Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹92.0 LAdmitted-Finance 19 LAKE TEMPLE ROAD KOLKATA 700029 | KOLKATA | WEST BENGAL | 700029 | -26.02% | ₹92.0 L | L1 | Admitted-Finance |
| 2 | L2₹1.0 Cr+₹12.5 L (13.5%)Admitted-Finance | -16.00% | ₹1.0 Cr+₹12.5 L (13.5%) | L2 | Admitted-Finance |
| 3 | L3₹1.1 Cr+₹18.4 L (20.0%)Admitted-Finance 3 4 JEEVAN DEEP BUILDING 10 PARLIAMENT STREET NEW DELHI 1 PH 011 43573493 9899713006 | -11.20% | ₹1.1 Cr+₹18.4 L (20.0%) | L3 | Admitted-Finance |
| 4 | Rejected-Technical OLYMPIA PLATINA PLOT NO 33B SOUTH PHASE GUINDY CHENNAI 600032 | CHENNAI | CHENNAI | TAMIL NADU | 600032 | - | - | - | Rejected-Technical All necessary documents, as per the bid conditions have not been submitted. |
| 5 | Rejected-Technical E3 172 ARERA COLONY NEAR 10 NO MARKET ARERA COLONY BHOPAL MADHYA PRADESH 462016 | BHOPAL | MADHYA PRADESH | 462016 | - | - | - | Rejected-Technical The performance of the agency in the ongoing/ existing contracts has been observed to be unsatisfactory. |
Tender Value
₹1.2 Cr
EMD Value
₹2.5 L
Closing Date
25 May 2026, 3:00 pmClosed
Superintending Engineer
O/o SE, AIIMS RAIPUR
Supply, Installation, Testing and Commissioning of Cooling Tower (02 Nos.) at Hospital Block, AIIMS Raipur
2025_IMSRP_889781_3
24/SE/AIIMS/RPR/2025-26
Open Tender
Electrical Works
Works
180 days
AIIMS Raipur
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹2.5 L
10 Jul 2026
15 Apr 2026
26 May 2026
15 Apr 2026
25 May 2026
15 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing and commissioning of Rectangular FRP Induced draft, Counter flow, Four cell, Direct/Gear driven, site erected cooling Tower of Heat Rejection Capacity - 2835600 Kcal/Hr (Capable to maximum of 3024000 Kcal/Hr) based on the parameters given and complete with PVC Fill, Louvers, Drift Eliminator , TEFC Motor, Propeller Fan(04 NOs), FRP Casin , FRP Basin, Base Frame M.S & Steel Ladder, Deflector Cowl. The Cooling Tower (CTI Certified) shall confirm to technical specifications given in the tender. The maximum allowable Noise Level at a distance of 3 meter from cooling Tower shall be less than 75 db. The cooling Tower model shall be to suit site condition and provided with suitable VFD and electrical panel. Designed Wet bulb Temp.-28.3 Degree Celcius
Water inlet/outlet Temp.-36.39 Degree Celcius /32.22 Degree Celcius
Design Flow -680 CMH
Note: The rate also includes dismantling of the existing cooling tower to be replaced. | 2 | Each | - | - |
| 2 | Supply, Installation, Testing and commissioning of "c class mild steel chilled water piping with all necessary fitting like bends,tees,reducers,sockets ,Vibrations Isolaters & pipe supports etc. .Pipe shall be conforming to IS:1239 part-1 & Part -2 and IS 3589 along with required valves (like isolation, drain, float, balancing, equalizer valve etc.for both the cooling towers) Motorised Valves with all ancillary and as per direction of Engineer Incharge. | 1 | Lot | - | - |
| 3 | Supplying, installation, testing and commissioning of M.V. cubical type totally enclosed dust and vermin proof Main Distribution Boards having 1 Incomer MCCB and Outgoing Starters for 02 Nos of Cooling Towers suitable for use on 430 V 3 phase 4 wire 50 Hz AC supply, having compartmentalized construction for different incoming/outgoing MCCBs from approved Make and separate bus bar & cable alleys, fabricated from 2 mm thick CRCA sheet steel of uniform width complete with copper bus bars, MV danger notice plate, Digital type ammeter with Ammeter selector switch, voltmeter with Voltmeter selector switch, LED indicating lamps, Interconnection with suitable capacity copper strips / rods, connection of incoming and outgoing cables with thimbles, smoke/Siemens grey colour stove enamelled painted and having following incoming and outgoing switchgears, 2 earth bolt, removable cable gland plate with spare suitable hole, wall/floor mounted, lockable using hollow standard LT Panel lock key complete as per site required or as approved by Engineer In-charge.
A. INCOMER
01 nos 250amps 25kA TPNL MCCB from Approved Make Thermo-magnetic release type with rotary handle. 01 nos Digital type single function volt meter to show 0-500V voltage with phase selector switch. 01 nos Digital type single function ameter to show amperage with phase selector switch. 03 Nos CTs 125/5 ratio 03 LED Indication Light with toggle switches
B. OUTGOING
09 nos Star Delta starter and 3 nos spare feeder for future extension. | 1 | Each | - | - |
| 4 | Supply, Installation, Testing and commissioning of Push Button Station for Cooling Tower as per required specification and direction of Engineer Incharge. | 2 | SET | - | - |
| 5 | Supply, Laying and fixing of one number 3.5 core x 185 sq.mm Aluminium Unarmoured PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade on cable tray as required. | 100 | Meter | - | - |
| 6 | Supply, Laying and fixing of one number 3 core x 10 sq.mm Aluminium armoured PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade on cable tray as required. | 500 | Meter | - | - |
| 7 | Supply, Laying and fixing of one number 10 core x 1.5 sq.mm Copper armoured PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade on cable tray as required. | 150 | Meter | - | - |
| 8 | Supplying and installation of 150 mm width X 50 mm depth X 1.6 mm thickness size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. | 150 | Meter | - | - |
| 9 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | 8 | Set | - | - |
| 10 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. | 230 | Meter | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.01 MB
BOQ_951741.xls
BOQ • 0.29 MB
NIT.pdf
Tender Documents • 1.96 MB
Corrigendum.pdf
PDF • 0.68 MB
Extension_corrigendum.pdf
PDF • 0.06 MB
Extension_corrigendum.pdf
PDF • 0.15 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .