CWE PATIALA
HQ COMMANDER WORKS ENGINEERS BLDG No 26 NEW LALBAGH PATIALA 147001 Contact 01712200082
REPAIR MAINT OF LT DISTRIBUTION SYSTEM INCL REPAIR LT PANELS AT MIL STN DAPPAR
2023_MES_597655_1
CWE/PAT/T-08/2023-24
Open Tender
Electrical and Maintenance Works
Works
180 days
DAPPAR
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
AGE(I) DAPPAR
₹60,000
30 Jun 2023
23 May 2023
21 Jun 2023
23 May 2023
19 Jun 2023
6 Jun 2023
23 May 2023 - 5 Jun 2023
Amount
Disconnecting & taking out old unserviceable LT cable of any size all as specified and directed by Engr-in-Charge.
Supply, laying, jointing, connecting, testing & commissioning UG cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured electric power cable (heavy duty 1100 volts grade with standard aluminium conductor of cross sectional area 120 sqmm x 3.5 core all as specified and directed by Engr-in-Charge. NOTE - (a). The quoted rate is deemed to be inclusive of arranging respective shutdown, disconnection of cables, commissioning of feeder after the completion of job and inclusive of any minor spares and jobs required for the completion of the job. (b). The cost of excavation, returning, filling, removal and PCC cable covers will be measured and paid under relevant items of this schedule.
All as per ser item No 2 here-in-before but size of LT under ground cable 95 sqmm 3.5 core all as specified and directed by Engr-in-Charge.
All as per ser item No 2 here-in-before but size of LT under ground cable 50 sqmm 3.5 core all as specified and directed by Engr-in-Charge.
All as per ser item No 2 here-in-before but size of LT under ground cable 35 sqmm 3.5 core all as specified and directed by Engr-in-Charge.
All as per ser item No 2 here-in-before but size of LT under ground cable 25 sqmm 4 core all as specified and directed by Engr-in-Charge.
Excavation in trenches in soft/loose/hard soil n exc 1.5 m wide and not exc 1.5 m in depth and getting out including forming bottom to required level or slope for laying pipes / laying of cable complete all as specified and as directed by Engineer-in-Charge.
Returning filling in soft / loose soil in trenches including spreading, leveling and well ramming in 25 cm thick layers complete all as specified and as directed by Engineer-in-Charge.
Removal of surplus soil to a distance n exc in 50 m and deposited where directed at a level n exc 1.5 m above the starting point complete all as specified and as directed by Engineer-in-Charge.
Material and labour sand cushioning (dry sand) to underground cable for cable protection 23 cm thick in two layers (8 cm thick before laying of cables and 15 cm thick after laying the cable and punning down the sand to 18 cm thickness.). Complete all as specified and as directed by Engineer-in-Charge. (Note:- Only punned thickness 18 cm of sand shall be measured for payment purposes).
Material and labour precast concrete cable cover, class LV, type 1 with peak, size 250mm x 150mm x 40mm all as specified and directed by Engr-in-Charge.
Make bore to road width for providing GI pipe medium/light grade both end socketed for passing armoured cable complete all as specified and directed by Engr-in-Charge.
Material and labour for galvanized iron tubing size 40 mm bore (Light grade) with all necessary fittings laid in trenches under road crossing or fixed on poles / walls / under floors for cable protection complete all as specfied and as directed.
Material and Labour for earthing with galvanised iron earth plate of size 600x600x6mm thick buried directly in ground not less than 2.25m below normal ground level,earth plate packed on all sides with charcoal mixed with salt in alternate layers of 15 cm thickness connected by galvanised iron earth earth strip 32x6mm soldered & riveted to earth plate, galvanised iron earth strip will be provided by using 50mm bore galvanised iron pipe (light grade) earth plate to transformer body and neutral or test point of transformer, including flat iron clamp 25x3mm including bolts, nuts and washers complete including watering galvanised iron pipe 20 mm dia 'Light grade' 2.5m long the earthing includes PCC pit including necessary earth works and disposal of surplus soil to a distance not less than 50m, chamber of PCC 1:4:8 type D-2 using 40mm graded stone aggregate, coping shall be of PCC 1:3:6 type C-I using 20mm graded stone aggregate, RCC pit cover 50mm thick in 1:2:4 type B-I using 20mm graded stone aggregate, reinforced with 8mm dia @ 15cm c/c complete all as shown on sketch No 3 of SSR-I of 2009 and as specified and as directed by Engr-in-Charge.
Material and Labour earth continuity conductor GI of 32x6 mm of GI strip by means of bolts, nuts, check nuts and GI washers complete all as specified and directed by Engr-in-Charge.
Material and Labour Synthetic insulating mat (rubber matting), ISI Marked suitable for 1100 Volts electrical grade 2mX1mX2mm thick chequered top, ISI marked to be laid in front of LT panel board complete all as specified and directed by Engr-in-Charge.
Material and Labour for Danger notice boards of 1.6mm thick mild steel sheet, vitreous enamelled white,with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for LT 25x20cm size all as specified and directed by Engr-in-Charge.
Material & Labour for application of two coats of aluminium paint on steel tubular/rail pole of 9/11/13/15 M long externally after removal of old paint, rust, dust, oil, grease or any other foreign deposits by paint removers or burning off by blow lamps, cleaning with scrapers and chemicals for removal of rust for any number of coats of any width or girth incl. numbering of poles in black base & white letters paint and including. painting five no. strips upto 30 cm on bottom of pole with black and yellow colour paint alternately all as specified and directed by Engr-in-Charge
Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size upto 25 to 50 sqmm, core outdoor type and taking down fault complete all as specified and directed by Engr-in-Charge.
Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size upto 70 to 120 sqmm, core outdoor type and taking down fault complete all as specified and directed by Engr-in-Charge
Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size upto 150 to 185 sqmm, core outdoor type and taking down fault complete all as specified and directed by Engr-in-Charge.
Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size upto 240 to 300 sqmm, core outdoor type and taking down fault complete all as specified and directed by Engr-in-Charge.
Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, Supply & Fix MCCB FP, 36kA, 400 AMPS with Thermal - Magnetic Release Type Ics = 100% Icu, Adjustable Over Load setting: 0.4 -1.0 x In, Adjustable short circuit for each phase from 1.5 - 8 x In including spreader terminals . NOTE - Quoted rate is deemed to be inclusive of minor jobs and minor spares required for fitment of MCCB in the existing panel all as specified and directed by Engr-in-Charge.
Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, Supply & Fix MCCB TP, 25kA, 250 AMPS with Thermal - Magnetic Release Type, Ics = 100% Icu, Adjustable Over Load setting: 0.4 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, including spreader terminals all as specified and directed by Engr-in-Charge. NOTE - Quoted rate is deemed to be inclusive of minor jobs and minor spares required for fitment of MCCB in the existing panel all as specified and directed by Engr-in-Charge
Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, Supply & Fix MCCB TP, 25 kA, 200 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, including spreader terminals all as specified and directed by Engr-in-Charge. NOTE - Quoted rate is deemed to be inclusive of minor jobs and minor spares required for fitment of MCCB in the existing panel all as specified and directed by Engr-in-Charge
Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, Supply & Fix MCCB TP, 25 kA, 160 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In,including spreader terminals all as specified and directed by Engr-in-Charge. NOTE - Quoted rate is deemed to be inclusive of minor jobs and minor spares required for fitment of MCCB in the existing panel all as specified and directed by Engr-in-Charge
Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, Supply & Fix MCCB TP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, NOTE - Quoted rate is deemed to be inclusive of minor jobs and minor spares required for fitment of MCCB in the existing panel all as specified and directed by Engr-in-Charge
Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, Supply & Fix MCCB TP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, including spreader terminals all as specified and directed by Engr-in-Charge. NOTE - Quoted rate is deemed to be inclusive of minor jobs and minor spares required for fitment of MCCB in the existing panel all as specified and directed by Engr-in-Charge
Supply and relplace existing u/s indicating lamp LED type suitable to operate on 230 volts AC Supply of R/Y/B colour as per site requirement all as specified and directed by Engr-in-Charge.
Supply & fix in replacement Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input current measurement range 0-200 A, CT/PT site programmable including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) all as specified and directed by Engr-in-Charge.
Supply & fix in replacement Single function 3 phase LED voltmeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) all as specified and directed by Engr-in-Charge.
Supply and replace existing unserviceable CT as that of existing ratio and model suitable for 3 phase supply all as specified and directed by Engr-in-Charge.
Painting to electric control panel of E/M installations by cleaning the existing old paint with the help of mechanical tools such as wire brush, scraper and sand paper from the surface of panel and painting the prepared surface with two coat of synthatic enamel paint of approved shade over a coat of red oxide primer complete all as specified abd specified.
Repairing/servicing of APFC panel board by replacing the all defective components with new components, re-wiring, cleaning, testing, reconnecting, re-installing and commissioning the APFC panel board complete all as specified and directed by Engr-in-Charge. (a). All new components,. required for replacement shall be measured and paid separately under relevant items of schedule here-in-after however the quoted rate is deemed to be inclusive of cost of cleaning agents, grease, cable lugs, cable glands, nut/bolt and washer combination all as approved by Engr-in-Charge
Supply & fix in replacement APFC relay of 8 stage supply Voltage 415 V AC and current Input - 1A or 5 A with specs as - 3 Phase Current and Voltage measurement, PF display - 3 Digit after decimal, Individual harmonics measurement up to 31st order, Dual PF setting for Mains - DG application, Communication through Inbuilt MODBUS RS-485 Protocol all as specified and directed by Engr-in-Charge.
Supply & fix in replacement APFC relay of 16 stage supply Voltage 415 V AC and current Input - 1A or 5 A with specs as - 3 Phase Current and Voltage measurement, PF display - 3 Digit after decimal, Individual harmonics measurement up to 31st order, Dual PF setting for Mains - DG application, Communication through Inbuilt MODBUS RS-485 Protocol all as specified and directed by Engr-in-Charge..
Dismantling, supply and install, connect, test and commission of capacitor, 3 phase, Super Heavy Duty cylindrical type, self standing units, self healing property with MPP film with safety device in the form of pressure sensitive (over pressure) mechanical interrupter, 415/440V, 3 phase, 50 Hz, Capacity 5 KVAR, AC conformance to Standards IEC 60831-1 2/96, IS 13340 including testing, commisioning as in repairs complete all as specified and directed.
All as per item no 41 above but 10 KVAR all as specified and directed by Engr-in-Charge.
All as per item no 41 above but 20 KVAR all as specified and directed by Engr-in-Charge.
All as per item no 41 above but 25 KVAR all as specified and directed by Engr-in-Charge.
All as per item no 41 above but 48.50/50 KVAR all as specified and directed by Engr-in-Charge.
Supply and fix in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts suitable for 10 kVAR capacitor complete with connected switch gear/ components in various APFC panels all as specified and directed by Engr-in-Charge.
Supply & fix in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts suitable for 15 kVAR capacitor complete with connected switch gear/ components in various APFC panels all as specified and directed by Engr-in-Charge.
Supply & fix in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts and Spreader Link Kit suitable for 25 kVAR capacitor complete with connected switch gear/ components in various APFC panels all as specified and directed by Engr-in-Charge.
Supply & fix in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts and Spreader Link Kit suitable for 48.50/50 kVAR capacitor complete with connected switch gear/ components in various APFC panels all as specified and directed by Engr-in-Charge.
Supply & fix in repairs NO element complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs NC element complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs Illuminated push button- RED complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs Illuminated push button- GREEN complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs 1.1 KV current transformer of ratio 150/5 complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs 1.5 Sqmm multistranded copper FRLSH wire for control circuit complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs 2.5 Sqmm multistranded copper FRLSH wire for control circuit complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs 4.0 Sqmm multistranded copper FRLSH wire for control circuit complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs 6 sqmm multistranded FRLSH copper flexible cable complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs 10 sqmm multistranded FRLSH copper flexible cable complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs 16 sqmm multistranded single core copper conductor (Flexible) PVC Insulated Heavy Duty Industrial Cables for control circuit complete in various APFC panels all as specified and directed by Engr-in-Charge.
Supply & fix in repairs 35 sqmm multistranded single core copper conductor (Flexible) PVC Insulated Heavy Duty Industrial Cables for control circuit complete in various APFC panels all as specified and directed by Engr-in-Charge.
Supply & fix in repairs 1.5 sqmm pin type lugs complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs 6 sqmm pin/fork/round type lugs complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Supply & fix in repairs 6-32 A SP MCB, 10 kA 'C' series, 240 V AC, 50 Hz complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
(xi) Phase indication light Yellow - 01 Nos (xii) Phase Indication LIGHT Blue - 01 Nos (xiii) Control MCB 6 Amp 10 KA - 06 Nos (xiv) Current Transformer 320/5A - 03 Nos OUTGOINGS:- 50 KVAR Capacitor Bank :- (i) MCCB 125 Amp TP 25 KA - 01 Nos (ii) ON Indication Light RED - 01 Nos (iii) OFF Indication Light GREEN - 01 Nos (iv) Red Stop Push Button with block - 01 Nos (v) Green Start Push Button with block - 01 Nos (vi) MDXL Heavy Duty Capacitor 415 Volt 50Kvar*1Nos - 50 Kvar (vii) Capacitor Duty Contactor suitable for 50 Kvar capacitor, 3phase, 415volts with NO+NC Auxiliary Contacts - 01 Nos 25 KVAR Capacitor Bank :- (i) MCB 63 Amp TP 10 KA - 03 Nos (ii) ON Indication Light RED - 03 Nos (iii) OFF Indication Light GREEN - 03 Nos (iv) Red Stop Push Button with block - 03 Nos (v) Green Start Push Button with block - 03 Nos 2.5 mm air gap between testing (vi) MDXL Heavy Duty Capacitor 415 Volt 25Kvar*3 Nos - 75 Kvar (vii) Capacitor Duty Contactor suitable for 25 Kvar capacitor, 3phase, 415volts with NO+NC Auxiliary Contacts - 03 Nos
15 KVAR Capacitor Bank :- (i) MCB 32 Amp TP 10 KA - 01 Nos (ii) ON Indication Light RED - 01 Nos (iii) OFF Indication Light GREEN - 01 Nos (iv) Red Stop Push Button with block - 01 Nos (v) Green Start Push Button with block - 01 Nos (vi) MDXL Heavy Duty Capacitor 415 Volt 15Kvar*1 Nos - 15 Kvar (vii) Capacitor Duty Contactor suitable for 15 Kvar capacitor, 3phase, 415volts with NO+NC Auxiliary Contacts - 01 Nos 10 KVAR Capacitor Bank :- (i) MCB 25 Amp TP 10 KA - 01 Nos (ii) ON Indication Light RED - 01 Nos (iii) OFF Indication Light GREEN - 01 Nos (iv) Red Stop Push Button with block - 01 Nos (v) Green Start Push Button with block - 01 Nos(ii) ON Indication Light RED - 03 Nos (vi) MDXL Heavy Duty Capacitor 415 Volt 10Kvar*1 Nos - 10 Kvar (vii) Capacitor Duty Contactor suitable for 10 Kvar capacitor, 3phase, 415volts with NO+NC Auxiliary Contacts - 01 Nos 5 KVAR Capacitor Bank :- (i) MCB 16 Amp TP 10 KA - 02 Nos (ii) ON Indication Light RED - 02 Nos NO+NC Auxiliary Contacts - 03 Nos (iii) OFF Indication Light GREEN - 02 Nos
(iv) Red Stop Push Button with block - 02 Nos (v) Green Start Push Button with block - 02 Nos (vi) MDXL Heavy Duty Capacitor 415 Volt , 5Kvar*2 Nos - 10 Kvar (viiii) Capacitor Duty Contactor suitable for 5 Kvar capacitor, 3phase, 415volts with NO+NC Auxiliary Contacts - 02 Nos Air Fan 6" - 02 Nos Auxiliary contact - 10 Nos BUS BARS :- 200Amp, TPN 415Volts 3Phase 4Wire Color Coaded Aluminum busbars (for outgoings & Incomings) - 01 Set MISCELLANEOUS:- Nuts, Bolts, Washers, Ferul Numbers, Cable Ties, Tie Base, Copper PVC Control Wire, Power Wire, Copper, Thimbles, Panel Locks, I-Hooks, PVC Tape, Insulators, E-type, L-Type, Round Type, MCB Chanel, PVC Chanel, Connector Chanel, Connectors, Foam Ga - 01 Lot
Material & Labour for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415Volts 3Phase 4 Wire factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, indoor type double door LT cubical panel made out of CRCA MS sheet 1.6mm thick duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar all including angle iron base frame of 40mmx40mmx6mm. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 below nearest ground level and should be with 400 mm offsets on all 04 sides of the panel complete and should be inclusive of following fitted in accessories :- A. INCOMING - (i) MCCB 315 Amps ,415 V 4 pole 35 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 400/5A -01 Nos,Shunt Release as per OEM specifications and model - 01 Nos. B. OUTGOING - (ii) MCCB 100 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make : Cat pat No : including spreader terminals - set of 04 and direct rotary handle -02 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model - 03 Nos. (iii) MCCB 63 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model - 05 Nos. (vii) MCB TPN 63 amps- 02 nos (viii) LED indicators - R/Y/B 240 V AC - 11 Sets of three - outgoing feeders (iii) OFF Indication Light GREEN - 01 Nos (iv) Red Stop Push Button with block - 01 Nos (v) Green Start Push Button with block - 01 Nos (vi) MDXL Heavy Duty Capacitor 415 Volt 50Kvar*1Nos - 50 Kvar (vii) Capacitor Duty Contactor suitable for 50 Kvar capacitor, 3phase, 415volts with NO+NC Auxiliary Contacts - 01 Nos
(ix) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) (x) Single function 3 phase LED voltmeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable including suitable size CTs (set of 3) - 08 Nos. (Outgoing feeders) (xi) Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable including suitable size CTs (set of 3) - 08 Nos. (Outgoing feeders) (xii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 6 Nos. (xiii) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc.
All as per item no 66 above but with following specifications:-
A. INCOMING - (i) MCCB 250 Amps ,415 V 4 pole 35 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 400/5A -01 Nos,Shunt Release as per OEM specifications and model - 01 Nos. D. OUTGOING - (ii) MCCB 63 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model site programmable for measurement of V, A, PF, kW, kVA, Load hours including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) (vi) Single function 3 phase LED voltmeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable including suitable size CTs (set of 3) - 09 Nos. (Outgoing feeders) (vii) Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable including suitable size CTs (set of 3) - 09 Nos. (Outgoing feeders) (viii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 6 Nos.
Note for Item Nos 66 to 68 above:- a. Panel drawing must be approved prior to placing PO to the Panel manufacturer from the Engineer-in-Charge. b. To ensure safety, reliability and accountability of component co-ordination, all the major components such as circuit breakers, contactors and the enclosure system called for in this specification should preferably be from a single manufacturer. The OEM shall be preferably manufacturer of aforesaid components and switchgear.
Repairing/servicing of APFC panel board ranging from 150 - 200 KVAR by replacing the all defective components with new components, re-wiring, cleaning, testing, reconnecting, re-installing and commissioning the APFC panel board complete all as specified and directed by Engr-in-Charge.
All as per item 69 above but APFC panel board ranging from 100 - 150 KVAR all as specified and directed by Engr-in-Charge.
All as per item 69 above but APFC panel board ranging from 50 - 100 KVAR all as specified and directed by Engr-in-Charge. NOTE FOR ITEM No - 69 to 71 Supply of cable lugs and cable tags are deemed to be included in the quoted rates.
Supply & fix Plastic body Instrument Cooling axial fan of 120 x 120 x 38 mm size fitted complete within the panel including cutting of a suitable sized hole on the panel body and wiring with 1.5 Sqmm copper conductor cable and MCB SPN 6 Amps all complete incld disconnecting and dismantling the old one as per satisfaction of Engr-in-Charge.
Dismantling old unserviceable cable ducts from within the panel, Supply & Fix PVC cable ducts of size of size 45x30 MM including drawing existing cable through the ducts and commissioning the panel all as directed and specified by Engr-in-Charge.
Dismantling old unserviceable DIN Rails from within the panel, Supply & Fix DIN Rail for mounting of MCBs of rating 6 to 63 Amps and of poles - 2/3/4 all as directed and specified by Engr-in-Charge.
Supply & fix in repairs 63 A TP MCB, 10 kA 'C' series, 240 V AC, 50 Hzcomplete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge
Raman Electric Trading Co
HARISH SALES CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .