NAVIN KUMAR
ED - Hisar
Implementation of complete Fire Plan scheme at the IAH-maharaja Agarsen Airport, Hisar (Pdg. Fire Alarm and PA System for existing building at Civil aerodrome at Hisar)
2023_HRY_271939_1
2023B373EC49 B0B1 4951 B55A 5CC53CE863F6666BAR
Open Tender
Electrical Works
Works
90 days
Hisar
2 documents required · 2 mandatory
₹5,000
₹1.4 L
Yes
7 Aug 2023
7 Apr 2023
17 Apr 2023
7 Apr 2023
14 Apr 2023
7 Apr 2023
Amount
Supply, Installation, Testing and Commissioning of Microprocessor based Intelligent Addressable Main Fire Alarm Control Panel with Suitable 2 Loops modules and each loop capable of supporting not less than 125 detector and 125 devices: Loop length up to 1.5 km, 600 Character/7` Color LCD touch screen display with bright colors to indicate alarms and events, Integrated Ethernet Ports and 2 Nos of RS 485 for networking, evacuation speaker zones, AHU Modules, Damper switch, Smoke extraction Fans, Lifts.. etc. The Panel shall support 8000 history logs in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 24 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger.The panel should also have IP30 or better protection. The panel shall have seamless integration with EVAC-certified Public Address System and shall be complete with all accessories. The fire Alarm Panel and Public Address System should be of the same make. Shall be EN54 -Vds/UL-FM Certification Make: Notifier/Honeywell/EDWARDS EST3-CB-14.
Supply, Installation, Testing, and Commissioning of an addressable multisensor detector including mounting base with LED… etc. complete as required with inbuilt Isolators as per NFPA 72 style 7 wiring requirements or with isolator base/module for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements: Drift Compensation feature and Automatic addressing. The detector should monitor Electromagnetic interference and report to the panel - current and average values. The detector should have IP40 or a better protection rating. EMC safety for the detector shall be 50 V/m. Shall be EN54 -Vds/UL-FM Certification Make: Notifier/ Honeywell/ EDWARDS .
Supply, Installation, Testing and Commissioning of addressable Heat detector with fixed and rate of raise feature including mounting base with LED… etc. complete as required. Each Detector should have 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005.The detector should monitor Electromagnetic interference and report to the panel - current and average values. The detector should have IP40 or a better protection rating. EMC safety for the detector shall be 50 V/m. Shall be UL/EN/VDS certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) Make: Notifier/ Honeywell/ EDWARDS.
Supply, Installation, Testing and Commissioning of addressable Double ACTION manual call point and necessary fixing arrangements with key complete as required. MCP should have IP52 or a better protection rating Shall be EN54 -Vds/UL-FM Certification Make: Notifier/Honeywell/EDWARDS.
Supply, Installation, Testing and Commissioning of Addressable Sounder with sound pressure 90 dB(A), Sounder should have IP40 or better protection rating. Shall be EN54 -Vds/UL-FM Certification Make: Notifier/Honeywell/EDWARDS.
Supply, Installation, Testing and Commissioning of Addressable Control Relay Module with inbuilt isolators as per NFPA 72 style 7 wiring requirements. Relay Control module shall be used for emergency control functions including shutting down Fire dampers in AHUs, tripping of AHUs, Fresh air fans, Ventilation fans, tripping of Access control doors, etc.. Shall be EN54/ Vds Certification/UL Make: Notifier/Honeywell/EDWARDS.
Supply, Installation, Testing and Commissioning of Glow Type EXIT Sign Board photoluminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class – 1 material PSPA fixed on 3 mm acrylic sheet on both sides showing marking (running man, Arrow, and Exit) and hang with the ceiling with chain and fastener including the cost of labor and material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work Make PES/Giolite/OMEX/SAVEMAX.
Supply, Installation, Testing and commissioning of Cabinet Speaker Max Power - 9 W , Rated power (PHC) - 6 W(6-3-1.5), Sound pressure level at rate power /1 w ,(at1kHz,1m) (at 1 kHz, 1 m) - 96dB/ 90dB, Effective frequency range (-10 dB) - 200-15000 Hz, Opening angle (at 1 kHz/4 kHz, - 6 dB),In degrees - 150/70, Rated voltage - 100 V, Rated impedance - 1667 Make Honeywell / Notifier / Ahuja.
Supply, Installation, Testing and commissioning of 15W Horn Loudspeaker made with ABS, water and dust protected to IP 65 Sound pressure level at 15W/1W - 115/103 dB (SPL), Effective frequency range 500 Hz to 5 kHz, Make Honeywell / Notifire / Ahuja.
Supply Installation Testing and Commissioning of 17U rack for 450 MM depth switch Mounting with Fan and 15 AmpX3 socket power Strip, PDU, Hardware Mounting Kit Make Comrack/Valrack/ CP plus.
Supply Installation Testing and Commissioning of 1 KVA UPS Overvoltage cut-off device (OVCD), Support for Generator Compatible with Wide Input. Wide Input Voltage window (110 – 280Vac) for Indian Environmental Conditions and for Optimized Battery Performance. UPS would support SNMP Mnagaer and web browser On-Line With 2-hour Backup MAKE APC/EINOVA/MICROTEK.
Supply, Installation, Testing and commissioning of 2 core multi strand 1.5 sq mm annealed copper conductor speaker cable in existing pipe/ channel I/C connection, etc.Make Finolex/plaza/Paymaire.
Supply, Installation, Testing, and commissioning of single core multi strand 1.5 sq mm annealed copper conductor speaker cable in existing pipe/ channel I/C connection, etc. Make Finolex/plaza/Paymaire.
Supply and erection of 25 mm dia PVC conduit pipe ISI marked (Medium) recessed in-wall/ceiling etc. including the cost of PVC bends, inspection box, and all other material required to complete the job in all respect to the entire satisfaction of Engineer-in-Charge of work. Make: Polyplast/ RAVINDRA /POLYCAB / Diplast
Supply of ABC stored pressure type fire extinguisher 6 Kg capacity MAP - 90% 5-year warranty bearing ISI mark for fire extinguisher ABC class of fire extinguisher will be manufactured strictly as per BIS IS: 683:2006 bearing ISI mark EN3 615 approved powder (Make - Cease fire/ Savemax/ SAFEX).
Supply of 5 Kg ceiling mounted fire extinguisher clean agent HFC 134A zero ODP, stored pressure type, pressure gauge gross weight 7.7 Kg empty weight 2.7 Kg, can height 267 MM diameter 230 MM Discharge time less than Bsec, Auto discharge mechanism on temperature rise applicable on class A,B,C and electrically started fire can construction valve construction forging and mechinig internal coating of can epoxy powder coating sheet metal thickness 1.60 Mm (Make - Cease fire/ Savemax/ SAFEX).
Supply of Co2 type Fire Extinguisher 4.5 Kgs capacity made from brand new seamless cylinder, as per ISI 7285 and CCE approval, fitted with a Discharge hose and horn and squeeze Grip type valve with initial charge as per ISI 15683:2006 specification, bearing ISI Mark.(Make - Cease fire/ Savemax/ SAFEX).
Supply of Mechnical foam type fire extinguisher 50 liter capacity MAP -90% with outside cylinder, Co2 Cylinder 1 KG Capacity for above AFFF foam compound for the extinguisher, 3000 ml capacity combine (Make - Cease fire/ Savemax/ SAFEX).
Supply of 3 Meter Rubber pipe with EPDM quality with squzeer grip nozzle for jet length ISI make (Make - Cease fire/ Savemax/ SAFEX).
Prime Computers
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .