Executive Engineer
AC Division, Works Department, IIT Delhi, Hauz Khas, New Delhi 110016
SITC of VRF / VRV type AC Units in Biomechanics Lab, (near Transport Unit) in IIT Delhi (incl. CAMC)
2024_IIT_828007_1
IITD/WORKS (SP-4759)/2024
Open Tender
Miscellaneous Works
Works
45 days
Indian Institute of Delhi Hauz Khas
As per tender documents
12 documents required · 12 mandatory
₹0
₹18,221
4 Nov 2024
26 Sept 2024
4 Oct 2024
26 Sept 2024
3 Oct 2024
26 Sept 2024
Amount
OUTDOOR UNIT: Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow / Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor-based Controller, top discharge type condensing unit(s), with R-410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI conditions and work even at 50 degree Centigrade ambient temperature without tripping. The unit shall be suitable to work on 400 V+/-10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required (any additional refrigerant required due to long pipe lines shall be within the scope of contractor). The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. (Acceptable make: Daikin / LG / Blue Star / Toshiba / Carrier / O'General / Mitsubishi / Voltas)
INDOOR UNIT HIGH WALL TYPE: Supply, installation, testing and commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/ dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cordless remote control with batteries, drain pan, necessary accessories etc. suitable for operation on 230 V ± 10%, 50 Hz, single phase ac supply, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS system. The cooling capacity of indoor unit will be at air inlet conditions of 27 degree C DB and 19 degree C WB temperature. (Make of the indoor unit shall be same as outdoor unit as per item no. 1)
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft / hard drawn copper refrigerant piping for VRV / VRF / Split AC system, complete with fittings (including Y-joints), with suitable adjustable ring type hanger supports, jointing / brazing including accessories, cutting of glass window wherever required with proper finishing, insulated with XPLE Class-O tubular insulation / with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquidlines, all accessories as per specifications etc. packing of all leakage either on wall or window with silicon / insulation, as required : [Acceptable make of copper pipes : Uniflow / Manibhadra / Ganpati / Mexflow / Mandev / Indigo / Godrej / Visiaro) Acceptable make of tubular insulation: Visiaro / Marshland / Avi Global / Armaflex / Aajjo / Dynamic / Uttam] NOTE: (1) The copper piping and piping circuit should be with minimum number of joints, which shall be attained by: (a) Using one end expanded tubes (b) bending the tubes instead of using elbow joints wherever 90 degree bending is required (2) Piping should be routed at site in such a manner, that brazed joints in the refrigeration piping are kept to a minimum (3) The makes of tube fittings shall be same as that of tubes (4) The thickness of fittings used shall be same as that of the pipe
6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
GI TRAY SUPPORT: Supplying and installing following size of perforated Hot Dipped Galvanised Iron Cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5% in convenient sections, joined with connectors, suspended / supported from the ceiling / wall with GI suspenders including GI bolts and nuts, GI C-Channels, etc. including GI protective sheet covering outside the room as required. (Only for outdoor portion)
225 mm width x 50 mm depth x 1.6 mm thickness
DRAIN / CABLE PIPE: Supplying and laying of ISI marked CPVC pipe of 25 mm dia for draining of sweated water / drawing communication cable from AC evaporator (indoor) unit including providing tee, joints, elbows, supports, etc. insulated with XLPE class - O tubular insulation / with Class-O closed cell elastomeric nitrile rubber tubular sleeves sections of 19 mm thick etc. complete as required. (Acceptable make: Astral / Geroge Fischer / Finolex / Prakash / Supreme / Prince)
DRAIN PIPE: Supplying and laying of ISI marked flexible braided PVC pipe of 25 mm dia for draining of sweated water from AC evaporator (indoor) unit including providing tee, joints, elbows, supports, etc. wherever required etc. complete as required.
Supplying and fixing of following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc as required. (but without MCB/RCCB/Isolator) (Acceptable make: Havells / Siemens / L&T / Legrand / ABB / Schneider / C&S / HPL / Hager)
12 Way, Double door
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Acceptable make: Havells / Standard / HPL/ Legrand / L&T / Polycab / C&S / ABB / Siemens / Schneider)
Single Pole
Double pole (as incomer to DB)
Supplying and fixing cable end box (loose wire box) suitable for 12 / 16 way double door SPN MCB DB on surface / recess complete with testing and commissioning etc. as required.
Providing and fixing 4 mm dia copper wire on surface or in recess for loop earthing along with existing surface / recessed conduit / submain wiring / power cable as required.
Supplying and laying of ISI marked FRLS industrial multistranded following type copper cable of following size of 1.1 kv grade conforming to IS694:2010 including making connection etc. for communication / indoor power supply between indoor and outdoor unit and other units, etc. through conduit complete as required. (for communication and power) (Acceptable make: KEI / Finolex / Polycab / Universal / Havells / Gloster / RR Kabel / Rallison) [NB: Single stranded cable not to be used]
2 core x 1.5 sqmm unarmoured
3 core x 2.5 sqmm unarmoured
4 core x 10 sqmm armoured
Providing and fixing following rating and breaking capacity and pole MCCB Conforming to IS/IEC 60947-2 & IEC 60947-2 with thermomagnetic release and terminal spreaders in sheet steel enclosure including drilling holes, duly factory painted as required, making connections, providing spreader terminal, etc. as required. (Acceptable make: Siemens / L&T / GE Power / C&S / Crompton / Havells / Legrand) For main power connection.
25 A, 18 kA, FPMCCB
Supplying and making end termination with brass compression gland and tinned copper lugs for following size of pvc insulated and pvc sheathed / XLPE copper conductor cable of 1.1 kV grade as required.
4 core x 10 sqmm
Fabricating, Providing and fixing M.S. iron frame fabricated with M.S. C-channel of size 50 mm x 50 mm x 6 mm (thick) for resting the condenser unit on the roof / floor of the building duly supported from the bottom as required including painting and grouting the framework with cement concrete etc. complete as required. (Acceptable make of angle: SAIL / Jindal / TATA / Prakash / Nezone)
Providing and laying in position cement concrete 1:3:6 (1 cement : 2 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
Supplying and fixing of 4 Module non-metallic Outdoor type Waterproof MCB box having protection of IP-65 with 4 Pole C-series MCB, transparent sheet with spring-operated auto-closure, din bar for mounting MCBs (but without MCBs and incomer) as required. ( Acceptable Make: Grasp / Legrand / Havells)
SUB HEAD - 2 (AMC) (Supplementary agreement shall be formed after DLP) under ARMO Fund
Comprehensive (Routine, Preventive and Breakdown) maintenance of 10 HP VRF / VRV Type AC unit including its all accessories, condensers, evaporator units, time to time checking of refrigerant leakage, electrical circuits, etc. for smooth operation of the entire AC units during the defect liability period of 1 year after date of commissioning as per maintenance schedule. (No payment shall be made separately for this period): 1st Year
Comprehensive (Routine, Preventive and Breakdown) maintenance of 10 HP VRF / VRV Type AC unit including its all accessories, condensers, evaporator units, time to time checking of refrigerant leakage, electrical circuits, etc. for smooth operation of the entire AC units after defect liability period of 1 year from the date of commissioning as per maintenance schedule. Any breakdown shall be attended within 4 hours of reporting. Spare parts required during breakdown maintenance shall be arranged and replaced by the Contractor. This is applicable for the whole system of AC units installed. (N.B.: 01 Job means during a period of one year)
2nd year (For 12 months)
3rd year (For 12 months)
4th year (For 12 months)
5th year (For 12 months)
6th year (For 12 months)
RefAir Engineering Works
AB3S SOLUTIONS PVT LTD
M/S COOLREF ENGINEERS
Bidder Name
M/S COOLREF ENGINEERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .