Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 145 1 0 NEAR OLD LIC SHIV NAGAR VILLAGE TOWN MODIPURAM CITY MEERUT MEERUT UTTAR PRADESH 250110 INDIA | MEERUT | UTTAR PRADESH | 250110 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
Tender Value
₹11.8 L
EMD Value
₹11,800
Closing Date
24 Jan 2022, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC MUZAFFARNAGAR
NEAR 132 KV SUB STATION BHOPA ROAD MUZAFFANAGAR
WORK TENDER
2022_UPTCL_674163_1
ETC MU T 142 2021 22
Open Tender
Electrical Works
Item Rate
45 days
THANABHAWAN
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
EE ETD MUZAFFARNAGAR
₹11,800
2 Feb 2022
10 Jan 2022
24 Jan 2022
10 Jan 2022
24 Jan 2022
10 Jan 2022
90 days
Amount
Schedule Q-1 (Construction of 132 KV T/F Bay)
Erection of main and Aux. structure consisting of ATM, DKR, ABR, AXM, BTM, YMM, XPM, BTI, BCT, ALP, BBL, etc. including all allied works complete in all respect. Department shall provide each and every nuts and bolts of the structure. The work shall be strictly carried out as per drawing & technical specification.
Erection of equipments as per instruction manual of various equipments and technical specification including shifting of material equipment from store to erection site including all other associated work with the help of crane which will be provided by the contractor at his own cost for completion of the job satisfactorily:-
145KV CB with structure
145KV BUS/Line Isolator
145KV Tandem Isolator
145 KV T/F C&R Protection Panel
145 KV CTs
120 KV Post Insulator
Apex Energy meter panel
36 KV VCB with Structure
36 KV Bus Isolator
33 KV CT & PT Junction Box
132 KV CT Junction Box
Inter connection of equipment with specified conductor with 132 KV Main & Transfer bus including cutting bending of conductor & jumpering clamping as per drawing & technical specification to complete the 132 KV Bay in all respect.
Stringing and proper sagging of new overhead 132KV Jack bus of 63 MVA 132/33 KV T/F of three phases with ACSR Panther Conductor for approx. 60 mtr span. The work involves cutting of conductor, making of bus bar of suitable length, fitting of Tension fittings, hoisting of 70 KN disc Insulator etc. and stringing. All material shall be supplied by the department free of cost and work also include shifting all material from store to site in switchyard and all other associated works to complete the job satisfactorily.
Stringing and extension of 33KV Main Bus Section (R,Y,B phases) with ACSR Twin Moose Conductor 30 Mtr. span. The work involves cutting of conductor, making of bus bar of suitable length, fitting of Tension fittings, hoisting of 70 KN disc Insulator etc. and stringing. All material shall be supplied by the department free of cost work also include shifting all material from store to site in switchyard and all other associated works to complete the job satisfactorily.
Connecting of U shape jumper R,Y,B phase of 33KV Main Bus of ACSR twin Moose, work includes jointing of ACSR Moose conductor below the gantries with help of suitable PG clamps and spacer and cutting of conductor as required and all other associated works to complete the job satisfactorily.
Shifting of 10 MVAR Capacitor bank-I main gantry including dismantling of 02 No. CCM and 01 No. CGM and 33 KV Jack Bus of 10 MVAR Capacitor bank-I and then erection of 02 No. CCM and 01 No. CGM at new foundation. Work also includes stringing of new 33 KV Jack Bus of 10 MVAR Capacitor bank and Inter connection of equipments (CT,Isolator etc.) with new bus including cutting, bending of conductor & jumpering clamping along with all other associated works to complete the job satifactorily as per drawing & techinical specification,
Laying of 40 mm size MS round bar blow 800mm from ground level including cutting, straightening, welding, painting of joints, excavation of trench its back filling and all other associated work to complete the job satisfactorily.
Fabrication of 3 meter long electrodes with MS Rod having 150mm long conical shape and then its piercing vertically inside the ground with 800mm below ground level and its welding with main earthmat including cost of consumable materials, men and T&P excluding the cost of 40mm MS round.
Earthing of substation structure and various equipment and cable racks etc. with already laid earthmat laid 800mm below ground by various size MS flat. Including excavation and back filling of earth after completion of work, straightening, bending, cutting, welding and drilling holes including painting of MS flat with one coat of red oxide and two coat of Bus green paint above ground and in trenches and one coat of red oxide and two coat of black bituminous paint of best quality on all underground joints for proper completion of work.
Laying and dressing of control cable in trenches after removal of trench covers as per cable schedule including clamping with 25x3mm Al. strip and G.I. Nut and Bolts including cutting, peeling of the control cable.
2x2.5 Sq. mm
4x2.5 Sq. mm
6x2.5 Sq. mm
Termination of cables as laid above as per cable schedule (provided by contractor) including making necessary holes in panel base plate or junction box as per site requirement providing & fixing of cable gland of appropriate size. Supply & providing ferules on each core of cable and its termination and other associated work to complete the work (Glands will be provided by the Deptt. free of cost.)
Earthing of 132 KV LAs with 75x10 mm M.S. Flat after making rectangular configuration along with Six Nos. (3 meter Length) 40 mm dia. M.S. Electrodes as per drawing as per technical specification.
Earthing of 33 KV LAs with 50x6 mm M.S. Flat after making rectangular configuration along with Four Nos. (3 meter Length) 40 mm dia. M.S. Electrodes as per drawing as per technical specification.
Schedule Q-2 (Installation of 63 MVA T/F )
Shifting/Dragging of New 63 MVA 132/33 KV Transformer from existing place to plinth up to 20Mtr. distance including turning to tank if required (Distance up to 20 Mtr.) including all T&P and work required to complete the job satisfactorily.
(a) Additional shifting 30 mtr @ 5mtr per Job
Complete erection of 63 MVA T/F by erection of radiators, conservator tank, all bushing, their turrets connecting all pipe line, cooling fans, motor driver mechanism of tap changer, RTCC panels, oil pumps and associated oil pipe lines etc. to complete the job stifactory including first filling of oil the topping of Transformer oil (Not circulation) in tank, radiators, oil pipe lines, conservator tank etc. and other associated works for satisfactorily complection of work. No department crane/ T&P shall be provided.
Cable termination from RTCC, Marshaling box of 63 MVA T/F & connecting the cable in 63 MVA to RTCC, Marshaling box, DM panel after ferruling and redressing and all other associated works to complete the job satifactorily as per drawing & techinical specification,
Centrifuging of complete T/F oil in T/F by connecting centrifuging pipes circulating the T/F oil through centrifuging machine to be provided by the contractor and taking the BDV value of the oil periodically till the required value is achieved as per direction of supervising engineer. The work includes all the work related to centrifuging the oil and filling the oil in T/F and tank (Approx. 25 KL)
Earthing of T/F body, MB, OLTC DM box, RTCC panel HV and LV LA at two points using 75x10/50x6mm M.S flat and 40 mm M.S rod after making delta formation with 3 M long electrodes.
A . Making of delta earthing for 63 MVA T/F as per norms of UPPTCL.
Jumpering of transformer from HV side with single Panther and LV side with double zebra/Moose complete up to 33 KV main bus.
Schedule Q-3 Material (Supply)
Supply of bolted type tension fitting for ACSR twin Moose conductor without turn buckle for 33 KV Main bus suitable for each disc string 10 Nos. Disc insulators with hardware fitting D-shackle, Socket Ball Hook, Yolk plate etc, as per standard technical specifications.
Supply of bolted type tension fitting for ACSR twin Moose conductor with turn buckle for 33 KV Main bus suitable for each disc string 10 Nos. Disc insulators with hardware fitting D-shackle, Socket Ball Hook, Yolk plate etc, as per standard technical specifications.
Supply of bolted type tension fitting for ACSR single panther conductor without turn buckle for 132 KV Jack bus suitable for each disc string 10 Nos. Disc insulators with hardware fitting D-shackle, Socket Ball Hook, Yolk plate etc, as per standard technical specifications.
Supply of bolted type tension fitting for ACSR single panther conductor with turn buckle for 132 KV Jack bus suitable for each disc string 10 Nos. Disc insulators with hardware fitting D-shackle, Socket Ball Hook, Yolk plate etc, as per standard technical specifications.
Supply of three bolted type P.G. clamp made of alu. Alloy LM-6 suitable for Panther to Panther conductor.
Supply of four bolted type P.G. clamp made of alu. Alloy LM-6 having 04 Nos. bolts suitable for Moose to Panther conductor.
Supply of four bolted type P.G. clamp made of alu. Alloy LM-6 having 04 Nos. bolts suitable for Moose to Moose conductor.
Supply of Two ‘U’ type bolted type suspension fitting assembly made of alu. Alloy LM-6 complete with socket eye, ball link, Anchor nut, spring and plain washer suitable for ACSR Panther conductor for 70 KN insulator, as per sample.
Flexible copper Bond made of electrolytic tinned copper rope of size 37/7/0.457 having length 550mm with a nominal tolerance of ± 2.5% Tinned copper lugs shall be pressed jointed to both end of the copper bond as per standard technical specifications.
Hot dip galvanized perforated cable troy 18 SWG having width 75mm as per standard technical specification.
Hot dip galvanized perforated cable troy 18 SWG having width 150mm as per standard technical specification.
Supply of bimattalic 132 KV Bus/Line Isolator Clamp suitable for single panther conductor made of Allu. Alloy LM-6, with nut, bolt & washer, as per sample.
Supply of bimattalic 132 KV CT Clamp suitable for single panther conductor made of Allu. Alloy LM-6, as per sample.
Supply of bimattalic 132 KV CB Clamp suitable for single panther conductor made of Allu. Alloy LM-6, nut, bolt & washer, as per sample.
Supply of 33 KV Bus Isolator Clamp suitable for twin moose conductor made of Allu. Alloy LM-6, with nut, bolt & washer, as per sample.
Supply of 33 KV CT Clamp suitable fortwin moose conductor made of Allu. Alloy LM-6, as per sample.
Supply of 33 KV CB Clamp suitable for twin moose conductor made of Allu. Alloy LM-6, nut, bolt & washer, as per sample.
Supply of 120 KV LA Clamp suitable for single panther conductor made of Allu. Alloy LM-6, nut, bolt & washer, as per sample.
Supply of 30 KV LA Clamp suitable for single panther conductor made of Allu. Alloy LM-6, nut, bolt & washer, as per sample.
Supply of 33 KV PT Clamp suitable for single panther conductor made of Allu. Alloy LM-6, nut, bolt & washer, as per sample.
Supply of Bus Post Clamp for single panther conductor made of Al. Alloy LM-6.
Supply of 132/33 KV CT Junction Box hut type size 80x40x25 cms made of 18 SWG MS Sheet duly painted provided with non-disconnecting type terminal connector, standard make, as per sample.
Supply of 02 Bolt 250 mm spacing, spacer for twin moose conductor as per technical specification.
SHIVAM ENGINEERS
M/s S.S. Refregeration
Meena Elect & Engg. Works
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .