Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹63.1 LAccepted-AOC 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹63.1 L Quoted ₹63.2 L | L1 | Accepted-AOC L1 |
| 2 | L2₹70.7 L+₹7.5 L (11.9%)Rejected-AOC | ₹70.7 L+₹7.5 L (11.9%) | L2 | Rejected-AOC L2 |
| 3 | L3₹75.9 L+₹12.7 L (20.1%)Rejected-AOC I 910 JAHANGIR PURI NEAR BY ANAND MAYA HOSPITAL NORTH WEST DELHI DELHI 110033 UDYAM DL 06 0040830 | NORTH DELHI | DELHI | 110033 | ₹75.9 L+₹12.7 L (20.1%) | L3 | Rejected-AOC L3 |
| 4 | L4₹77.7 L+₹14.5 L (23.0%)Rejected-AOC | ₹77.7 L+₹14.5 L (23.0%) | L4 | Rejected-AOC L4 |
| 5 | L5₹1.2 Cr+₹55.2 L (87.4%)Rejected-AOC NATIONAL TOWER 5TH FLOOR SCO 89 DSC RANJIT AVENUE AMRITSAR 143001 PUNJAB | AMRITSAR | AMRITSAR | PUNJAB | 143001 | ₹1.2 Cr+₹55.2 L (87.4%) | L5 | Rejected-AOC L5 |
Tender Value
Refer Docs
EMD Value
₹1.4 L
Closing Date
7 Jun 2021, 6:00 pmClosed
CWE AF Bhisiana
HQ CWE AF Bhisiana-151201
SPECIAL REPAIR OF CENTRAL AIR CONDITIONING PLANT AT AF STATION SIRSA
2021_MES_440396_1
CWE(BHI)/SIR-08/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AF Station Sirsa
As per NIT
6 documents required · 6 mandatory
₹1,000
Yes
GE (AF) Sirsa
₹1.4 L
Yes
23 Jun 2021
4 May 2021
9 Jun 2021
4 May 2021
7 Jun 2021
25 May 2021
4 May 2021 - 17 May 2021
Amount
DOUBLE SKIN AIR HANDLING UNITS WITH 25 MM THICK CFC-FREE PUF INJECTED INSULATION PANEL, 10 MICRON PRE-FILTERS Replacement in repairs of double-skin type horizontal, floor- mounted, top discharge air handling units given below having corrosion resistant extruded aluminum hollow profile , heavy gauge galvanized steel channel base frame, 25 mm double skin panel with pressure injected CFC & HCFC free PUF with 'k' value of 0.02 W/°C m & density 40 kg/cum, pre-coated pre-plasticized galvanized outer and inner skin 0.60mm thick, air-tight casing using gaskets and self-adhesive tapes, AMCA certified energy efficient fans with double inlet double width backward curved impellers for high static pressure mounted on luminal extruded slide rail base frame, chilled water coils with combination of 6 rows deep,Hot water Coil with 4 rows deep & Dehumidifier coil with 2 Rows deep with anti-corrosion Aluminum fins, PVC Nylon hinges & handles, view port and marine lamp, limit switch, SS-304 drain pan, 10 micron pre-filters, inspection windows/doors, supply/return air dampers, complete all as specified and directed. Note:- Necessary civil work viz. PCC foundation for placement of AHU, etc. shall be covered in the scope of work. The AHU shall be as as per the approved particular technical specifications and the following design criteria. (a) Suitable DIDW backward fan with AMCA certified blower having outlet velocity not exceeding 9.2 m/s. (b) 4 Pole, TEFC, high efficiency, squirrel cage induction motor drive having BHP rating 20% higher than the peak capacity, suitable for 415 V ±10%, 50 Hz, 3-Phase AC power supply. (c) V-belt drive assembly with pulleys, belt, guard, etc., double canvass connections with zip to discharge duct/plenum, etc. (d) 50 mm thick, washable HDPE, 90% down 10 micron pre-filters, filters, fixing framework, hinge type access doors, etc. (e) 6 row deep chilled water coil ,4 row deep hot water coil & 2 row deep dehumidifier coil section with aluminum fins and copper tube tested on 21 kg/sq cm with SS sandwiched drain tray, etc.
Shed No 538 & 540 (14500 CFM; 80 mm WG static pressure)
Shed No 541 & 542 (4500 CFM; 80 mm WG static pressure)
PAN TYPE HUMIDIFIER Replacement in repairs of ultrasonic humidifier with below specification i. Complete package with all plumbing and electrical works done and factory tested. ii. Flying water fog having water particle as small as 1-5µ is produced. iii. Waiting time for humidity creation is maximum up to 3 Minutes. iii. Instantaneous humidity available with just a press on start button. iv. Level of accuracy achieved in humidity control is 92-97%. Safety Feature i. Reliable Piezo transducers duly interlocked with level sensors. ii. Level switches for upper and lower water level. Stops working when water level is too low. iii. Water overflow protection. iv. Water and air filter assembly. v. Solenoid operated water makeup connection.
Humidifier of capacity 42KG/HR ( For shed no 538 & 540)
Humidifier of capacity 18KG/HR for (Shed no 541 & 542)
CONDENSER WATER PIPING Replacement in repairs of MS ERW Class 'C' condenser water piping of following size with all necessary fittings i.e. bends, tees, reducers, flanges, structural support, wooden blocks, air-purge valves, drain-valves, etc. including two coat of enameled paint over one coat of red oxide primer, as required all as specified and directed.
BUTTERFLY VALVE Replacement in repairs of PN 1.0 rated short & long body type butterfly valve of following size designed, manufactured and tested as per IS: 13095 (1991), suitable for isolation and throttling services, having Cl body & dis SS AISI 304 disc seal, CS clamping ring and SS AISI 410 shaft and flange drilling standard end connection with accessories etc. as required all as specified and directed.
Y-STRAINER Replacement in repairs of Y-type strainer with Cl/MS body of following size, bolted cover, flanged ends, basket of brass/ bronze/ SS wire mesh complete with flanges, nuts-bolts, gaskets and flange drilling standard end connection with accessories etc. as required all as specified and directed.
BALANCING VALVE M&L for 2-way globe type S-1710 DZR brass variable orifice balancing valve having brass body of following size, EPDM body/bonnet O-ring, steel retaining clip, brass adjustable stop, brass stem, brass bonnet, SS cone retaining nut, EPDM disc O-ring, handwheel, test point for 240 PSI non-shock cold working pressure and maximum temperature 250 ° F at 240 PSI, flow measurement accuracy ±5% all complete as specified and directed.
FLOW SWITCH: Replacement in repairs of paddle type Water Flow Switch.
DRAIN PIPE Replacement in repairs of UPVC pipes and fittings of following size, resistant to chemical & electromechanical corrosion, conforming to EN 1452-2, having specific gravity 1.43, shore hardness 70 ° C to 90 ° C, tensile strength 500 kg/sqcm, bending strength 950 kg/sqcm, modulus of elasticity 3.2 X 10 kg/sqcm and dielectric strength > 40 kV/mm complete with accessories etc. as required all as specified and directed.
CHILLED / HOT WATER PIPING Replacement in repairs of MS ERW Class 'C of following nominal sizes of chilled/Hot water piping with all necessary fittings i.e. bends, tees, reducers, flanges, structural support, wooden blocks, air-purge valves, drain-valves, etc. duly insulated thick closed cell elastometric nitrile rubber with aluminum foil laminated on one side of minimum 45 Kg/cum density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class ‘ O ’ insulation applied by suitable rubber based adhesive confirming to standard OEM specifications, complete including repairing of damage to building etc. all as specified and directed. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
125 mm- 25 mm thick.
100 mm - 25 mm thick.
80 mm- 25 mm thick.
65 mm- 19 mm thick.
50 mm- 19 mm thick.
40 mm- 19mm thick.
32 mm - 19 mm thick.
Y-STRAINER Replacement in repairs of Y-type strainer with Cl/MS body of following size , bolted cover, flanged ends, basket of brass/ bronze/ SS wire mesh complete with flanges, nuts-bolts, gaskets and flange drilling standard end connection with accessories etc. duly insulated to the same specifications as the connected piping, as required all as specified and directed.
BUTTERFLY VALVE M&L for PN 1.0 rated short & long body type butterfly valve of following size designed, manufactured and tested as per IS: 13095 (1991), suitable for isolation and throttling services, having Cl body & disc, SS AISI 304 disc seal, CS clamping ring and SS AISI 410 shaft and flange drilling standard end connection with accessories etc. duly insulated to the same specifications as the connected piping, as required all as specified and directed.
BALANCING VALVE M&L for Balancing type, PN 1.6 rated of following size, balanced/high range ability control valve duly insulated to the same specifications as the connected piping as per following specification. Nominal pressure PN16 Medium Temperature -10oF~ +110oF Maximum Body Material IS:210, FG 220 CI Stem Material ASTM A276,GR SS 410 Disc Material Stainless steel Disc Hand Wheel Cast Iron Leakage Rate No visible leakage Medium Type Water Flange standard ISO7005-1 (GB/T 9113) Shell Test pressure 24bar Seal Test pressure 17bar.
3-WAY TEMPERATURE CONTROL VALVE M&L for cast iron 3-way mixing valve of following size, suitable for operation upto 10 bar, with electronically operated actuator for AHUs. Water flow through the valve shall be regulated by rotation of brass slipper between the main and the bypass ports; it shall be possible to manually rotate the brass slipper through 360 ° and interchange the main and the common ports, to facilitate installation at site. All internals of the valve shall be rust-proof and the 'O' ring shall be of elastomeric insulation. The valve actuator shall be of electronic type with DC motor, the actuator's angle of rotation shall be 90°, it shall be without any limit switches and shall be overload-proof. It shall have an indicator to indicate the position and push-button to disengage the gear train for manual operation including duly insulated to the same specifications as the connected pipe, as required all as specified and directed.
BALL VALVE Replacement in repairs of ball valve 25 mm NB & manufactured as per IS: 9890 (1981) and tested as per BS 6755 Part- 1, having floating type three piece design, CS body, SS- 304 ball, PTFE seal/packing/gasket, CS fasteners and lever and screwed /socket weld end connection with accessories etc., as required all as specified and directed.
12 mm Ball.
25 mm Ball.
32 mm Ball.
AUTO-AIR-VENT Replacement in repairs of Automatic air-vent having 12mm end connections.
PRESSURE GAUGE Replacement in repairs of 100 Dia dial type pressure gauge along with syphone , ball cock etc.
TEMPRATURE GAUGE Replacement in repairs of Temperature gauge.
Replacement in repairs of Digital type thermostat for temperature display and control.
Replacement in repairs of Digital type Humidistat for Humidity display and control.
AIR DISTRIBUTION (GALVANIZED STEEL SHEET DUCTING) Replacement in repairs of site/factory fabricated galvanized steel sheet (G.S.S.) square/rectangular ducting for supply/return air, fabricated from galvanized steel sheet, having zinc coating of 120 gm/sqm total on both sides complete with neoprene rubber gaskets, elbows, splitters, vanes, supports to installed /hanging the duct with suitable size of SS hole fastener etc as per IS: 655/1963 with required scaffolding work to install the ducts at site of following sheet thickness complete all as specified and directed. Note for ducting work: (i) Necessary cutting of existing walls/prefabricated sheet for passing/installation of duct and making good as per existing as per site requirement including necessary material required for completion of the work shall be including in the rate quoted by the contractor. Nothing extra payment is admissible on the account. (ii) The duct work shall be as per IS-655. (iii) The Galvanized steel sheet for duct work shall conform to class viii with zinc coating of 120 gm/sq mtr as per IS-277(2003). iv) The contarctor shall design the ducting layout to meet the desired air flow rate matching with CFM of new AHUs and submit the shop drawings of ducting layout for the approval of GE before execution of work.
24 Gauge.
22 Gauge.
20 Gauge..
18 Gauge.
FIRE DAMPER Replacement in repairs of following size of fire damper complete with smoke detector/thermistor, fusible link etc. and actuator as required for operation. The fire dampers shall be spring activated on melting of fusible link having melting point 67.13° C. The fire damper shall be located in the SA/RA ducts at all fire rated crossover (shafts, walls, etc.). The control panel shall be located in such a way that the reset can easily be done. These combination smoke and fire dampers shall be interlocked with the building management system for the fire detection or HVAC and shall trip/close in the event of fire/smoke in the respective zone. Fire damper shall be tested as per ULL- 555 and certified by CBRI. The fire-damper shall be of at least 120 minutes fire-rating as per the approved particular technical specifications and shall meet the following design criteria: (a) Bare fire dampers with 400 mm sleeve. (b) Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position. (c) Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers. (d) Sealing any openings around the sleeve of the fire dampers with approved fire sealant as per the recommendations of the manufacturer and specifications.
Motorized, spring return type, combination fire and smoke damper as described in above
Actuator electrical spring type, remote indication of the fire damper position as described in item No 21.00 above and as specified.
Control panel of actuator as described in item No 21.00 above and as specified.
ACOUSTIC INSULATION Replacement in repairs of 15mm thick Class O open-cell engineered nitrile rubber foam acoustic insulation having good sound absorption, damping and barrier properties, antimicrobial product protection, thermal conductivity, as per EN 12667, not exceeding 0.047 W/mK at 20° C, density 140-180 kg/cum and conforming to class 1 rating for surface spread of flame in accordance with BS 476 Part 7 & UL 94 (HB, V-0). The acoustic insulation material shall be free of dust and fibre; it shall pass fungi/mould resistance as per DIN EN ISO 846 method A and bacterial resistance as per DIN EN ISO 846 method C and air erosion resistance test in accordance to ASTM Standard C 1071-05 without any laminate or covering (section 12.7) from an independent accredited testing agency, complete all as specified and directed.
THERMAL INSULATION Replacement in repairs of closed cell elastomeric nitrile rubber with aluminum foil laminated on one side, having thermal conductivity not exceeding 0.037 W/mK at mean temperature of 20° C as per EN 12667, moisture diffusion resistance factor or ‘µ’ value of minimum 7,000 for base insulation material without the foil as per EN 12086, fire performance such that it passes Class O as per BS476 Part 7 for surface spread of flame and also fire performance of V0, HB as per UL 94, 1996, density without the foil between 40 to 55 kg/cum. The insulation material shall be FM (Factory Mutual) USA approved and dust & fiber free. The Aluminum foil shall be 60 microns thick and its weight shall be 193 gsm as per EN ISO 2286-2, tensile strength 90 N / 15 mm as per EN ISO 527-3 with elongation > 10% as per EN ISO 527-3, complete for following thickness of insulation all as specified and directed.
19 mm thick thermal insulation.
SUPPLY/RETURN AIR DIFFUSERS/ GRILLS Replacement in repairs of removable supply/return air diffusers/ grilles of extruded aluminum sections duly powder coated with volume control damper, complete all as specified and directed.
18 G galvanized sheet steel volume control duct damper
VARIABLE FREQUENCY DRIVE M&L of following Variable Frequency Drives with IP 55 enclosures and mains disconnect switch comprising of the following: (a) Built in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the Variable Frequency Drive. (b) Built in EMC filters (electromagnetic compatibility filters) for restriction of conducted emissions to comply with 61800:3 (un restricted distribution) :2004 Category C 1 (50 meter). (c) Three feedback PID controller having capability to simultaneously accept 3 feedback signals from temperature sensors or pressure sensors for process optimization and accordingly control the speed of the AHUs or pumps. (d) Integral graphical keypad.
Variable frequency drive (VFD) of power size 10 kW.
Variable frequency drive (VFD) of power size 5.5 kW.
ELECTRICAL CABLES Replacement in repairs of XLPE cable of following cross sectional area insulated, screened, PVC bedded, galvanized steel wire or strip armoured electric power cable (heavy duty) with aluminum/Copper stranded conductor 1100 volts grade, laid in trenches, passing through ducts/pipes, fixing along poles, complete all as specified.
4 Sqmm x 4 Core - Copper.
2.5 Sq mm x 3 Core - Copper Flexible.
M & L for GI strip of size 25 mm x 3 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed.
M & L for GI wire of size 8 SWG as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed.
Supply and fixing of perforated Hot Dipped Galvanized Iron cable tray made out of 2.0 mm thick galvanized iron sheet of following size cable tray with perforation not more than 17.5% including all accessories i.e bends, coupler, cable tie, joined with connectors, suspended from the ceiling with G.I. suspenders, G.I. bolts & nuts, etc as required, complete all as specified and directed .
150mm x 50mm.
300mm x 50mm.
Replacement in repairs of Chiller (Model No XWC4S-052A ) Evaporator - part code HEDX-BCH013. Scope of work is including dismantling of existing evaporator and fixing of new.
Replacement in repairs of Cooling tower (Model No 6125- 125 TR) Motor.
Replacement in repairs of HP/LP switch of chiller Model No -XWC4S-052A - Blue Star.
Replacement in repairs of crank case heater of Chiller Model No -XWC4S-052A - Blue Star.
Supply and charging R-22 refrigerant along with nitrogen pressure testing , flushing of system if required.
Wiring of Chiller safety controls & calibration by authorized OEM(M/s Blue Star ltd) person.
Replacement in repairs of Compressor of chiller Model No - XWC4S-052A - Blue Star.
Replacement in repairs of LWT Sensor of Chiller Model No XWC4S-052A Blue Star.
Carefully taking down/dismantling of existing , AHU, ducting and all other connected items and accessories and deposit it in MES Yard including making good of disturbed surfaces. Note for Item 40: (i) Removing existing false ceiling frame/grid, tiles for ducting work and refixing of false ceiling and tiles after ducting work is deemed to be included in quoted rates. (ii) Any damage to false ceiling and tiles is to be make good by contractor.
M/S N.K BUILDERS
SATISH AND CO
HVAC Engineering Co
NAFREF ENGINEERS PVT LTD
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .