Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.6 LAccepted-AOC | L1 | Accepted-AOC Rates quoted reasonable | |
| 2 | L2₹18.9 L+₹93,840.70 (5.21%)Rejected-Finance OPPOSITE J K BANK BAROO NH1 HAIDERY COMPLEX BAROO KARGIL BAROO KARGIL LADAKH 194103 | KARGIL | LADAKH | 194103 | L2 | Rejected-Finance Rates quoted higher side | |
| 3 | L3₹22.3 L+₹4.3 L (23.7%)Rejected-Finance E 140 2010 BKP VILL AMTALLA PO DUMARCHIR DIST PAKUR PIN 814111 JHARKHAND | PAKUR | PAKUR | JHARKHAND | 814111 | L3 | Rejected-Finance Rates quoted higher side |
Tender Value
Refer Docs
EMD Value
₹38,440
Closing Date
18 Jan 2022, 6:00 pmClosed
CWE (AF) PANAGARH
HQ CWE AF PANAGARH MILITARY ENGINEER SERVICES AIR FORCE STATION ARJAN SINGH PO BIRUDIAH DIST BURDWAN WEST BENGAL PIN 713148
SPECIAL REPAIRS TO HT UG CABLE OF EXCHANGE BUILDING, VCB PANELS AND REPLACEMENT OF HANGER HIGH BAY LAMPS OF 87 SQN AREA AT 31 WING PANAGARH
2021_MES_493227_1
82350/PAN/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
GE AF PANAGARH
Please refer tender documents
9 documents required · 9 mandatory
₹500
GE AF PANAGARH
₹38,440
Yes
8 Feb 2022
8 Dec 2021
20 Jan 2022
8 Dec 2021
18 Jan 2022
6 Jan 2022
8 Dec 2021 - 22 Dec 2021
Amount
Note : Prior to commencement of the subject works, the contractor needs to submit valid Electrical License in the name of himself/them self or Agreement with agency having valid Electrical License alongwith Agency's Electrical License to the Accepting Officer for his approval through GE. In absence of such documents, no work will be executed at site and to be treated as defaulter on the Contractor's part . In addition, Supervisor for execution of electrical works employed by the Contractor shall posses Supervisory Certificate of competency issued by concerned State Govt/Union Territory and the Worker/Tradesman for execution of Electrical Works must hold necessary permit issued by concerned State Govt/Union Territory.
Material and labour for excavating in trenches not exc 1.50 mtr wide and not exc 1.50 mtr in depth for taking out/laying of under ground cable, pole or stay and getting out in soft/loose soil, complete all as specified and as directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft /loose soil or hard/dense soil all as specified and directed by Engineer-in-Charge. .
Removing excavated material not exceeding 50 M and depositing where directed at a level not exceeding 1.5 M above starting point all as specified and directed by Engineer-in-Charge. .
Supply and spreading dry sand of approved quality for cushioning of UG cable laid in trenches all as specified and directed by the Engr-in-Charge
Supply, laying, jointing and testing of electric cable, nominal cross sectional area of 120 sqmm, 3 core heavy duty 11KV (E) grade, XLPE insulated, screened with sound compacted aluminium conductor, conductor screening with extruded semi-conducting layers insulation screening with copper tape covers laid up with PVC (ST-2) extruded inner sheathing galvanised steel strip armoured PVC (ST-2) outer sheathed cable conforming to IS-7098(Part-II) amended of following sizes, laid in trenches/cable duct complete all as specified and as directed :-
Supply, jointing and testing cable jointing kit for 11KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed by the Engr-in-Charge. Note :- (a) Cutting of faulty cable / joint is deemed to be included in the above quoted rates. (b) Earth work i.e. exc, removal, and returning filling will be measured & paid separately
Supply, jointing and testing cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed by the Engr-in-Charge. Note :- (a) Cutting of faulty cable / joint is deemed to be included in the above quoted rates. (b) Earth work i.e.excavation, removal, and returning filling will be measured & paid separately
Supply and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete all as specified and directed by the Engr-in-Charge.
Supply and fixing in replacement for 80mm bore GI protection pipe light grade for cable protection incl all fittings laid in trenches or fixed on pole all as specified all as specified and directed by the Engr-in-Charge
Supply and fixing in replacement lightening surge arrestors expulsion type complete with all fittings such as bolts, nuts, washers etc having transmission class, discharge capacity 65 kilo amp all as specified and directed.
M & L for disconnecting and taking out HT VCB for Overhauling of Spring charge unit including cleaning & removing of scales, soot or any hydroscopic layer accumulated on copper bus bar using proper chemical cleaning reagents like CRCs, checking nuts, bolts, make break operation both mechanically and electrically smooth including greasing of all moving/ fixed contact, nut & bolts checking contact resistance, Internal control wiring, repairing/replacing heating coil removing moisture for all the feeders complete all as directed by Engineer-in-Charge. Note: Spares required for replacement will be paid and measured separately.
M & L for Disconnecting of cables from HT VCB panel checking of earth fault and over current relays testing of relays with the help of relay testing kit (boosting Kit) and resting of relays as per desire load current reconnecting the cables, including calibration of relays, for proper tripping and functioning and replacement of U/S parts if required and testing complete for tripping all as directed by Engineer-in-Charge. Note: Spares required for replacement will be paid and measured separately.
M & L for replacement of under mentioned unserviceable items (to be incorporated against item No. 12 & 13 :-
LED Indicator lamp of voltage Range : 110A - 110 VAC 110D - 110 VDC 240A - 240 VAC 220D - 220 VDC
Supply and fix three phase over current and earth fault relay Suitable for CT Secondary 1 Amps or 5 Amps, Aux Supply 77-250V DC/AC (230VAC) suitable for existing breakers including taking down old U/ S relay all as specified and directed by the Engr-in-Charge.
Supply and fix tripping coil DC 24/110 Volts suitable for existing breakers all as specified and directed by the Engr-in-Charge.
Supply, installation, commissioning and testing 11 KV, single phase, resin cast indoor potential transformer of ratio 11KV/110V, accuracy class 1.0, burden VA 200/phase, highest system voltage 12 KV, insulation level 28KV, lightning impulse 75 KV, voltage factor 1.2 continuous and 1.9 times for 8 hours for with suitable enclosure including taking down of U/S PT complete all as specified and as directed. Make :Crompton ,Type : PT-005,Burden Vally or equivalent make
Supply, installation, commissioning and testing 11 KV, 3P/3W,50 Hz, 800 Amps, resin cast, enclosure type, indoor CT of ratio 80-40/1A, accuracy class 1.0, main CKT (STC) 13-1KA (3 Sec) , E/CKT - 13-1 KA (1 Sec) 200/phase, highest system voltage 12 KV, insulation level 28KV, lightning impulse 75 KV, with suitable enclosure complete all as specified and as directed. Make :Crompton ,Type : CT-005,Burden Vally or equivalent make
Supply and installation of power pack unit of Input 110VAC 50 C/S,3 phase, Out put 110, Cap-300, make Crompton safety devices complete suitable for existing breakers including taking down old power pack unit all as directed
Material and labour for PCC (1:3:6) type C2 (using 40mm graded stone aggregate) as in foundation of poles, stay etc all as specified and directed by the Engr-in-Charge..
Material and labour for PCC (1:2:4) type B1 (using 20mm graded stone aggregate) as in pedestal coping including necessary formwork finished fair using extra cement complete all as specified and directed by the Engr-in-Charge..
Material and labour for disconnecting the electric connection and dismantling to the existing old LT panel board of any size and keeping aside in safe custody / depositing to MES store yard including its accessories as schedule of credit to contractor or as directed by Engineer-in-Charge.
Material and labour for Vermin dust proof LT junction box outdoor type of suitable size made out of MS sheet 3.15 mm thick, powder coated, rear and front operated door with locking arrangement, suitable aluminium busbar 200 Amp and fixed on angle iron base suitable for pedestal mounting of size 60x60x5 mm for connecting cable on both side complete all as specified and directed by the Engr-in-Charge.
Design, Fabrication, Testing & Commissioning of Vermin dust proof LT Feeder Pillar board outdoor type of suitable size made out of MS sheet 3.15 mm thick, CPRI approved, powder coated , rear and front operated door with locking arrangement , suitable aluminium busbar and fixed on angle iron base suitable for pedestal mounting of size 50x50x5 mm to accommodating the following (BPI) :- INCOMING :- (a) MCCB 400 Amps, 4 pole, 36 KA - 01(in coming) OUTGOING :- (b) MCCB 250 Amps, 4 pole, 25 KA - 01 No (Outgoing) (c) MCCB 160 Amps 4 pole, 25 KA - 01 Nos (out going) (d) MCCB 125 Amps 4 pole, 25 KA - 01 Nos (out going) (e) MCCB 100 Amps 4 pole, 25 KA - 02 Nos (out going) (f) MCCB 63 Amps, 4 pole, 25KA - 02 Nos (out going) (g) MCB 32 Amps, DP, 15KA - 02 Nos (out going) (h) MCCB 16 Amps, DP, 15KA- 02 Nos (out going) (i) Digital Multi-functional Meters for measuring current, voltage and frequency including CTs of suitable rating and class (j) Astronomical timer switch Note : The rate also inclusive of all materials mentioned from sl no (a) to (j) etc complete.
Material & Labour for earthing complete with galvanised steel earth plate electrode of size 60 cm x60 cm x 6.0mm thick burried directly in ground (earth pit not less than 2.25 m below ground level) with top edge not less than 1.5 m below ground level, connected to galvanised wire 4.0mm dia as earth lead by means of bolts, nuts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No 3 of SSR part I, connected to earth test point all as specified or indicated complete with excavation, earth work, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix , type B1 cover reinforced with 8mm dia TMT bars @150mm C/C both ways ,GI funnel with GI watering pipe 20mm dia med gde ,wire mesh, protection pipe 15mm dia GI pipe light grade for earth lead upto 7.50m long complete all as directed and specified and testing on completion.
Material & Labour for earthing complete with galvanised steel earth plate electrode of size 60 Cm x 60 Cm x 6.00 mm thick burried directly in ground earth pit not less than 2.25 m below ground level with top edge not less than 1.5 m below ground level connected to galvanised flat of size 32 x 6 mm dia by means of bolts nuts, check nuts washers of galvanised iron or steel all as shown in electrical plate No 3 of SSR Part-I connected to earth test point all as specified or indicated complete with excavation, earth work, returning filling, removing excavated soil, Notes:-The unit rate also including for excavation, earth work in any type of strata, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bars @150mm C/C both ways ,GI funnel with GI watering pipe 20mm dia med grade ,wire mesh, protection pipe 40mm dia GI pipe light gde for earth lead upto 7.50m long complete all as specified including testing on completion. .
Supply and fixing in replacement for 50 mm bore GI protection pipe light grade for cable protection incl all fittings laid in trenches or fixed on pole complete all as specified and directed by the Engr-in-Charge.
Material & Labour for boring of holes under road, pavement, hard standing by trenchless technology/manual excavation as necessary including machine ,tools etc as per site requirement.
Material & Labour for replacement of unserviceable existing wiring of LT Panels located at different locations and wiring with new copper wiring 2.5/4 sqmm with copper lugs epoxy insulator bar and insulating the bus bar with tape conforming with colour code complete all as specified & directed.
Supply only the following items:- ( to be incorporated under item No : 31 above)
2.5 sqmm single core sheathed copper cable
4 sqmm single core sheathed copper cable
6 sqmm single core sheathed copper cable
Copper lugs of suitable size
DMC resin /Red polyamide type Epoxy insulator bus bar connector/supporter of suitable size/dimension
LT Panel Locking set
Supply and fixed in repairs for 3 Ph ammeter digital type 3.5 digit display 0-500A range square shape with CT Coil fixed to existing LT Panels complete all as specified and as directed.
Supply and fixed in repairs for 3 Ph Voltmeter digital type 3.5 digit display 0-500V range square shape with PT Coil fixed to existing LT Panels complete all as specified and as directed.
Material & Labour for cutting the burnt out aluminium lugs and relugging of LT cable in cable end box of transformer on switches including cutting existing lugs suitable for cable of size 70 to 185 sqmm and reconnection after repair work and testing etc complete all as specified and directed. Note: The cost of the liftings/relaying of cable whereas required for relugging is deemed to be inclusive in the unit rates quoted by the bidder against that item.
Material and labour for end termination joints (epoxy type) for LT PVC / XLPE insulated armoured aluminium conductor cable including jointing and testing etc for the following size :- Make : 3M /M-seal/Denson/Raychem etc Note : (i) Cutting of faulty cable/ joint is deemed to be included in the above quoted rates. (ii) If old burnt/damaged LT cable/joint retrieved will be issued to contractor as schedule of credit.
16 sqmm to 50 sqmm 4 core / 3.5 core
70 sqmm to 185 sqmm 3.5 core
Material & Labour for Painting of LT Panels of any size/dimension by preparation of old painted surfaces, cleaning refixing panel board door with hinges, repairing/replacing broken hinges of LT Panel door, Insulating with rubber strap, nut bolts etc removing of existing rust grease oil spot etc, priming with aluminium red-oxide and then applying 1st grade of synthetic enameled spray paint (two coat) of approved make, brand and colours (includes cost of paint) & foundation and painting names of the distribution location complete all as directed by Engineer-in-Charge.
Supply and fix industrial LED luminaries highbay lighting of capacity 200W environment friendly and robust highbay/mediumbay LED IP66 luminaries with high efficiency in replacement including taking down old U/S HPMV/MH lamp on various height i.e 15 to 18 Mtrs in hangar, Arial port, warehouse etc. including taking down existing unserviceable light of any capacity or any type. Make: (i) EVEREADY Cat No- LEDH1BAY20015R-02 (ii) Crompton, Cat No. LHB11-200-CDL/60-M (iii) make Bajaj Cat No. BGHBM 200W LED XE / or equivalent Philips. NOTE: Necessary arrangement like hydrulic boom ladder and tools for fixing /removing of lights to be arranged by the contractor and deemed to be included the above quoted rate.
M/S Ali Trading Co
MBS TRADING CO.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .