Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Rejected-Technical | Rejected-Technical Due to non submission of similar nature of work |
| 2 | Rejected-Technical AT LAMTIBAHAL PO BRAJARAJNAGAR P S BRAJARAJNAGAR DIST JHARSUGUDA ODISHA 768216 | JHARSUGUDA | ODISHA | 768216 | Rejected-Technical Due to non submission of similar nature of work |
| 3 | Rejected-Technical | Rejected-Technical Due to non submission of similar nature of work |
Tender Value
₹38.0 L
EMD Value
₹37,959
Closing Date
13 May 2026, 5:00 pmClosed
Superintending Engineer
Office of the Superintending Engineer
Renovation of Existing Eye OT to Modular Eye OT (DHH Category) at Jharsuguda for the year 2025-26
2026_EICCL_128355_3
Bid Identification No-SE-RandB-JSG-20- OF 2025-26
Open Tender
Civil Works - Others
Percentage
120 days
Jharsuguda
Please refer Tender documents.
2 documents required · 2 mandatory
₹6,000
₹37,959
Yes
4 Aug 2026
5 May 2026
14 May 2026
5 May 2026
13 May 2026
5 May 2026
5 May 2026 - 13 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Air Handling Units | - | - | - | - |
| 2 | AHU : Double skin air handling units Ceiling suspended type, with 2 mm thick thermal break aluminum profile, 43± 2 thick Puf panel having a density not less than 38 kg/m3 Panel shall have 0.6 mm precoated G.I sheet as outer skin and 0.6mm thick plane GI inner skin. The Unit shall be suitable for clean room applications with coving inside. The AHU shall consists of return air mixing chamber, G4 filter section with filter, DX TYPE cooling coil, fan section with DIRECT DRIVE PLUG FAN with TEFC squirrel cage induction motor. Fine filter section with EU7 filter after the fan section. AHU shall be complete with fresh air, return air and supply air dampers. Fan section & filter section shall have service door. 1500 cfm @ 125mm WC SP. To be connected with 5.5 Tr air cooled condensing unit | - | No. | 0.29 | - |
| 3 | Exhaust air system with volume control damper, 10 micron filter and ducting with cowl and bird screen and discharge to building shaft. Exhaust air to be taken from AHU after fan
section. | - | No. | 1 | - |
| 4 | AHU Control Panel: Self standing / wall mounted electrical panel constructed out of 16 G CRCA sheet duly powder coated with suitable capacity of main incoming MCCB, bus bar, metering panel consisting of voltmeter, ammeter and outgoing feeders consisting of MCCB/ MPCB, contractors, relays, single phase prevetor for ahus motors, LDB & PDBs complete with
on/off trip indication lamps etc. Panel for AHU, ODU | - | sets | 0.29 | - |
| 5 | DUCTING: GI ducting 24 swg with all joints sealed with silicon sealant insulated with XLPE rubber insulation with aluminum foil faced and joints with tape including suports all as
required and as directed by Engineer-in-charge | - | sft | - | - |
| 6 | Condensing Unit: 5.5 TR Nominal capacity Air cooled condensing unit with single compressor. This will be connected with copper pipes with DX cooling coil inside AHU including Refrigerant copper piping with fittings, expansion valves and insulation and control
instrument for condensing unit, all complete. | - | sets | 0.29 | - |
| 7 | Dampers: GI volume control damper | - | Nos | 1 | - |
| 8 | Hatch Box: Static Pass Box made of SS 304 construction with UV light and door interlocks,
Internal size 600 x600 mm | - | Nos. | 0.29 | - |
| 9 | Differential Pressure Gauge: Magnhelic gauge with GI box with SS cover plate and sensors
with necessary tubing | - | Nos. | - | - |
| 10 | Electricals: LDB/PDB with CMBs, wiring for light, power sockets etc and cabling for AHU,
CDU, earthing , 5/15 amp power sockets for OT | - | sets | 0.29 | - |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
cancelled_1.pdf
pdf • 0.15 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
DTCN03.pdf
Tender Documents • 4.73 MB
BOQ_588429.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .