Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.8 CrAccepted-AOC 1ST FLOOR KRISHNA TOWERS OPP TO THRIKKAKARA TEMPLE THRIKKAKARA P O COCHIN 682 021 | ERNAKULAM | KERALA | 682021 | ₹2.8 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹2.8 Cr+₹3.4 L (1.22%)Rejected-Finance | ₹2.8 Cr+₹3.4 L (1.22%) | L2 | Rejected-Finance L2 |
Tender Value
₹3.1 Cr
EMD Value
₹6.3 L
Closing Date
24 Feb 2020, 6:00 pmClosed
Asstt. General Manager (E-E)
AAI, LGBI Airport, Guwahati-781015
Operation and Maintenance of E and M and GLF installations installed in Technical Block, Terminal Building, Operational area and Nav-Aids locations at LGBI Airport, Guwahati
2020_AAI_42401_1
AAI/AGM(E-E)/NIT-30/2019-20
Open Tender
Electrical Works
Item Rate
730 days
LGBI Airport, Guwahati
Meeting the requirements given in the NIT criteria
5 documents required · 5 mandatory
₹1,120
Airports Authority of India
₹6.3 L
15 May 2020
8 Feb 2020
2 Mar 2020
8 Feb 2020
24 Feb 2020
8 Feb 2020
8 Feb 2020 - 20 Feb 2020
Amount
Operation and maintenance of all E&M installations alongwith all equipments of GLF system, LT panels, light fittings/fans, Perimeter lighting, High masts (New & old apron) installed at Technical Block/ DVOR/ DME/ Localizer/ Glide Path/ Inres / Fire section/ CISF Out post/ Hangar Building/ Runway and Operational area by engaging the manpower for carrying out preventive maintenance, attending breakdown maintenance/ complaints/ faults and taking rectification action to ensure the serviceability & satisfactory working condition of the system, maintenance of records/ documentation/ store/ dismantled materials etc. on round the clock basis on all working days including Saturdays, Sundays and holidays as per the detailed terms of special conditions, schedule of maintenance and specifications etc. complete as required.
1st Year
2nd Year
Operation and maintenance of all E&M installations of 11kV/440Volts sub-station alongwith all equipments and installations i.e. HT/LT Panels,HT Transformers, AVRs, DG sets, AMF Panels, light fittings/fans etc. at Radar building by engaging the manpower for carrying out preventive maintenance, attending breakdown maintenance/ complaints/ faults and taking rectification action to ensure the serviceability & satisfactory working condition of the system, maintenance of records/ documentation/ store/ dismantled materials etc. on round the clock basis on all working days including Saturdays, Sundays and holidays as per the detailed terms of special conditions, schedule of maintenance and specifications etc. complete as required.
1st Year
2nd Year
Operation and maintenance of all E&M installations of HT/LT electrical & mechanical installations at Outer Marker by engaging the manpower for carrying out preventive maintenance, attending breakdown maintenance/ complaints/ faults and taking rectification action to ensure the serviceability & satisfactory working condition of the system, maintenance of records/ documentation/ store/ dismantled materials/ transportation of HSD oil from AAI store to Outer Marker etc., at round the clock basis on all working days including Saturdays, Sundays and holidays as per the detailed terms of special conditions, schedule of maintenance and specifications etc.
1st Year
2nd Year
Operation and routine cheaking, cleaning and minor adjustment etc. of "Elevators & Escalators" installed at different locations of Terminal Building on round the clock basis by engaging the manpower for operation, attending complaints/faults and taking corrective action to ensure the serviceability and satisfactory working of the system on all working days i/c Saturday, Sundays & holidays complete as required as per the detailed specifications, terms and condition under this contract.
1st Year
2nd Year
Operation and routine checking, cleaning and minor adjustment of "Precision control Air conditioning plants" installed at New Rader building including maintaining required temperature by proper operation, taking follow up action for ensuring serviceability of Air conditioning plants on round the clock basis on all working days including Saturdays, Sundays and holidays as per the detailed specifications, terms and conditions under this contract.
1st Year
2nd Year
Annual inspection and servicing of oil filled transformers of following capacities and ratings including cleaning, checking and tightening of bushings, valves, flanges etc for oil leakage, replacement of gaskets if required, checking Buchholz relay contacts & their operation, checking insulation resistance of transformer winding, checking of oil level gauges, oil temp indicator & winding temp guage contacts & their operation, checking and tightening of HV/LV cable terminations and body/neutral earthing including submission of report complete as per site requirements
100KVA, 11/0.433KV
315KVA, 11/0.433KV
Dehydration of transformer insulating oil through centrifugal oil purifier/sprinkler machine and heating arrangement to attain withstand strength of 50 KV for one minutes including submission of test of breaking strength of oil report before and after dehydration etc. complete as required.
Supply and replacing the Silica gel in all type of Breathers installed in power transformers in various locations
Annual Inspection, servicing, overhauling and testing of 11KV VCB panel comprising of 05nos. VCB's (02 incomers + 03 outgoings) totally enclosed, fully interlocked horizontal draw out type 630Amps VCB breakers panel of Kirloskar make from the OEM/ Authorized dealer as per the manufacturers recommendations including calibration of all relays (O/C & E/F Numerical relay, Master trip relay, Trip circuit supervision Relay and Auxiliary relay) installed in each VCB panel, chekcing and measurement of IR values of breakers and busbars, contact resistance of breakers etc as per the manufactures recommendations and submission of calibration/ service reports etc., as required. (Supply of spares excluded)
First Year
Second Year
Visit charges for attending the breakdown maintenance for 11 KV HT panels with Kirloskar make VCBs including traveling allowances, boarding and lodging, consumables, tools and testing kit etc., as required (Supply of Spares excluded) (1 Job = 1 breakdown visit).
Annual inspection, servicing, overhauling and testing of 315 KVA LT Automatic voltage stabilizer(Make : Automatic Electric Ltd.) comprising of Auto Step Up/Down Transformer, Controller unit & Buck/Boost Transformer including required service/repair, adjustment, setting, cleaning, replacement of defective wornout parts etc. from the OEM / Authorized dealer / Specialized agency including submission of report etc complete as per site requirements. (Supply of spares excluded)
First Year
Second Year
Annual inspection, servicing, overhauling and testing of 630 Amps, 11KV RMU panel board comprising of LBS/VCB totally enclosed panel of Schneider make from the OEM/ Authorized dealer as per the manufacturers recommendations including calibration of all relays (O/L, E/F, Master trip etc.) installed in each RMU and submission of calibration/ service reports as required. (Supply of spares excluded)
First Year
Second Year
Supply and replacement of following components in the existing HT/LT Panelboards including connections, returning of dismanted items to AAI store, setting/programming of meters etc complete as required
LED type indication lamps (22.5mm) of 110VDC/230VAC (Red/ Yellow/ Green/ Amber)
LED type indication lamps (22.5mm) of 110VDC/230VAC (Blue/White)
Electrical panel door lock (Stainless steel) of various sizes suitable for existing panels
Rotary handle of MCCBs of upto 125A capacity of all makes (Extended type)
Rotary handle of MCCBs of 160A-250A capacity of all makes (Extended type)
Rotary handle of MCCBs of 315A-400A capacity of all makes (Extended type)
Supply and fixing of side hinged-door fixed with base SMC junction Box of size 250mmx200mmx100mm (Loop-in-Loop-out Box) on the GI pole with suitable size MS clamp including providing & fixing 63A, 4Pole connector for loop in & loop out to terminate 2Nos, 4 core 25 sq. mm. armoured aluminum cable, 6Amp SP MCB 'C' curve in din rail, Interconnection etc. as required. (Make: Sintex: model no. JS-JB-2520 or its equivalent)
Providing and fixing of following components for LED type continuous solar trafic Blinker light.
LED type continuous solar trafic Blinker light of Red colour with minimum 172nos. of LED suitable for operation on 12V DC supply with ON/OFF provision alongwith all accessories etc. complete as required.
12V, 26Ah battery suitable for solar trafic Blinker light with enclosures having lockable housing box etc. complete as required.
Painting of electrical panels, feeder pillar box, PAPI Light fixtures, transformer housing box etc. with one or more coats of syntehtic enamel paint of approved shade (as per ICAO standard for PAPI Light fixtures) after cleaning the rusted area, providing the mask to meters, handles, sight glass/ lens etc. and removing the same after painting complete as per actual site requirements.
Painting i/c numberingof Runway/Taxiway/ Approach light fittings with one or more coats of syntehtic enamel paint of recommended shade (as per ICAO standard) after cleaning the rusted area, providing the mask to lens area etc. and removing the same after painting complete as per actual site requirements.
Painting of existing street Light/perimeter Light poles of heights up to 6 Mtrs. with one or more coats of synthetic enamel paint / aluminium paint of approved shade after thoroughly cleaning the surface i/c numbering & Painting AAI logo on the poles.
Painting of following capacities/ratings of Transformers /LT Automatic voltage stabilizer as per direction of E-I-C with one or more coats of synthetic enamel paint of approved shade after through cleaning the surface, primer coat wherever required, providing the mask to meters, sight glass etc. and removing the same after painting etc complete as required as per site requirements.
315KVA 11/0.433 kV Transformer
100KVA 11/0.433 kV Transformer
315 KVA LT Automatic voltage stabilizer
Lettering with synthetic enamal paint of approved quality and brand with stencil of following letter size and spacing as per the direction of Engineer-in-charge at various panels / equipments etc as reqd. (Lettering of one letter/numeral is considered as 1 Each)
Upto 30mm letter height
Exceeding 30mm letter height but not exceeding 60mm letter height
Repairing of existing earth pit including providing and fixing of CI cover plate, funnel, necessary brick work, plastering & painting the masonary chamber complete as per site requirements
Providing First Aid Box as approved by St. John Ambulance Brigade/Indian Red Cross conforming to IS 2217-1963 with upto date amendements.
Detection of Cable fault in LT UG cable of rating 1.1 KV Grade 3/3.5/4 core Aluminium conductor of all sizes identifying pin point location with help of cable fault finding machine including transportation, deputing extra manpower, excavation and confirmation of cable fault but excluding cable jointing etc as per site requirement
Detection of Cable fault in HT UG cable of rating 11 KV Grade 3 core / 1 core Aluminium conductor of all sizes by identifying the fault in pin point location with help of cable fault finding machine including transportation, deputing extra manpower, excavation and confirmation of cable fault but excluding cable jointing etc as per site requirement
Hiring of Unskilled labours on day to day basis for unforeseen works like excavation, refilling, Shifting of materials, cleaning and other maintenance activities as directed by E-I-C at differenent locations of LGBI Airport etc. complete as required. (The contractor is bound to pay the minimum fair wages prevailing at the time of opening the tender and/or statutory increase in future during the entire period of the contractor by state/central govt.) (one labour per day = 1 Job)
Execution of items of schedule of rates CPWD DSR-2018 as and when required for attending breakdowns, repair & maintenance and upkeep of internal and external electrical installations as per direction of E-I-C at differenent locations in operational area/radar/outermarker/ technical building/ ancillary building etc. complete as per the special Terms and Conditions in addition to General Terms and Condition of Contract as required. The bidder shall quote the rate in INR only for the job corresponding to Rs.10,00,000/- and percentage (%) above / below shall be calculated by AAI and paid accordingly after deducting GST component from the DSR-2018 rates.
ABHISHEK ASSOCIATES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .