Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14 LAccepted-AOC 63 2ND MAIN ROAD NGO COLONY ADAMBAKKAM CHENNAI 600 088 | CHENNAI | CHENNAI | TAMIL NADU | 600088 | L1 | Accepted-AOC Being a lowest bidder | |
| 2 | L2₹16.3 L+₹2.3 L (16.1%)Rejected-Finance 53 HOUSING BOARD COLONY PHASE II UDHAMPUR 182101 J K | UDHAMPUR | UDHAMPUR | J K | 182101 | L2 | Rejected-Finance BEING L2 | |
| 3 | L3₹16.4 L+₹2.4 L (16.8%)Rejected-Finance PLOT NO 15 JAYASURIYA STREET GANGAI NAGAR KALLIKUPPAM AMBATTUR CHENNAI 600053 | CHENNAI | CHENNAI | TAMIL NADU | 600053 | L3 | Rejected-Finance BEING L3 |
Tender Value
₹18.1 L
EMD Value
₹36,200
Closing Date
10 May 2025, 6:00 pmClosed
Shri Vishal Garg, IDSE, SE(SAG)
COMMANDER WORKS ENGINEERS CHENNAI PALLAVAN SALAI CHENNAI 600 002
INSTALLATION OF 11 KV OUTDOOR VCB RMG UNIT FOR AVAILING HT SUPPLY FROM TANGEDCO AT CDA COMPLEX CHENNAI UNDE GE CHENNAI
2025_MES_703930_1
88481/E8
Open Tender
Miscellaneous Works
Item Rate
120 days
GE Chennai
As per tender documents
8 documents required · 8 mandatory
₹500
GE Chennai
₹36,200
5 Jun 2025
8 Apr 2025
14 May 2025
8 Apr 2025
10 May 2025
22 Apr 2025
Amount
Supply, erect, testing and commissioning of HT 11 KV outdoor RMG Panel complete all as per TNPDCL specifications and comprising the following accessories complete all as specified and directed Make:ABB
(a) 11 KV, 1250 Amps, 26.3 KA drawout type Vacuum Circuit breaker with 230V AC Motor and 110V DC closing/opening shunt, aux contact - 6 NO + 6 NC - 01 for outgoing (b) 11 KV, 630 Amps, 26.3 KA Load Break switch - 02 Nos as incomers (c) Potential Transformer, fixed type, Epoxy resin cast - 3 phase of ratio 11KV/110V, Core:15VA, CL 0.2 accy - 01 No (d) Current Transformer, Epoxy resin cast - ***/5-5A, Core 1:0.2S/5V A per phase for Metering , Core 2: 5P20/15V A for protection - 03 Nos (e) Overcurrent relay - 03 Nos, earth fault relay - 01 No, Master tripping relay - 01 No (f) Digital Ammeter and Voltmeter - 01 each (g) Provision for TOD Meter - 01 No
(h) RYB phase indicator lamps, ON/OFF/TRIP/Trip CKt healthy/Spring Charged indication Lamp - 04 Nos at incomer side - 08 Nos at outgoing side (j) TNC switch - 03 Nos (k) Space heater/illumination lamp - 03 Nos (l) Powerpack - 240V AC/110V DC - 01 No (m) Test Terminal block - 01 No (n) Copper busbars of size 50 mm X 10 mm mounted on epoxy resin cast insulators - 03 sets (o) Door switch for actuated CFL for panel illumination - 03 Nos (p) LV control fuses/power and control terminals alongwith complete control wiring - 03 Nos (q) MS Sheet enclosure suitable for with IP 55 Protection - 2 for LBS and 1 for VCB
Note: The quoted rate shall deemed to be inclusive of the following : (i) All technical specification as per attached enclosure Appx 'A' (ii) Material and labour for HT KV Heat shrinkable end termination kits - 3 Nos (iii) Charges towards transportation, erecting, testing and commissioning RMG panel complete (iv) Charges towards dismantling the old existing OCB RMG unit ,transpot and depositing to TANGEDCO (v) Charges towards obtaining TANGEDCO approval and factory inspection and MRT testing complete as required and diected
vijay kumar gupta and co (BID ID -3289451)
Banyan Engineers and Contractors (BID ID -3292362)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .