General Manager (Elect.)-EPG
EXPANSION PROJECT-TnC CELL,MINES AND REFINERY COMPLEX,NALCO,DAMANJODI,ODISHA
Re-Routing of Underground Cables from ERS to Administrative Building, Ash Handling area, Misc. Works for Construction Power Supply and Enabling works.
2021_NALCO_630423_1
MnR/PROJ/TnC/2021/06
Limited
Miscellaneous Works
Works
180 days
Refinery, NALCO, DAMANJODI
4 documents required · 4 mandatory
₹0
Exempted
9 Jun 2021
19 May 2021
9 Jun 2021
19 May 2021
5 Jun 2021
19 May 2021
90 days
Amount
Removal of 1.1KV grade, Power Cable from Underground trench/Overhead trays of Size upto 3.5X185 sqmm including removal of Glands / Clamps etc. including transportation, depositing at Stores & as per direction of Engineer-in-charge
Laying of 1.1KV grade, Power Cable through Structures/Overhead trays/Conduit etc. size upto 3.5/4CX95 sqmm including transportation from Stores to site. All the tools & tackles, consumables, labours required for execution of the job are included in the scope of the contract & as per direction of Engineer-in-charge
Excavating of trench & Laying / removal of multicore power cables with supply of sand, bricks, back filling etc. of 1.1KV grade size above 3.5 CX70 sq mm upto 3.5/4CX185 sqmm including transportation from Stores to site. All the tools & tackles, consumables, labours required for execution of the job are included in the scope of the contract & as per direction of Engineer-in-charge.
End Termination of 1.1KV grade, Power Cable of Size upto 3.5/4CX95 sqmm including supply of Lugs & other Consumables & as per direction of Engineer-in-charge.
Removal of 1.1KV grade, Control Cable from Underground trench/Overhead trays upto size 16CX2.5sqmm including removal of Glands / Clamps etc., including transportation, depositing at Stores & as per direction of Engineer-in-charge
Laying , re-routing of Copper Control Cables upto Size 24Cx2.5 sqmm. on Cable trays/Column/Beam structures etc., with proper clamping, dressing, Identification tag.etc. and alla hard wares as required including Transportation from Materials Storage Section to Construction site. All the tools & tackles, consumables, labours required for execution of the job are included in the scope of the contract & as per direction of Engineer-in-charge.
End Termination of 1.1KV grade, Control Cable of Size upto 16CX2.5 sqmm including supply of Lugs & other Consumables & as per direction of Engineer-in-charge.
Laying of HT Cables over any surface,clamping to the wall/poles/strucure/Tray of Size 3C X 300 sqmm, upto a height of 20 m. All the tools & tackles, consumables, labours required for execution of the job are included in the scope of the contract & as per direction of Engineer-in-charge
Excavating of trench & laying/removal of HT Cables...supply & spreading of sand and spreading and laying bricks, back filling etc. Size 3CX185 -300 sqmm. All the tools & tackles, consumables, labours required for execution of the job are included in the scope of the contract & as per direction of Engineer-in-charge.
Fabrication & erection of supports structures (Material shall be free issue from NALCO) . All the tools & tackles, consumables, labours required for execution of the job are included in the scope of the contract & as per direction of Engineer-in-charge.
Supply GI Ladder type Cable tray of size 600 mm width of following width made out of 2.0 mm thick MS Sheet duly Hot Dip Galvanized in standard length of 3.0 mtr having side channel size 100 x 15 x 15 mm and inside rung of size 35 x 15 x 15 mm duly welded at an interval of 300 mm including 2 nos GI coupler plates of size 70 x 210 x 2.0 mm along with 16 nos M8 x 20 mm Electrogalvanized nut, bolt and washer (without cover). Galvanizing as per IS2629 and 4759 , Mass coating of Zinc 610 grm/mtr sq / 86 microns average & as per direction of Engineer-in-charge
Installation of cable tray of size upto 600 mm width with MS Clit and support welded to the structure members. The party shall supply all other materials like arrangement of welding machine, welding rods, gas cutter required for cutting & welding along with other materials etc. as required for installation & as per direction of Engineer-in-charge.
Supply & Installtion of End Termination in 11 KV cable. By heat shinkable cable jointing kit of Raychem/3M make as per direction of Engineer-in-Charge.
Gravel Spreading: The soil of the entire switchyard area shall be levlled before placing the site surfacing/gravel fill material. After all the structures & equipments have been erected & accepted, the site shall be rolled or compacted with suitable water sprinkling to form a smooth & compact surface condition, which shall be matching with finished ground level of the switchyard area. After due compaction & de-weeding, of the surface of the entire switchyard, the area shall be provided with crusher dust of 75 mm thickness after proper comapction. Care shall be taken for proper gradient for easy discharge of storm water. After the surface is prepared to the required slope & grade a base layer of uncrushed/crushed broken gravel level of -40 mm nominal size shall be spread , rolled & compacted to a thickness 100 MM. The material required for site surfacing/gravel filling shall be free from all types of otganic materials & shall be of standard approved quality, machine broken & as directed by the Engineer-in-Charge. (Material shall be in the scope of the party/contractor) & as per direction of Engineer-in-charge
Laying of Telecom cable upto 50 pair as per direction of Engineer-in-charge
Supply & Installtion of Earthing strip 50 x6 mm along trenches including excavation, cutting and fixing to wall, embedding inside walls and floor,above floor, with cable tray, support structures, welding at joints , providing anti-corrosive paints of bitumin and jute covering for welding, clamping, necessary hardware for connection etc. All the tools & tackles, consumables, labours required for execution of the job are included in the scope of the contract & as per direction of Engineer-in-charge
Letter writing - Size -2"
Letter writing - Size -3"
Background painting
Insulator Pin 11kv - Supply, fixing and connection of following insulators including supply and fixing of hardwares and clamps on poles structures of following voltage grade including all labour and materials, as per specification & as per the direction of Engineer-in-Charge
Supply & Installation of straight through joint in 11 KV cable. By heat shinkable cable jointing kit of Raychem/3M make as per direction of Engineer-in-Charge.
Fire Bucket : Supply & Installation of 3 Nos GI Bucket of 12 Ltrs capacity painted with Red Oxide paint and written with white paint FIRE and mounted on MS angle iron bracket of size 50mm x 50 mm x6 mm thick and 500mm. as required including filling with dry sand as per specification & direction of Engineer-in-Charge
Safety Devices : Supply & fixing of Standard First Aid Box confirming to IS:2217-1963 & as per direction of Engineer-in-Charge
Safety Devices : Supply of 11KV Hand Gloves as per EU standard 60903:2003 , Class 2.0/catagory - RC/Size 10 & as per direction of Engineer-in-Charge
Safety Devices :Supply & fixing of Caution Board as per specification & direction of Engineer-in-Charge.
Safety Devices :Supply & fixing of Shock Treatment Chart (prescribed under IE Rule) duly framed with glass and supported from back with hard board with supply of all material labour T&P etc for proper completion of work & as per direction of Engineer-in-Charge.
Safety Devices :Supply & Fixing of Medium Voltage Danger Notice Plate 200mm x 200 mm made of MS 2 mm thick and vitreous enameled white on both sides with inscription in signal RED Colour on front side as required & as per direction of Engineer-in-Charge.
Safety Devices :Supply & Fixing of High Voltage Danger Notice Plate 250mm x 200 mm made of MS 2 mm thick and vitreous enameled white on both sides with inscription in signal RED Colour on front side as required & as per direction of Engineer-in-Charge
Safety Devices :Supply of 11KV Discharge Rod with insulated handle and 20 M long 2.5 sqmm PVC insulated copper wire extension complete & as per direction of Engineer-in-Charge.
Supply of 11kv Gang operated Air Break Switch: 11kv AB Switch Gang operated - 11kv AB Switch, 400A, Type- FM15/400HSV :12KV, RatedCurrent - 400A, frequency-50Hz(+/-) 5%, Off Load, Outdoor type, Heavy Duty complete with insulator, Base opertaing Rod, Contacts, Clamps with colour phase marking and ready to use conditions, Make-DRETCER PANICKER & as per direction of Engineer-in-Charge.
Supply & Installation of 2.0 mm Insulation Mat : Electrically insulated high voltage PVC Synthetic Insulating mat for use as floor covering in electrical installations of 2.0MM (+/-10%) thick suitable up to AC use voltage of 3.3KV (rms) classified as "CLASS-A" as per IS-15652:2006. Supply & fixing of nominal 2.0MM (+/-10%) thick high voltage insulating mat having tested for leakage current & AC dielectric as per IS-5652:2006. - Dielectric strength shall be minimum 30kV AC (rms). - Width of standard Mat piece shall be one meter & length shall be 5.0 meter - Color of the mat shall be black. - Insulation resistance shall be minimum 100000 M.Ohms with 5000V Megger. - The mat shall have excellent physical properties to withstand movement of instruments involved in electrical equipments (trolley etc) and foot traffic - The mat shall be resistant to acids, alkalis, oil, fire & low temperature (Category-III). - The mat shall be water and moisture proof. - Marking and Packing shall be as per IS-15652:2006. - Type test report of the offered item shall be attached along with the offer. - Supply of suitable adhesive, jointing & fixing on floor at site shall be in the scope of supplier. works shall be well finished and satisfactory.
Earthing-Earthing,Supply, Installation, testing and commissioning of class"B" GI earth electrode of 50 mm dia and 3000 mm long complete with with earth pit with RCC cover with all necessary materials including excavation of earth pit filling with layers of Charcoal & salt, back filling providing necessary brick work slab cover, connection with GI strips, including all labour and materials complete as required & as per direction of Engineer-in-Charge. All earth strips should be interconnected to frame earth grid as per IE rule & as per IS 3043-1987 specification. Funnel is to be provided with wire mesh of suitable size on top of the funnel. All materials are included in the scope of the party.
Installation & testing of Street Light : Supply , Installation, testing & commissioning of pre-wired wall mounted 90W LED Street Light fixture with supporting accessories including providing & fixing of GI bend pipe approximately 1.5 Meter length with junction boxes etc as required & as per direction of Engineer-in-Charge . Make: Philips/Venture/Bajaj/CG/Syska
Erection of Rail/PSC pole at 11KV lines : Transport & erection of Rail/PSC pole at 11KV lines.. This includes digging of pit, supply of metal chips and cement MS Clamps etc as required, fixing of cross arms,GI pin insulators and binding of pin insulators with conductor complete as required & as per direction of the EIC. Pole/ GI pin, pin insulators shall be supplied by Nalco as free issue material.
Supply & erection lighting arrestors : Supply & erection of 11 KV distribution class lighting arrestors of Raychem / Elpro make ,9kv, 5KA, gapless including all fixing arrangements, clamping etc including supply of all hardwares nuts & bolts, labours as required and as per direction of Engineer-in-Charge
Dismantling of structure/Panels by gas cutting, un bolting, etc , shifting the dismantled structure/Panels to designated location as per direction of Engineer-in-Charge
Transformer : Transportation of 630 kVA Transformer from store/site including dismantling, Loading,unloading & installation at site as required & as per direction of Engineer-in-Charge
Gravel Spreading: The soil of the entire switchyard area shall be levlled before placing the site surfacing/gravel fill material. After all the structures & equipments have been erected & accepted, the site shall be rolled or compacted with suitable water sprinkling to form a smooth & compact surface condition, which shall be matching with finished ground level of the switchyard area. After due compaction & de-weeding, of the surface of the entire switchyard, the area shall be provided with crusher dust of 75 mm thickness after proper comapction. Care shall be taken for proper gradient for easy discharge of storm water. After the surface is prepared to the required slope & grade a base layer of uncrushed/crushed broken gravel level of -40 mm nominal size shall be spread , rolled & compacted to a thickness 100 MM. The material required for site surfacing/gravel filling shall be free from all types of otganic materials & shall be of standard approved quality, machine broken & as directed by the Engineer-in-Charge. (Material shall be in the scope of the party/contractor).
Obtaining Statutory CEA Clearance:This includes Preparation & submission of all relevant documents to CEA, all necessary coordination with CEA & obtaining necessary Statutory CEA Clearance
SUSHANTA ENGINEERS
stage.html
html • 0.02 MB
finance_663324.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .