| Sl No | Description | Qty | Unit | Spark Electrosystems L1 | Power Engineering Corporation L2 | Naren Electric Co L3 |
|---|---|---|---|---|---|---|
| 1.00100 KVA Transformers | ||||||
| 1.01 | i) Overhauling of 100 KVA Transformers: (2 nos)
ii) Replacement of new breather along with Silica gel & accessories, Drain plugs, oil indicator, all gaskets of transformers etc.
iii) arresting overall oil leakages.
iv) Supply & filling up of oil as per IS 335 specification (Qty- 490 liters for two transformers)
v) Testing and rectification of Earth Pits. (15 nos)
vi) Painting of Transformers. (2 Nos.)
Testing of 100 KVA Telawane make Transformers.
i) Transformer Turns Ratio (TTR)
ii) Winding Resistance
iii) Insulation Resistance test of H.T & L.T winding
iv) Magnetic Balance
v) Vector Group
vi) Excitation with reduced voltage
vii) BDV measurement of oil | 2 | JOB | 81,000 ₹1,62,000 Lowest | 82,750 ₹1,65,500 | 86,500 ₹1,73,000 |
| 2.00HT, LT and APFC panel | ||||||
| 2.01 | Preventive maintenance of 11KV RMU Panels along with VCB Breakers.(3 nos) (ABB Make). The job includes cleaning & servicing of cable chamber. Cleaning & Improvement of IR Value of Insulators, CTs, Lubrication of mechanism, checking Electrical/ Mechanical operational trials, minor rectifications, general upkeep & all the associated works, Relay testing of HT panels
Preventive maintenance of main L.T. panel including servicing of switches, cleaning & lighting of busbars, Providing electrical insulating safety mat for 440 volts LT panel, cable connections & general upkeep.
Preventive maintenance of APFC panel. The Job Includes replacement of capacitors in APFC panel. servicing of switches, cleaning & tightening of busbar, cable connections checking of all the capacitor and general upkeep and report the condition of contactors. | 1 | JOB | 87,300 ₹87,300 Lowest | 88,500 ₹88,500 | 92,000 ₹92,000 |
Tender Value
Refer Docs
EMD Value
₹3,000
Closing Date
2 Apr 2026, 4:00 pmClosed
AE Tulsi WTP
Office of the Deputy Hydraulic Engineer Bhandup Complex Brihanmumbai Municipal Corporation, Administrative Building, 2nd floor, Bhandup Complex Water Treatment Plant Durgah Road, Khindipada, Mulund West, Mumbai 400082
Servicing, Overhauling and Testing of HT, LT substation panels, switchgears, transformers and APFC panel at Tulsi Water Treatment Plant, Bhandup Complex.
2026_MCGM_1286124_1
DyHE/B.C./25/80/ODN
Open Tender
Electrical and Maintenance Works
Item Rate
61 days
Dy.HE.Bhandup Complex
Please refer Tender documents.
2 documents required · 2 mandatory
₹430
₹3,000
30 Jun 2026
17 Mar 2026
7 Apr 2026
17 Mar 2026
2 Apr 2026
17 Mar 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1100 KVA Transformers | |||||
| 1.01 | i) Overhauling of 100 KVA Transformers: (2 nos)
ii) Replacement of new breather along with Silica gel & accessories, Drain plugs, oil indicator, all gaskets of transformers etc.
iii) arresting overall oil leakages.
iv) Supply & filling up of oil as per IS 335 specification (Qty- 490 liters for two transformers)
v) Testing and rectification of Earth Pits. (15 nos)
vi) Painting of Transformers. (2 Nos.)
Testing of 100 KVA Telawane make Transformers.
i) Transformer Turns Ratio (TTR)
ii) Winding Resistance
iii) Insulation Resistance test of H.T & L.T winding
iv) Magnetic Balance
v) Vector Group
vi) Excitation with reduced voltage
vii) BDV measurement of oil | - | JOB | 1.25 | - |
| 2HT, LT and APFC panel | |||||
| 2.01 | Preventive maintenance of 11KV RMU Panels along with VCB Breakers.(3 nos) (ABB Make). The job includes cleaning & servicing of cable chamber. Cleaning & Improvement of IR Value of Insulators, CTs, Lubrication of mechanism, checking Electrical/ Mechanical operational trials, minor rectifications, general upkeep & all the associated works, Relay testing of HT panels
Preventive maintenance of main L.T. panel including servicing of switches, cleaning & lighting of busbars, Providing electrical insulating safety mat for 440 volts LT panel, cable connections & general upkeep.
Preventive maintenance of APFC panel. The Job Includes replacement of capacitors in APFC panel. servicing of switches, cleaning & tightening of busbar, cable connections checking of all the capacitor and general upkeep and report the condition of contactors. | - | JOB | 10 | - |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
equotationTenderDocument.pdf
Tender Documents • 0.65 MB
BOQ_2213801.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .