Tender Value
₹72.4 L
EMD Value
₹1.4 L
Closing Date
11 May 2026, 2:00 pmClosed
JITENDER KHURANA
Gurugram University Gurugram
SITC of VRV ACs for mini auditorium and offices of Deptt in Admin Block at Sec 87 GUG
2026_HRY_518562_1
2026F203EA20 4EBF 4114 9CFD FE50ECE6EE421857GGU
Open Tender
Civil Works
Works
70 days
Manesar
2 documents required · 2 mandatory
₹5,000
Yes
₹1.4 L
Yes
29 Apr 2026
29 Apr 2026
11 May 2026
29 Apr 2026
11 May 2026
29 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
2 TR or 2.5 HP (or above) 4 - way Cassette Unit
Make:- Daikin/Toshiba/Mitsubishi Electric | 1 | Nos. | 56,113 | ₹56,113 |
| 2 | Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature
3 TR or 4.0 HP (or above) 4 - way Cassette Unit Make:- Daikin/Toshiba/Mitsubishi Electric | 27 | Nos. | 62,708 | ₹16,93,116 |
| 3 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications
9.5 mm dia (3/8) (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Make:- Rajco/Mandev/Maxflow | 205 | Metre | 472 | ₹96,760 |
| 4 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications
12.7 mm dia (1/2) (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Make:- Rajco/Mandev/Maxflow | 85 | Metre | 592 | ₹50,320 |
| 5 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications
15.86 mm dia (5/8) (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Make:- Rajco/Mandev/Maxflow | 295 | Metre | 836 | ₹2,46,620 |
| 6 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications
19.1 mm dia (6/8) (OD) (hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Make:- Rajco/Mandev/Maxflow | 8 | Metre | 870 | ₹6,960 |
| 7 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications
22.2 mm dia (OD) (7/8) (hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Make:- Rajco/Mandev/Maxflow | 195 | Metre | 1,026 | ₹2,00,070 |
| 8 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications
28.58 mm dia (11/8) (OD) (hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Make:-Rajco/Mandev/Maxflow | 92 | Metre | 1,412 | ₹1,29,904 |
| 9 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications
34.9 mm dia (13/8) (OD) (hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
Make:- Rajco/Mandev/Maxflow | 7 | Metre | 1,971 | ₹13,797 |
| 10 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications
41.3 mm dia (15/8) (OD) (hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
Make:- Rajco/Mandev/Maxflow | 110 | Metre | 2,523 | ₹2,77,530 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.07 MB
BOQ_597451.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .