Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹50.3 LAccepted-AOC 103 1A RAJA DINENDRA STREET KOLKATA 700 005 | KOLKATA | KOLKATA | WEST BENGAL | 700005 | L1 | Accepted-AOC AOC | |
| 2 | L2₹74.1 L+₹23.8 L (47.2%)Rejected-Finance 01 BALIA BALIA SAGARDIGHI MURSHIDABAD WEST BENGAL 742237 | MURSHIDABAD | WEST BENGAL | 742237 | L2 | Rejected-Finance L2 | |
| 3 | L3₹84.2 L+₹33.9 L (67.4%)Rejected-Finance ALIPURDUAR | L3 | Rejected-Finance L3 | |
| 4 | Not Admitted-Fee/PreQual/Technical ALIPURDUAR ALIPURDUAR WEST BENGAL | ALIPURDUAR | ALIPURDUAR | WEST BENGAL | - | Not Admitted-Fee/PreQual/Technical Others-Insufficient documents |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
2 May 2023, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer PWD Cooch BeharElectrical Divis
Executive Engineer PWD Cooch Behar Electrical Division
WBPWD/EE/CED/e-NIQ-45/22-23
2023_WBPWD_486150_1
WBPWD/EE/CED/e-NIQ-45/2022-23
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Alipurduar
please refer tender documents
6 documents required · 6 mandatory
₹80,000
Yes
Executive Engineer PWD Cooch BeharElectrical Divis
12 Sept 2025
2 Mar 2023
5 May 2023
2 Mar 2023
2 May 2023
14 Mar 2023
10 Mar 2023
Amount
Condensor Unit for 16.5 TR capacity system- SITC of 16.5 TR Capacity Microprocessor based air cooled Condensing Unit Eco friendly refrigerant (R 32 R410A/R407C),thermastatic expansion valve, multiple scroll/screw compressor, arrangement for operation with Dx type AHU, and suitable for operation on 415+ / -10% Volt, 50Hz, 3 PH AC supply with adequate auxilary protection like oil heater with thermostat for prevention of ingress of liquid refrigerent in the compressor piston chamber, over current, HP/LP Cut outs, Power contactors & control logic circuit for periodic operation of working & standby Condenser fans, Compressors and matching condensing units. Outdoor Air cooled Condenser unit shall comprise multi row Copper coil with Aluminium fins and Axial fan as required housed in a sheet metal chamber with adequate ventilation as OEM standard. (Make:General/ Hitachi / Voltas/ Daikin/ Bluestar/Carrier/ Mitshubishi Electric) [3W+1S] No extra shall be payable for refrigerant gas & transportation/ shifting work.
Floor Mounted Outdoor type Air Handling Unit - SITC of site assembled type modular double skinned construction with continuous insulation with thermal break. The AHU enclosure's outer & inner Skin layer of 0.6 mm or higher & outer skin has to. be polymer coated and insulation panel should be made of thermal break profile - PUF insulation with thickness of at least 40mm or better. The AHU should have Heat Recovery Wheel for extrating@ 2100 CFM stale air with the arrangement of VCD and injection of fresh air @ 1400 CFM with VCD and mixing chamber for return air and fresh air with 03 (Three) stage filtration system (Prefilter having efficiency (EU - 4/MERV7) 90% down to 10 micron, Fine Filter having efficiency 99% down to 3 micron (MERV-14 (Make - FMI/ Spectrum/ Thermi) and HEFA filter MERV-17 0.3 Micron for both Inlet & Outlet including UV lamp of suitable rating for each of the air-suction & discharge of condition space as well as injection of fresh air and emmission of stale air as per direction of EIC). The AHU Coil to be with hydrofolic coating. The AHU Fan assembly should be either motor directly coupled with Impeller or Belt driven as per OEM standard suitable for air velocity range 7.3 - 8.2 ft./Sec through the multi-layer 12 mm - 19 mm dia Copper tubes with Alluminium Fins (as per OEM standard). There should be AHU fans of Forward/ Backward Curve, with discharge not less than 6600 CFM, compatable for 415V, 50 Hz supply continuous duty Class IE 1 (Make for Fan Unit - Nicotra/ Kruger/ Caryaire) (Make for Motor - Crompton / Kirloskar/ NEC/ ABB/ Siemens). Similar arrangement should be made for Heat Recovery Wheel. External Static pressure will be within 10 - 20 mm Wg. (Make: Zeco / System Air/ Edgetech) (AHRI/EUROVENT CERTIFIED)
Supply and fixing of UVC EMIITTER for the above fan's for prevention of growth of microbes.The minimum UV intensity in the coils shall be 700-800 UW-SEC/CM2. The unit shall be UL.Listed (UL-1995) to be fitted inside Air distribution ducting system with suitable support arrangement, as per direction of EIC. (Make-Philips Signify/ALFAA/RULS/AERO PURE)
SITC of Hard Drawn Copper refrigeration pipe line for Suction & Discharge with Cu. Brazing joints & necessary supports & brackets of different sizes in accordance with the required ODU pipe size. (Make-NIPPON/HITACHI-RYOKU/MANDEV)
Supply and fixing of necessary electrical arrangements of Air Conditioning Units, P,VC insulated FRLS grade Copper cable for connection betweeen indoor and outdoor units, 1.1 KV grade. 7 core x 1.5 mm^2 (Finolex/Polycab/Havells/RR Kabel)
4 core x 2.5 mm^2 (Finolex/Polycab/Havells/RR Kabel)
4 core x 6 mm^2 (Finolex/Polycab/Havells/RR Kabel)
Supply & fixing of dia UPVC drain pipes with all necessary hanging arrangements. 32mm Dia (Make-Supereme/Oriplast/Filolex)
Supply & Fixing of class-VIII grade (120GSM) confirming to IS -277 & Supply Air duct along with necessary support, flanges etc. as required and as per IS - 655 standards of following gauges (Make-Tata/Sail/Jindal) For 18 SWG
For 20 SWG
For 22 SWG
Supply and fixing acoustic lining of supply air duct and plenum with 10mm thick open cell Nitrile rubber (Class-O) of density 140Kg/cum-160Kg/cum insulation with cadmium plated nuts, bolts, stick pins, CPRX compound etc. completed as per direction of EIC (Make- Accroflex/ K-flex/ Armacell).
Supply and fixing Heat Retardant closed cell Class'O' 19mm thick Nitrile Rubber insulation with AI Foil Faced Outside Supply Air duct. (Make-Armacell/K-flex / Accroflex)
Supply & Fixing of Liner type AI Powder Coated Continuous Supply air Grill with VCD. (Make- Premire/ Systemair / Air Enterprise/ Caryaire)
Supply & Fixing of Liner type Al Powder Coated Continuous Return air Grill without VCD. (Make-Premire / Systemair / Air Enterprise/ Caryaire)
Supply & Fixing of Fusiable Link Fire Damper, Galvanized Steel Sheet with 125 GSM Zink Coated, Certified by CBRI ( U-555, 1995) with minimum fire rating not less than 120 min, must be Fusiable Link Spring with 74°c Temerature rating U1 Listed. (Make- Greenheck/ Systemair / Air master/ Caryaire)
SITC of heavy duty anti vibrational pad to protect the system from any kind of unwanted vibration.
Supply & Fixing of G.l Cable tray 300mm x 50mm x 1.25 mm
Supplying, fabrication & fixing 03 Nos. M.S. Angle/M.S chanel of size (75 mm x 75 mm x 6mm) for placing the outdoor unit of ductable split AC incl. drilling 05 nos holes in each Angle including cutting holes into the wall & grouting the same (1:1 ½ :3) etc for Air Conditioning Units.Supplying, fabrication & fixing 4 Nos. M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm)& ISA 50X50x6 mm for making Base Frame table type for installation of incl. drilling 2 nos holes in each channel.
Supply & fixing covering the outdoor duct with 3 mm thick ACP board (MAKE- Aludecor / Urobond or others reputed make) incl. AL channel & complete with linkages, levers, fittings, supports, all accessories any other item required to make the system complete to cover the outdoor ducts (both return & supply) as per direction of EIC.
S & F of Nitrile rubber insulation ceiling top of thickness 19mm with Aluminium foil faced with help of Adhesive and Anchor fastener with Al. strip of 19 mm width. (Make- Accroflex/K-flex/Armacell)
S & F of Non return damper incl. necessary fixing materials.
Supply, Installation, Testing and Commissioning of wall mounted weather proof cubical type LT distribution control panel fabricated from sheet steel comprising with following accessories incl. Internal wiring , earthing & painting.
a) MCCB suitable rating as incomer & outgoing as per the ratings of AHU motor and Heater & ODU.
b) DOL/SD starter as per HP ratings.
c) Terminal block for power distribution.
d) Contactor, auxiliary contractor, over load relay with inbuilt single phasing protection & interlocking arrangement. (AHU to ODU).
e) Phase indicating lights and indicating lights for ON, OFF & TRIP status.
g) Wiring for microswitch for auto operation of fans during emergency/in case of fire and opening/closing of fire dampers.
h) One DC Relay for sensing Fire Detection system.
i) Danger Board.
M/S DAS ENTERPRISE
BAPI ELECTRICAL WORKS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .