Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.9 LAccepted-Finance | L1 | Accepted-Finance TECHNICAL AND FINANCIALLY QUALIFIED | |
| 2 | L2₹11.1 L+₹12,034 (1.10%)Accepted-Finance | L2 | Accepted-Finance TECHNICAL AND FINANCIALLY QUALIFIED |
Tender Value
₹11.5 L
Closing Date
20 Nov 2021, 12:00 pmClosed
OFFICE OF EX. ENGINEER KPDCL DIV.SHOPIAN
OFFICE OF EX. ENGINEER KPDCL DIV.SHOPIAN NEAR DEGREE COLLEGE SHOPIAN
IMPROVEMENT OF ELECTRICAL INFRASTRUCTURE BY VARIOUS CREATIONS OF TRANSFORMERS AND IMPROVEMENT OF HT/LT NETWORK AT VARIOUS VILLAGES IN DISTRICT SHOPIAN AS PER ENCLOSED SBD UNDER BACK TO VILLAGE 3rd AND PRI GRANTS ON PARTIAL TURNKEY BASIS
2021_PDD_147342_1
EDS/ETENDER/82 OF 2021-22 DATED.10-11-2021
Open Tender
Electrical and Maintenance Works
Item Rate
30 days
UNDER JURISDICTION OF KPDCL DIV.SHOPIAN
Stamped signed copy of SBD ENIT Confirming TANDC
Contractor REG. card pan Card
valid GST reg. WITH GST CLEARANCE UPTO LAST QUARTER
bid security declaration format as EMD.
BID DOC COST AS TR OR GR
LABOUR LICENSE
ALL DOCS
BOQ
8 documents required · 8 mandatory
₹1,000
EXECUTIVE ENGINEER KPDCL DIVISION SHOPIAN
Exempted
23 Nov 2021
10 Nov 2021
20 Nov 2021
11 Nov 2021
20 Nov 2021
12 Nov 2021
11 Nov 2021 - 19 Nov 2021
Amount
Supply, Transportation, Installation, testing & commissioning of 63 KVA 11/0.433 KV 3 phase 50 Hz outdoor type Dyn-11 oil immersed, ONAN cooled Aluminium wound step down Energy efficient level 2 Transformer conforming to IS: 1180 (Part 1) 2014 ammended upto date with first filling of oil conforming to IS : 335 of 1983 with latest amendments.
Supply, Transportation ,Installation,testing & commissioning of 25 KVA 11/0.433 KV 3 phase 50 Hz outdoor type Dyn-11 oil immersed, ONAN cooled Aluminium wound step down Energy efficient level 2 Transformer conforming to IS: 1180 (Part 1) 2014 ammended upto date with first filling of oil conforming to IS : 335 of 1983 with latest amendments.
Loading,Transportation, Errection, testing & commissioning of ST poles 9 mtr long 410-SP-33 with base plate and cap (Poles shall be supplied by deptt)
Loading,Transportation, Errection,testing & commissioning of ST poles 8 mtr long 410-SP-15 with base plate and cap (Poles shall be supplied by deptt)
Supply, Loading,Transportation,Laying, stringing, tensioning and binding of ACSR 0.03 weasel including pretenioning for removal kinks, fixing of Hardware fittings
Supplying and erection of GI channel/GI angle cross arms including fixing GI channels ( 100x50x6mm) / (75x40x6 mm) / angles(50x50x6 mm) with 50X8 mm back clamps without drilling/punching holes in the poles.
Supplying and erection of GI Channel “V’ cross-arm (75 x 40x6mm) with GI Angle Pole Top Bracket (50x50x6 mm) including back clamps of 50X8 mm for fixing V-Cross arm and pole top bracket without making holes in the ST pole as per REC standard for single pole structure.
Providing & fixing of 11 KV pin insulator Complete (Polymer )5 KN With Pins
Providing & fixing of 11 KV GO AB Switch 200A alogwith Handle and other accessories
Providing & fixing of 11 KV LA SET 9 KVA ,10 KA,LA WITH ,Polymer Housing Station Type
Providing & fixing of 11KV D.O FUSE SET 3 Phase 400 Ampere ,Polymer
Supply and installation of 11 kV Disc Insulators (polymer) Complete with fitting( 45 KN)
Supply and fixing of LT Fuse set complete job
Supply anfd Fixing of Shackle Insulators Porcelein (16 KN) alongwith GI Mukhi Clamps (50* 6 mm) for LT Shackle Insulators with to be fixed withpout drilling/punching of Poles on ST POLES
Providing & fixing of PVC Cable 185 mm sq Single core
Providing & fixing of PVC Cable 50 mm sq Single core
Providing & fixing of Alumunium Thimbles of sizes
Providing & fixing of Nut & Bolts GI
Providing & fixing of SL CLAMP (25, 63 KVA) HD
Supply and painting 1 coat red oxide paint and 2 coats of al (@ 1 ltr/pole red oxide paint and 1 ltr/pole aluminium paint)
Supplying and erection of Danger Plates with clamps with writing in English and Regional Language
Supply and fixing of anti-climbing GI Barbed wire binding with Clamps at a distance of 30 to 40 cm at a height of 3.5 to 4 m from ground level. At-least 2 kgs GI barbed wire(12 SWG) is to be used per pole for the purpose.
Supply and laying of Cement bottoming 1:2:4 mix as per REC standards 0.45 cum/pole including muffing 20 cm above ground level plaster and curing of concrete in size of 600x600x1700mm for refilling the pit (the leftover pit after concreting to be filled with soil and boulders) NOTE: Please refer Pole drawings for details
Supply and fixing of LT line spacers: 4 Wire 3 Wire
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Supplying and fixing of pole Earthing Complete by GI Spiral Earthing, 8 SWG 115 turn coil earthing as per REC J-1 drawing
Pre and post photography of works/spots alongwith geo tagging. (per site 4 photographs)
Identification of assets by marking of Transformer with white paint & marking of poles with Black paint at a height of 2.40 mtr from ground level. (Note : Mention Name of Scheme , Implementing Agency (JKPDD), Year of Implementing (2021-22)
southern
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .