Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.9 LAccepted-AOC 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | L1 | Accepted-AOC Lowest Bidder. | |
| 2 | L2₹4.0 L+₹11,771.40 (3.05%)Rejected-Finance ATURIA BADURIA NORTH 24 PARGANAS PIN 743427 | BADURIA | NORTH 24 PARGANAS | WEST BENGAL | 743427 | L2 | Rejected-Finance L2 | |
| 3 | L3₹4.1 L+₹28,375.56 (7.35%)Rejected-Finance | L3 | Rejected-Finance L3 |
Tender Value
Refer Docs
EMD Value
₹8,100
Closing Date
17 Feb 2025, 11:00 amClosed
Assistant Engineer, P.W.Dte., B.M.C. ESD
Office of Assistant Engineer, P.W.Dte., B.M.C. ESD
Electrical Installation Work for Proposed Construction of District Integrated Public Health Laboratories at Jubilee Building of BMC and H, Purba Bardhaman ---- SITC of Fire Detection System.
2025_WBPWD_807490_1
WBPWD/AE/BMCESD/NIeQ-04/24-25 (3rd Call)
Open Tender
Electrical Work/ Equipment
Item Rate
30 days
Purba Bardhaman
Please refer Tender documents.
3 documents required · 3 mandatory
₹8,100
2 May 2025
28 Jan 2025
19 Feb 2025
28 Jan 2025
17 Feb 2025
28 Jan 2025
Amount
Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, soft addressable, ( VDS / UL / FM / ULC approved ) , ethernet ready fire alarm control panel, with each loop capable of taking minimum 120 devices. The panel shall be able to give pin point location of all fire/ fault conditions. The Panel should be able to store minimum 1000 log events in its Memory as per recommended standards. (Approved Make : Siemens/EsserHoneywell/Bosch/Securiton or as per existing system)
The panel shall have in-built rectifier, Loop cards, interface card for connecting external serial printer, 4 line, 40 charecter / line alphanumeric LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working or capable of operating the system for 2 hours during alarm condition, with integral battery charger complete as required. The panel shall have extra loop card to serve as stand by in case of burntout or malfunctioning of any operating loop cards. The FACP shall be capable of being networked with other similar FACP located at different part of the premises through ethernet (LAN). The panel should have necessary Ethernet card installed in it for bidirectional communication with 3rd party BMS/Scada and 3rd party public address system. All necessary memory map (incl. device address) should be provided. Minimum 4 potential free spare contacts should be provided with the panel. The system must be preloaded with licenced software. (Approved Make : Siemens/EsserHoneywell/Bosch/Securiton or as per existing system)
2 Loops Panel
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector IP-42 ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Siemens/EsserHoneywell/Bosch/Securiton or as per existing system)
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point IP-42 ( VDS / UL /ERTL/ LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make : Siemens/EsserHoneywell/Bosch/Securiton or as per existing system)
Supply, Installation,Testing & Commissioning of IP Addressable Loop Powered Hooter (sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP-65 ( VDS / UL /ERTL/ LPCB / FM approved). (Approved Make : Siemens/EsserHoneywell/Bosch/Securiton or as per existing system)
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL /ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : Siemens/EsserHoneywell/Bosch/Securiton or as per existing system)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) ( Make. Finolex/Gloster/ RR Kable/Polycab) through 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision MMS/ AKG/ Universal/ Polycab) on the surface of the wall.
Cleaning, servicing and checking of all existing Intelligent multisensor Fire Detectors inbuilt with optical smoke sensor as well as additional heat detector sensor, Manual Call Point, Hooter.
Labour charges for dismaintaling the existing fire detection system same such as PVC pipe,wire,dector,device and other accessories etc.[ 4 nos. labour for 1 day]
Making necessary drawing of total installation and submitted to the office after successful commissioning and testing of Fire detection system.
Add GST @18%
Add LWC @1%
S K CONSTRUCTION (BID ID -6128901)
KARMAKAR AGENCIES (BID ID -6128927)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .