Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.2 LAccepted-AOC | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹32.0 L+₹2.8 L (9.43%)Rejected-AOC | L2 | Rejected-AOC Not lowest | |
| 3 | L3₹32.0 L+₹2.8 L (9.68%)Rejected-AOC KG 115 SABIRA MANZIL HBR 2ND STAGE VENKATESH PURAM BANGALORE 560 045 | BENGALURU URBAN | KARNATAKA | 560045 | L3 | Rejected-AOC Not lowest | |
| 4 | L4₹32.2 L+₹3.0 L (10.3%)Rejected-AOC | L4 | Rejected-AOC Not lowest | |
| 5 | L5₹34.3 L+₹5.1 L (17.4%)Rejected-AOC | L5 | Rejected-AOC Not lowest |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
9 Jul 2021, 6:00 pmClosed
GE I R nd D West Bengaluru
GARRISON ENGINEER I R nd D WEST BANGALORE DRDO COMPLEX CV RAMAN NAGAR BANGALORE
REPAIRS TO MCB DBs, SUBMAIN WIRING, MAINT / RENEWAL OF EARTHING, REPLACEMENT OF CONVENTIONAL HIGH BAY LIGHT FITTINGS IN TECH AREA AND ALLIED WORKS UNDER GE (I) RndD (WEST) BENGALURU
2021_MES_439348_1
GE(I) R ND D (WEST)/BAN/14 OF 2021-22 8884E8
Open Tender
Civil Works
Item Rate
330 days
Bengaluru
Class and Category as per NIT
8 documents required · 8 mandatory
₹500
GE I R nd D West Bengaluru
₹90,000
Yes
7 Sept 2021
10 Jun 2021
15 Jul 2021
11 Jun 2021
9 Jul 2021
26 Jun 2021
11 Jun 2021 - 25 Jun 2021
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixtures and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc removing serviceable materials to store for keeping in safe custody or for offering credit (credit for all the retrieved items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc., all as specified and as directed. Note : Cost of Cutting chases, pinning in, where required for concealed conduit wiring, and making good disturbed surfaces to match with adjacent surfaces including pointing in cement mortar 1:3, girth not exceeding 15 cm on brick / PCC block masonry / concrete surfaces, shall deemed to be included in quoted rate.
Material and labour for concealed Point wiring with PVC insulated unsheathed, multi stranded copper conductor FRLS cable of size 1.5 sq.mm, 1100 grade, with PVC insulated unsheathed multi stranded copper conductor cable of size 1.5 sq.mm for earth continuity wire, drawn into and including non metallic rigid PVC conduit of suitable size, medium grade ISI marked including metal flush boxes of suitable size, modular white cover plate and provision of 3 mm thick plastic laminated sheet cover for mounting switches/ sockets etc fixed on walls/ roof surface concealed in walls including all necessary wall cutting and making good disturbed surface complete all as specified and directed for One light / fan / bell point controlled by one, one way switch 5/6 Amps complete all as specified and as directed. Note : The quoted rate shall deemed to include the cost of metal flush boxes, modular white cover plate, provision of blank plates as per requirement and making the disturbed surfaces to match with the existing.
All per Serial Item No 2 here-in-above, but suitable for 3-pin, socket outlet 5 Amps, fixed on independent board.
All per Serial Item No 2 here-in-above, but suitable for 3-pin, socket outlet 5 Amps, fixed on same board.
All per Serial Item No 2 here-in-above, but suitable for two 2-way switch, fixed on independent board.
Material and labour for, concealed Point wiring for One power point, 3 pin 15 amps socket out let 230 Volt 50HZ on Independent board with 2.5 sq.mm (nominal area) PVC unsheathed, PVC insulated, multi standard copper conductor cable of 1100 Volts, FRLS grade, single core cable drawn through rigid non metallic concealed PVC Conduit of suitable size, medium grade, ISI marked fixed on walls / ceiling / roofs along with 2.5 sq.mm cable but in green colour as continuous earthing wire and connecting to common earth dolly complete with modular white cover plate with frame and metal flush box for mounting switch socket combinations as required complete all as specified and as directed.
Supply and fix Modular Switch, One module , One way, 6 Amps, 240 Volts all as specified and as directed.
Supply and fix Modular Switch, One module , One way, 16 Amps, 240 Volts all as specified and as directed.
Supply and fix Modular Switch, 2-way, 1 module, 6 Amps complete all as specified and directed.
Supply and fix, Modular socket outlet 5 pin, 5 Amps (multi purpose), complete all as specified and directed.
Supply and fix, Modular socket outlet 6 pin, 15 Amps (multi purpose), complete all as specified and directed.
Supply and fix, Modular bell push switch, one module, single pole, 230 volts 5/6 Amps capacity all as specified
Supply and fix in repairs, Modular fan Regulator,120 W, electronic stepped type, 230 Volts 2 module, complete all as specified and as directed.
Supply and fix in repairs, Ceiling rose surface type, Bakelite, 65 x 50 mm ISI marked with three terminals all as specified and as directed.
Supply and fix in repairs, lamp holder PVC/polycarbonate type with black plate, suitable for 6 W LED lamp (including 6 watt lamp) complete all as specified and as directed.
Supply and fix in repairs, bell buzzer, working on 230 volts, single phase complete all as specified and as directed.
Taking down unserviceable sub main wiring, supply and fixing Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, multi stranded copper conductor cable, 2 runs of single core of size 10 Sq mm and one run of earth continuity conductor of size 6 Sq mm to be drawn through and including non metallic rigid PVC conduit, medium grade ISI marked conduit of 25 mm dia fixed on surface / concealed in walls / roof / floors complete all as specified and as directed. NOTE: - i) Two runs of 10 sq.mm cable, one run of 6 sq mm earth wire and one run of PVC conduit shall be measured as one length. ii) Cost of Cutting chases, pinning in, where required for concealed conduit wiring, and making good disturbed surfaces to match with adjacent surfaces including pointing in cement mortar 1:3, girth not exceeding 15 cm on brick / PCC block masonry / concrete surfaces, shall deedmed to be included in quoted rate.
Taking down unserviceable sub main wiring, supply and fixing Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, multi stranded copper conductor cable, 2 runs of single core of size 6 Sq mm and one run of earth continuity conductor of size 4 Sq mm to be drawn through and including non metallic rigid PVC conduit, of 25 mm dia fixed on surface / concealed in walls / roof / floors complete all as specified and as directed. NOTE: - i) Two runs of 6 sq.mm cable, one run of 4 sq mm earth wire and one run of PVC conduit shall be measured as one length. ii) Cost of Cutting chases, pinning in, where required for concealed conduit wiring, and making good disturbed surfaces to match with adjacent surfaces including pointing in cement mortar 1:3, girth not exceeding 15 cm on brick / PCC block masonry / concrete surfaces, shall deedmed to be included in quoted rate.
Taking down unserviceable sub main wiring, supply and fixing Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, multi stranded copper conductor cable, 2 runs of single core of size 4 Sq mm and one run of earth continuity conductor of size 2.5 Sq mm to be drawn through and including non metallic rigid PVC conduit, of 25 mm dia fixed on surface / concealed in walls / roof / floors complete all as specified and as directed. NOTE: - i) Two runs of 4 sq.mm cable, one run of 2.5 sq mm earth wire and one run of PVC conduit shall be measured as one length. ii) Cost of Cutting chases, pinning in, where required for concealed conduit wiring, and making good disturbed surfaces to match with adjacent surfaces including pointing in cement mortar 1:3, girth not exceeding 15 cm on brick / PCC block masonry / concrete surfaces, shall deedmed to be included in quoted rate.
Taking down unserviceable sub main wiring, supply and fixing Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, multi stranded copper conductor cable, 4 runs of single core of size 10 Sq mm and two run of earth continuity conductor of size 6 Sq mm to be drawn through and including rigid steel stove enameled black conduit of 32 mm dia fixed on surface / concealed in walls / roof / floors complete all as specified and as directed. NOTE: - i) Four runs of 10 sq.mm cable, two run of 6 sq mm earth wire and one run of PVC conduit shall be measured as one length. ii) Cost of Cutting chases, pinning in, where required for concealed conduit wiring, and making good disturbed surfaces to match with adjacent surfaces including pointing in cement mortar 1:3, girth not exceeding 15 cm on brick / PCC block masonry / concrete surfaces, shall deedmed to be included in quoted rate.
Taking down unserviceable FTL light fitting, Supply and fix, wall mounted LED tube light fitting with lamp, 9/10 Watt, 2 feet, with high lumen output, environmental friendly, energy efficient LED, with accessories, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, complete with diffuser, polyester louver with 9 watt LED tube & integrated electronic driver 9/10 W fitting as per cat No LHEXACP7IN1W010 of make Havells or techno commercially equivalent makes specified here-in-after complete all as specified.
Taking down unserviceable FTL light fitting, Supply and fix, wall mounted LED tube light fitting with lamp, 18/20 Watt, 4 feet, with high lumen output, environmental friendly, energy efficient LED, with accessories, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, complete with diffuser, polyester louver with 9 watt LED tube & integrated electronic driver 18/20 W fitting as per cat No LHEXACP7IN1W020 of make Havells or techno commercially equivalent makes specified here-in-after complete all as specified.
Supply only LED ceiling mounted recessed full lit luminaire with glare free uniform illumination with lamps, 36 Watt, (2 feet x 2 feet), with high lumen output, environmental friendly, energy efficient LED, electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI >= 80, with constant current driver 2.5 KV surge protection BIS certified with R number, integral drivers, prewired and connecting with 3 core 1 sq mm sheathed copper flexible cable, complete as per Cat No LCTLRNE-36-FO-CDL of make Havells or techno commercially equivalent makes specified here-in-after complete all as specified.
Supply only, LED outdoor, decorative post top lantern fitting, with lamp, 40 W, IP 65 protection, resistant to impact and corrosion, glare-free and better uniformity and swath high lumen output, environmental friendly, energy efficient LED, Class I system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH<10%, power factor ≥ 0.95, inbuilt surge protection 4 kV, colour temperature 5700 K, CRI >= 70, integral drivers having high voltage, short circuit protection and driver should be BIS certified with R number and 4 KV SPD, complete as per Crompton Cat No LPTO-40-CDL-M or techno commercially equivalent makes specified here-in-after complete all as specified.
Taking down unserviceable FTL / CFL light fitting of 36 W, Supply and fix, LED building security light fittings with lamp, 25 W, IP 65, with high lumen output, environmental friendly, energy efficient LED, street light fitting with lamps and accessories, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, fittings as per Cat No ENDURAPEARLSL25WLED757SASYTOPCMP of make Havells or techno commercially equivalent makes specified here-in-after complete all as specified.
Taking down existing unserviceable electric meters of any type, Supply and fix new electric energy meters, domestic type, 10 - 60 Amps, AC, single phase, digital type, static energy meter of accuracy class 1.0, working on 240 volts, 50 Hz, with back lit LCD display with special features like TOD, tamper logging, optical communication port & display in absence of power all as per Cat No. WM101BC7DDHBOX 10-60 Amps of L&T or other techno commercial equivalent model in Secure / HPL as approved including load test for at least 4 hours and recording the reading on hourly basis, obtaining the users signature, complete all as specified and as directed. Note: Old unserviceable electric meters shall be deposited to AGE E/M (R&D) West store yard.
Taking down unserviceable sheet metal enclosure/ DB, supply and fix, MCB DB SPN 8 way (Horizontal), double door with Sheet metal enclosure, flush mounted, prewired, 240 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respective items.
Taking down unserviceable sheet metal enclosure/ DB, supply and fix, MCB DB SPN 12 way (Horizontal), double door with Sheet metal enclosure, flush mounted, prewired, 240 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respective items.
Taking down unserviceable sheet metal enclosure/ DB, supply and fix, MCB DB TPN 4 way (Horizontal), double door, with Sheet metal enclosure, flush mounted, prewired, 415 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respective items.
Taking down unserviceable sheet metal enclosure/ DB, supply and fix, MCB DB TPN 8 way (Horizontal), double door, with Sheet metal enclosure, flush mounted, prewired, 415 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respective items.
Supply and fix, MCB SP, 240 volts, 5 to 32 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series all as specified and as directed.
Supply and fix, MCB SP, 240 volts, 40 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series all as specified and as directed.
Supply and fix, MCB SPN, 240 volts, 32 - 40 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series all as specified and as directed.
Supply and fix, MCB TPN, 415 volts, 63 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series all as specified and as directed.
Supply and fix, MCB TPN, 415 volts, 100 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series all as specified and as directed.
Taking down existing ceiling fan/exhaust fan of any sweep with blade and down rods etc from ceiling/walls by unscrewing the nut bolts, opening the split pin and keeping in safe custody repairing and re-fixing the same after repairs, complete all as specified and as directed. Note: Repairs shall be measured and paid for separately under respective items.
Disconnecting, taking down ceiling fan, with blade, inspecting motor assembly, replacing burnt out capacitors, split pins, etc, servicing, cleaning, greasing, removing all deposited materials, checking for smooth functioning, re-assembling the same complete all as specified and directed. NOTE:- Cost of PVC capacitor bracket -1 No, split pins - 6 Nos, 2.5 mfd capacitor - 1 No, shall deemed to include in this item.
Rewinding of ceiling fan motor with super enameled copper winding wire of suitable gauge after cutting and removing burnt winding, including varnishing of new winding and drying up carefully all as specified and directed.
Dismantling / opening of exhaust fan of 300/450mm sweep motor assembly inspecting all dismantled parts repairing replacing the unserviceable parts and following components with new ones including oiling greasing reassembling motor assembly all as specified and directed. NOTE:- Cost of PVC capacitor bracket -1 No, split pins - 1 Nos, & 2 mfd Capacitor - 1 No, shall be included in this item.
Rewinding of exhaust fan motor 300/450 mm sweep with super enameled copper winding wire of suitable gauge after cutting and removing burnt winding, including varnishing of new winding and drying up carefully all as specified and directed.
Material and labour for preparing old painted surfaces of ceiling fans of 1200 mm sweep, and applying spray painting with two coats of synthetic enamel paint of approved colour, including writing MES No on painted surfaces, complete all as specified and as directed.
Material and labour for preparing old painted surfaces of exhaust fans of 300 mm sweep, and applying spray painting with two coats of synthetic enamel paint of approved colour, including writing MES No on painted surfaces, complete all as specified and as directed.
Taking down unserviceable geyser of capacity 25/50 liters and re-fixing at the same locations, after painting with one coat of white paint and making it functional including replacement of cold and hot water connecting pipe, complete all as specified and as directed.
Supply and fix in repairs PVC Hot and Cold type connection pipe 15/20mm dia 450mm long with couplers and washers on both sides suitable for cold and hot water lines complete all as specified and as directed.
Disconnecting and removing the burnt cable end terminal at incoming of MCCB DB TPN / Cubical, cutting suitable length of cable of incoming cable and adjusting cable from loop, preparing cable ends of any size, crimpling aluminium lugs of suitable size, connecting back with necessary bolts, nuts, washers, etc., testing for any loose connections and making good the disturbed surfaces complete all as specified.. NOTE: The rate shall deemed to include for making hole in masonry / concrete to draw cables from loop and making good the disturbed surface matching with the adjacent surfaces, complete as per directions of Engineer-in-Charge.
Supply and fix, Aluminium lugs for aluminium conductor cables of 16 sq mm size
Supply and fix, Aluminium lugs for aluminium conductor cables of 25 sq mm size
Supply and fix, Aluminium lugs for aluminium conductor cables of 35 sq mm size
Supply and fix, Aluminium lugs for aluminium conductor cables of 50 sq mm size
Supply and fix, Aluminium lugs for aluminium conductor cables of 70 sq mm size
Disconnecting and removing the burnt cable ends in MCCB DB TPN / Cubical, taking out unserviceable burnt cable leads of any length of aluminium conductor and of any size, and providing PVC insulated 1100 V grade FR grade multi stranded copper conductor cable leads (approx 0.5 m length of 4 runs) suitable for cable of 16 Sq mm, with copper lugs of suitable size, crimped and connected to the bus bar of MCCB DB TPN/TP/FP of any capacity, with suitable nuts, bolts, washers complete including testing for any loose connection complete all as per directions of Engineer-in-Charge.
All as per Serial Item No 51 here-in-above, but for cable of 25 Sq mm
All as per Serial Item No 51 here-in-above, but for cable of 35 Sq mm
Excavation in trenches not exceeding 1.5 m deep and not exceeding 1.5 m wide and getting out in hard / dense soil all as directed.
Returning and filling in, soils, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick all as directed.
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as directed.
Material and labour for laying of burnt bricks sub class `B’ bricks of size 230 x 115 x 75 mm, laid in trenches for cable protection all as directed and specified
Screening excavated earth (passing through 12 mm square mesh), laying riddled earth in trenches for cable protection, under and above Cable all as specified in SSR Part - I (Clause No 19.75) and as directed by Engineer-in-Charge. Note : Punned thickness of riddled earth of 18 cm will be measured and paid.
Taking down existing 1100 Volts grade cable and Supply and laying new XLPE insulated cable, screened, bedded galvanized steel strip/wire armoured heavy duty with aluminium conductor of cross sectional area 10 Sq mm 2 core with cable protection works (as applicable) laid in trenches/ ducts/ fixed on pole/ wall/ laid under road / path/ culvert/ drains/ encased in pipe, including necessary lugs, jointing and testing complete all as specified and as directed. Notes :- Necessary excavation, earthwork and cable protection works will be measured and paid separately under respective items.
All as per Serial Item No 59 here-in-above, but for cable of size 3½ Core 35 Sq mm
All as per Serial Item No 59 here-in-above, but for cable of size 3½ Core 50 Sq mm
All as per Serial Item No 59 here-in-above, but for cable of size 3½ Core 70 Sq mm
Demolishing old earthing pit, and providing new earthing pit with material and labour for earthing complete with Galvanized Iron earth plate electrode 600 mm x 600 mm x 6 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to GI earth wire of 4 mm dia by means of bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 15 mm bore (light grade) connected to earthing test point all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 40 mm bore light grade GI pipe for watering funnel wire mesh, PCC chamber in cement concrete (1:3:6), type C1 , manhole cover with RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways for cover and MS frame etc., complete all as specified and as directed NOTES :- (i) The quoted rate deemed to include earth wire and protection pipe up to 7.5 metre from earth plate / earth point/test point. (ii) Earth pit shall be constructed at least 0.5 metre away from each earth chamber.
Demolishing old earthing pit, and providing new earthing pit with material and labour for earthing complete with Galvanized Iron earth plate electrode 600 mm x 600 mm x 6 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to GI earth strip of size 25 x 4 mm by means of bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 15 mm bore (light grade) connected to earthing test point all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 40 mm bore light grade GI pipe for watering funnel wire mesh, PCC chamber in cement concrete (1:3:6), type C1 , manhole cover with RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways for cover and MS frame etc., complete all as specified and as directed NOTES :- (i) The quoted rate deemed to include earth strip and protection pipe up to 7.5 metre from earth plate / earth point/test point. (ii) Earth pit shall be constructed at least 0.5 metre away from each earth chamber.
Sai Ram Builders
GS TRADERS
Srisrinivasaenterprises
Meghana and Gowda Enterprises
Pacific Enterprises
Solar Electricals and Electronics
Lucky Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .