Executive Engineer Electrical Division-3
Executive Engineer Electrical Division-3, Siri Fort Road Behind Gargi College New Delhi-49
Supply and Replacement of Split AC with VRV/VRF System in Table Tennis Hall at NSSC Jasola.
2026_DDA_897594_1
63/EE(E)/ELD-3/DDA/2025-26
Open Tender
Electrical Works
Percentage
30 days
As Per Tender Document
Please refer Tender documents.
16 documents required · 16 mandatory
₹0
₹28,020
Executive Engineer Electrical Division-3
7 Mar 2026
9 Feb 2026
20 Feb 2026
9 Feb 2026
19 Feb 2026
11 Feb 2026
11 Feb 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed Inverter type twin Rotary/Scroll Compressor(s),minimum two compressors (with individual seperate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient. temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 KW ISEER 6.4, Capacity > 40 and <70 ISEER 6.5, Capacity ≥70 ISEER 6.6 for ECSBC+ Building) For Cooling or Heating or Both
(DSR 2025 S.N:-31.2.3 )
A) 14 HP to 22 HP | 25 | Per HP | 20,385 | ₹5,09,625 |
| 2 | Supplying, Installation, Testing and Commissioning of following minimum capacity 4 way Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX
Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration Isolation, Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as
required. The Indoor units must shut down upon receivinga singal from the BMS System/Fire Singnals. The system shall be capable to adjust air flow as per room requirement in auto mode. The cooling capacity of indoor unit will be at air inlet conditions of 27 0C DB and 19 0C WB temperature.
(Make will be same as of Outdoor)
(DSR 2025 S.N:-31.4.8 )
a)3.6 TR | 6 | Each | 44,269 | ₹2,65,614 |
| 3 | COPPER REFRIGERANT PIPING
Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
(DSR 2025 S.N:-31.14 )
a) 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 60 | Meter | 487 | ₹29,220 |
| 3.01 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2mm | 30 | Meter | 615 | ₹18,450 |
| 3.02 | 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm | 60 | Meter | 739 | ₹44,340 |
| 3.03 | 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2mm | 30 | Meter | 904 | ₹27,120 |
| 4 | Supplying, Installation, Testing and Commissioning of Y/T/Multi Joints. Joints shall be of same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs
(DSR 2025 S.N:-31.13 )
a) Indoor Units | 6 | Each | 4,535 | ₹27,210 |
| 4.01 | b) Outdoor Multi Joint | 2 | Each | 8,098 | ₹16,196 |
| 5 | Providing of anti corrision coating on existing ODU unit copmlete for weather protection on exposed copper pipe as per OEM specifications. | 1 | Job | 25,243 | ₹25,243 |
| 6 | Supplying and laying of FRLS PVC Insulated Copper Conductor, Shielded Multi Core transmission cum control cable compatible for BMS system in the existing surface/recessed PVC conduit for looping & communication between Indoor unit & Outdoor unit of VRF system complete etc. as required.
3x1.5 sqmm. | 120 | Mtrs. | 158 | ₹18,960 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.24 MB
BOQ_943628.xls
BOQ • 0.30 MB
NIT.pdf
Tender Documents • 8.74 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .