Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹3.8 L
EMD Value
₹5,000
Closing Date
7 Apr 2020, 2:00 pmClosed
SE ETC Shahjahanpur
Electy Trans Circle Shahjahanpur
Replacement of Gasket of 160MVA Transformer I (EMCO Make) at 220KV S/S Shahjahanpur under ETD Shahjahanpur
2020_UPTCL_450195_1
146 ETC(S)/2019-20
Open Tender
Electrical Works
Fixed-rate
60 days
Shahjahanpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹885
A/c No. 10998697090 IFSC Code No. SBIN0003085.
₹5,000
11 Jul 2020
20 Mar 2020
7 Apr 2020
20 Mar 2020
7 Apr 2020
20 Mar 2020
20 Mar 2020 - 6 Apr 2020
Amount
The following works are to be carried out for Replacement of Gaskets with appropriate sizes for OLTC, PRV, Radiators, Tertiary Bushings etc of 220/132KV, 160MVA T/F-I (EMCO Make) at 220KV S/S Shahjahanpur along with other associated Works including all cost of Men, Materials, Misc. Consumables, Hydra, T&Ps etc. required for proper completion of work as per Technical Specifications & direction of the Supervising Engineer as per details below :
Dismantling of HV side Jumpers from Bushings with Single ACSR Moose Conductor, associated Terminal Connectors, P.G. Clamps etc.
Dismantling of LV side Jumpers from Bushings with Twin ACSR Moose Conductor, associated Clamps etc. to connect with all associated Equipments in between.
Draining out of half (approx. 23KL) old T/F oil from the radiators and main tank of 160MVA T/F-I (EMCO Make) and filling into the empty T/F oil drums at 220KV S/S Shahjahanpur.
Providing & Fixing of new Gaskets of appropriate sizes for OLTC, PRV, Radiators, Tertiary Bushings etc. by due Cutting & Fabrication out of Rubberized Cork Sheet Gaskets of of Konica / Torborze / Nu-cork make excluding main tank.
Filling of fresh Transformer Oil from T/F Oil Drums in 20KL capacity Oil Tank (approx. 23KL) and then Centrifuging of the Transformer Oil by Ultra High Vacuum Oil Filtration Plant till the Required Value is Achieved including shifting of 209 Litres capacity oil drums from stacking place to working site.
Filling & Topping Up of Centrifused Transformer Oil in Main Tank, Radiators, Conservator Tank etc. Centrifuging / Dehydration of the complete Transformer Oil of 160MVA T/F-I by Ultra High Vacuum Oil Filtration Plant after Connecting the Centrifuging Pipe with Transformer Tank to Oil Filtration Plant including Taking the BDV Values of Oil and IR Values of the Transformer Bushings, Periodically (every 2 hrs.) till the Required Value are Achieved.
Jumpering of HV side Bushings with Single ACSR Moose Conductor, associated Terminal Connectors, P.G. Clamps etc.
Jumpering of LV side Bushings with Twin ACSR Moose Conductor, associated Clamps etc. to connect with all associated Equipments in between.
Meena Elect and Engg Works
Perfect Power Transformer Associates
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .