrying out repairs to the extent of disconnection and dismantling of faulty wires, battens, conduits, boxes, Main switches, MCB, DBs, and other E/M faults pertaining to particulars equipment including providing wire upto 2.00 mtr and insulatiion tape required for the rectification of defect and refixing of existing dismantling serviceable articles complete all as specified and directed. Note :-One tradesman with helper work sepately ,Zone A . All area complain register and complain slip provide by contractor seprately. If tradesman and helper not receive complain or not done complain same day including Sunday also same no. of complain recovery in done complain and tradesman/helper will not come any day than three hundred rupees recovery per day per person.one tradesman with helper provide by the contractor for night/ emergency complaints. (i) Scope of work shall include replacement of bulbs /tubes held by users which will be handed over the repair if so required. (ii) Complaint pertaining to location and rectification of fault in more than one wiring point/sub main wiring/DB etc shall be considered as one complaint. Similarly complaint pertaining to replacement of minimum three fixtures in one BK/qtr/office/bldg involving movement of electricians will also be measured and paid as one complaint. Replacement of more than three fixtures but multiple of four fixtures or part thereof in one Bk/qtr/office/bldg etc will be measured as additional complaint. (iii) The complaint slip/job card shall be prepared round the clock by the MES Staff/ Supervisor and shall be handed over to contractor’s tradesmen. Complaint slip shall be got singed by user with name, number and rank and return the same to MES staff by same day. Complaints of emergent nature e.g no light, short circuiting and earth fault etc. shall be attended, round the clock. Other complaints can be attended during normal working hours. (iv) Bldgs requiring major nature of work e.g rewiring of complete bldg or major portion shall be intimated to JE E/M and separate team shall be deployed for the work. (v) Bldgs requiring rewiring of small qty of point wiring if ordered will be measured and paid separately. (vi) Cost of work requiring replacement of other stores will be measured as supply only and paid separately. (ix) Contractor shall provide the complain slip and containing 100 pages in triplicate properly binded and complaint book as per sample on requirement basis complete all as specified and directed.
Supply only socket out let 15A, 5 pin, multipurpose type complete all as specified and directed.
Supply only sheet laminated 3 mm thick including cutting required size drilling holes for incorporating switch, socket, regulators etc. complete all as specified and directed.
Supply only of capacitor 2.5 to 3.15 mfd as per existing capacity of 240V A.C complete all as specified and directed.
Supply only piano type switch 5 Amps, S.P. one way flush type complete all as specified and directed.
Supply only bell push flush type 5 amps complete all as specified and directed.
Supply only bell ding dong complete all as specified and directed.
Supply only piano type switch 15 Amps, S.P. one way flush type complete all as specified and directed.
Supply only socket outlet 3 Pin 5 Amps Multi purpose Piano type, flush type complete all as specified and directed. .
Supply only lamp holder insulated body with back plate suitable for batten fittings complete all as specified and directed. .
Supply only fan regulator electronic dimmers,450w,250v flush type suitable for 48”/56” sweep ceiling fans complete all as specified and directed.
Supply only fan regulator Electronic step type suitable for 48/56” ceiling fan complete all as specified and directed.
M&L for metal plug and socket with MCB and steel enclosure,including 20 Amp SP MCB complete all as specified and directed.
Supply only ceiling rose three terminals, ISI Marked.including taking down old unserviceable ceiling rose complete all as specified and directed.
Supply only in repairs PVC casing and caping, 20mm width complete all as specified and directed.
Supply only in repairs PVC conduit, 20mm width complete all as specified and directed.
S&F in replacement of Wall mounted Decorative luminaire suitable for 1 x8/9 W LED B22 cap including 1 x 8/9W led bulb complete all as specified and directed.
Supply only for wall mounted LED tube light fitting 20 watts batten not less than 120 lumen/watt for surface mounted, anodized extruded aluminium housing, high transmissitivity diffuser, high lumen ouput box type fitting, 230 volts and intregrated electronic driver connector block etc with warranty option of 5 years from date of installation complete with all accessories internally pre wired and necessary mounting arrangements, provision of new 3 core multistranded copper conductor of size 23/0.193 from ceiling rose to fitting complete all as specified and as directed.
Supply and fixing of post top lantern of LED 25W with symmetrical light distribution , spun alumnium landascape luminaire with high power LEDs as light source with suitable GI tubing including all accessories complete all as specified and directed.
Supply and Fixing in replacement LED light fitting Surface/Roof mounting Round type complete 1x12 W , (Dimension(mm) for round light : Ø180x40) polycarbonate batten including LED Tube, suitable for Dot auditorium complete all as specified and directed.
Supply & fixing in replacement LED security light luminaries of capacity 30 watt, SPD -10KV internal with lense, 240 volt, ,pressure dia cast aluminium housing frame, heat resistant toughtened clear glass with frame complete with accessories , IP 66 protection, pre wired up to a terminal block and mounting attachment,including pvc connector for connection complete all as specified and directed. Make orients and its equivalent.
Supply and Fixing in replacement LED light fittings 36 watt Recess Mounting type (WARM WHITE COLOUR) with mounting arrangement (Recess suitable for, 2x2 Grid, Hanging) Sheet aluminium housing with high quality LGP and PMMA diffuser. Separate HPF driver suitable for Armstrong and grid ceilling LED 240 volt along with fixing arrangements complete all as specified and directed.
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium stranded/Solid conductor, served with inner sheathing of PVC sheathed wire, one twin core cable flat or circular of 6 sqmm complete all as specified and directed.
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium stranded/Solid conductor, served with inner sheathing of PVC sheathed wire, one twin core cable flat or circular of 10 sqmm complete all as specified and directed.
Supply & Fixing metal base for electric board with suitable screw in replacement of old unserviceable board, after change the wooden board & Hylum sheet surface will be as per existing surface, size of board will be required as per site & complete all as specified and directed.
Supply only Modular socket, 6A -2/3 pin combined 2 module as per site required & complete all as specified and directed.
Supply only Modular socket, 6A/16A -2/3 pin combined 2 module as per site required & complete all as specified and directed.
Supply only Metal flush box 6 module as per site required & complete all as specified and directed.
Supply only Metal flush box 4 module as per site required & complete all as specified and directed.
Supply only Metal flush box 3 module as per site required & complete all as specified and directed.
Supply only White cover plate with frame 6 module as per site required & complete all as specified and directed.
Supply only White cover plate with frame 4 module as per site required & complete all as specified and directed.
Supply only White cover plate with frame 3 module as per site required & complete all as specified and directed.
Supply only Modular Fan step regulator, 120W - 2 module complete all as specified and directed.
Supply only Modular switch 1 way 6A 1 module as per site required & complete all as specified and directed.
Supply only Modular switch 1 way 16A 1 module as per site required & complete all as specified and directed.
Supply only round back plate of holder plastic body complete all as specified and directed.
Supply only screw of electric board with washers size of screw 4/6 inch. suitale for hanging board complete all as specified and directed.
S&F factory made, sheet steel distribution boards, protection class IP-42 suitable for mounting MCB, DBs conforming to IS-13032, IS-8623, BS-5484 with min 200 Amps rating copper bus bar, and of the under mentioned type :-
TP & N 4 Ways (double door)
SP & N 8 Ways Double door
Supply & fixing MCBs, 10 KA rupturing capacity, IS-8828 marked, of the under mentioned type and rating and fixing in DBs (DBs Catered separately in this schedule) in repair complete all as specified and directed. Note : Make of the MCB should be the same as that of DB
TPN 63 Amp .
SPN 32 Amps .
SP 6 to 32Amps
M&L for Earthing complete with galvanised mild steel earth electrode plate 600 X 600 X 6 mm thick buried directly and vertically in ground connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion ncluding provision of earth wire protected by galvanised iron 15 mm bore medium grade pipe with all fittings from the earth electrode fixed along pole or wall with and including 25 x 6mm flat iron clamp, bolts, nuts and washers and watering pipe shall be 20 mm bore GI medium grade from top of the earth pit to top of earth plate electrode including all excavation and earth work in any type of soil and removal of soil upto 50 metre, PCC pit with pre-cast RCC cover with handle, charcoal/salt, funnel , CI frame etc complete all as specified and directed. NOTES : (i) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.00 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth wire. Any variation in length shall be adjusted through deviation order (iii) Items includes cost of 7.5 metre earth lead wire. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides.
KUNAL ENTERPRISES (BID ID -3280512)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .