The tenderer must have minimum average annual contractual turnover of V/N or "V" whichever is less ;where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of 'total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet
(a)The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i)Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or (ii)Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or (iii)One similar work costing not less than the amount equal to 60% of advertised value of the tender. (b)(1) In case of tenders for composite works (e.g. works involving more than one distinct component, such as Civil Engineering works, S&T works, Electrical works, OHE works etc. and in the case of major bridges - substructure, superstructure etc.), tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i)Three similar works each costing not less than the amount equal to 30% of advertised value of each component of tender, or (ii)Two similar works each costing not less than the amount equal to 40% of advertised value of each component of tender, or (iii)One similar work each costing not less than the amount equal to 60% of advertised value of each component of tender.
Defination of Similar Work :- Similar works for the above tender shall be:- Supply, installation, testing and commissioning of any LT/HT Electrical Work
71 conditions · 6 needing a document upload
Valid copy of PAN and GSTIN needs to be furnished along with the documents.
Tender Form (First Sheet) as per 'Annexure-I'
For Sole Proprietorship firm a)Affidavit as per 'Proforma I'. b)Special power of Attorney as per proforma given in 'Proforma II' to be submitted by sole proprietor firm duly notarized.(Not required if tender documents are submitted by proprietor himself)
For Partnership firm a)Self/Notary attested copies of Partnership deed. b)Special Power of Attorney as per proforma given in 'Proforma-III' to be submitted by Partnership firm. (Not required if one or more partners are authorized in Parternership deed to sign on behalf of the firm.)
For Limited Company a) Copy of Memorandum & Articles of Association of Company. b)Self /Notary attested copy of resolution passed by Board of Directors authorizing its Director/ Employee to deal with tender on behalf of company. c) Attested copy of Notarized Special Power of Attorney includingratification clause duly signed by person authorized by the company.(D) A copy of Certificate of Incorporation
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Guideline/Specification for design, installation and commission of High Mast Tower.
The designing of high mast tower foundation should be done after testing of soil bearing capacity and approved by the competent authority
"The successful tenderer shall furnish complete specification of high mast & the following drawings:a) General arrangements drawing.b) Lighting layout & Electrical schematic drawing.c) Foundation drawing for High Mast.d) Any other drawing considered necessary by Railways."
"The design of High mast i) Must be validated and approved by RITES.ii)Galvanization thickness should conform to the relevant IS standard IS 2629/IS 4759/IS 1367(Part XIII)iii)Thickness of all sections (lower section, middle and top) should be clearly defined in the specification.iv)Design should ensure smooth raising/lowering operation under windy conditions."
Mandatory Documentation for High mast should be produced for traceability and quality assurance i) OEM test certificate ii) Type test report from NABL Lab iii) Tax invoice iv) Stock transfer Invoice v) Delivery Challan vi) Quality Assurance Plan (QAP) vii) General Arrangement drawing (GAD) viii) Technical data sheet ix) Warranty certificate x) Foundation Design calculation.
"Additional documents (If supplied through Authorized dealer) i) Material transfer certificate from OEMii)OEM authorization certificate iii) Receipt challans iv) Traceability documents for supplied material"
"For foundation bolts following points to be ensureda.Grade, make, and specifications of high tensile foundation bolts should be clearly mentioned in the technical specification.b.Foundation bolts should be supplied and certified by OEM only.c.Galvanized nuts, washers, and locking arrangements should be provided.d.Bolt tightening torque values should be specified and recorded during erection.e.Foundation Bolts & Hardware should confirm to relevant IS standards i.e. IS 2629 / IS 4759/ IS 1367(Part XIII) etc."
Provision of counterweights whenever required should form part of OEM design. Counterweight system should ensure proper balancing of lantern carriage, reduced load on winch mechanism and smooth operation during maintenance. Counterweights should be securely enclosed and protected and protected against corrosion.
Stainless steel wire rope should be used. Minimum specification should include grade material and should confirm to relevant IS standard. Diameter of wire rope should be min 6 mm or as per design requirement of OEM.
Design of High mast luminaire should account for size, weight and wind area so as to not affect structural loading of the Mast and the same to be certified by OEM.
"The mast should have permanent identification marking indicating.i)OEM name and address.ii)Year of manufacture.iii)Wind speed rating.iv)Safe working load.v)Mast Height.vi)Serial number of Mast."
Working life of High mast tower should be of 25 years.
All other specification/Guideline for High Mast Tower should be followed as per RDSO Technical circular No.2025/EEM/113/1/Pt. I dated 06.05.2026. in case of any inconsistency in technical specification mentioned in tender Document, RDSO Technical circular No.2025/EEM/113/1/Pt. I dated 06.05.2026 will be taken as reference.
At RNY, NLV & PBL Station - Additional Electrical works in connection with soft upgradation, Improvement of Facade, entry Porch, Waiting hall, Circulating area, landscaping & horticulture,Toilet Blocks and provision of 2nd Entry, Platform Shelters etc.
RNY-EL-T-14-2026-27~NFR
RNY-EL-T-14-2026-27
Open
Works - General
180 Days
Kamrup, Assam
₹0
₹3.3 L
30 Sept 2026
30 Sept 2026
9 Oct 2026
286 items across 8 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 16,09,798.21 | ||
| — | 1.00 | — | — | ||
| Supply of 16 mtr long high mast system with its all accessories and suitable equipments. Mast shaft shall be in two sections, hot dip galvanised and suitable for wind velocity as per IS: 875 part 3. It shall also include accessories for high mast including head frame, 3/4 point suspension system with steel wire rope 6 mm dia (7/19 construction) double drum winch, galvanised lantern carriage arrangement suitable for 9 luminaries (9 nos of 72LED/200 watt LED flood lights) symmetrically & its control gear boxes & lightning finial. The mast shall have an integral power tool installed inside the base compartment for its operation.Lightning protection system and surge protection devices(type-3) to be provided at the top. The cable connection for luminaries should be the size of 4.0 sq. mm, 5 core flexible EPR insulated PCP sheathed copper cable.The design of High mast Must be validated and approved by RITES. | — | — | — | 1,97,545.33 | |
| — | 9.00 | — | — | ||
| Supply,testing, fitting, fixing of defective 200 Watt high power LEDs with toughened glass and IP66 protection. System efficacy > 110 LPW 10KV SPD included. The LED fittings should be warranted for 5 years. | — | — | — | 2,25,000 | |
| — | 1.00 | — | — | ||
| Supply and erection of control panel housing suitable for control circuit for the operation of the mast, it shall also consist of suitable control for the power tool motor including timeswitch for 50%& 100% opertion of luminaries also including automatic switching ON/OFFsystem. | — | — | — | 11,030.3 | |
| — | 1.00 | — | — | ||
| Supply of foundation bolts manfactured from special steel along with nuts, washers, anchor plates and templates. | — | — | — | 7,059.84 | |
| — | 1.00 | — | — | ||
| Supply testing and fixing of twin dome aviation obstruction lights with 1 no 25 W neon spiral lamp (2 fittings/mast necessary) | — | — | — | 1,356.66 | |
| — | 1.00 | — | — | ||
| "Design and casting of suitable shallow foundation with M-20 concrete (1:1.5:3) for 16 mtr high mast . The designing of high mast tower foundation should be done as per1.Type of Soil and soil bearing capacity of the site2.Wind loading3.Seismic zone4.Dynamic Loading Due to Vibration and Loading.5.Minimum factor of safety as per relevant IS standards should be ensured.Certificate regarding the above points must be approved before execution of work." | — | — | — | 32,209.43 | |
| — | 1.00 | — | — | ||
| Errection of high mast tower with the help of suitable equipments & wiring of luminaries with supply of necessary wiring materials as per IS. | — | — | — | 22,656.95 | |
| — | 2.00 | — | — | ||
| Supply and erection of 80 mm dia thickness not less than 4.0 mm, 3 mtr. long G.I.pipe earthing including connection to high mast with G.I.Flats size 25x5mm (2 nos per mast) including construction of earth pit, RCC earth cover slab 1/2" thick and earth continuity as per EIC at site. | — | — | — | 3,507.2 | |
| — | 50.00 | — | — | ||
| Supply and laying of 50 mm dia GI pipe thickness not less than 3.6 mm for protection of cable as per direction of EIC at site. | — | — | — | 27,972.5 | |
| — | 200.00 | — | — | ||
| Supply and testing of 1100 volt grade, 16 sq mm 4 core XLPE insulated and PVC sheathed Aluminium multistrand round armoured aluminium cable as per IS 7098(Part 1) 1988 with up to date amendments. | — | — | — | 72,924 | |
| — | 200.00 | — | — | ||
| Laying of above LT XLPE insulated armoured aluminium cables as per instruction of site engineer. | — | — | — | 2,540 | |
| — | 200.00 | — | — | ||
| Excavation of cable trench 0.75 mtrs. below the GL with laying of armored cable and refilling the same by supply of 70mm sand and soil after digging the earth. The laying of armoured cable should be done as per direction of Engineer at site. . | — | — | — | 32,400 | |
| — | 1.00 | — | — | ||
| Design, fabrication, supply, installation, testing and commissioning of outdoor type Panel board comprising of following items and made of MS angle, channel by MS sheet of not less than 18 SWG duly welded and painted by 2 coats of primer, two coats of finishing paint (spray paint) Doco/Nerolac brand of approved colour both in interior and exterior as per direction of EIC at site - i) 100A,4P, 18KA, Ics = 100% Icu, conforms to IEC 60947-2 MCCB - 1 nos, ii) 63A, MCB TPN - 2 nos, iii) 40A, MCB DP - 1 nos & iv) 200A 4P copper bus bar - 1 set. | — | — | — | 9,928 | |
| — | 10.00 | — | — | ||
| Horizontal machine borring under track crossing at a depth of 2.0 mtr below GL including required size HDPE pipe observing all necessary safety for human life and others movement as per direction of engineer at site. | — | — | — | 57,190 | |
| — | 200.00 | — | — | ||
| Supply and testing of 1100 volt grade, 50 sq mm 4 core XLPE insulated and PVC sheathed Aluminium multistrand round armoured aluminium cable as per IS 7098(Part 1) 1988 with up to date amendments. | — | — | — | 1,66,144 | |
| — | 200.00 | — | — | ||
| Laying of above LT XLPE insulated armoured aluminium cables as per instruction of site engineer. | — | — | — | 2,540 | |
| — | 12.00 | — | — | ||
| Supply, carrying, loading & unloading of 5 mtr long with suitable size designer single bracket G I octagonal pole including base plate, junction box and foundation bolt 4x16 Nos (Length 450mm) etc. and erection with execution of CC foundation work of size 45cmx45cm in ratio 1:2:4 by cement,sand and chips of size 19 mm and down upto full depth & 1ft above the GL as per direction of EIC at site & 6A SP MCB. | — | — | — | 2,31,240 | |
| — | 12.00 | — | — | ||
| Supply, installation, testing & commissioning of IP 65 45 watt street light fittings complete including all accessories as per direction of EIC at site . Lumens out put should be of 100 Lumens/watt, LED should be as per LM-80/IS: 16105. LED driver's efficiency should be minimum 90%, Power factor of complete fitting should be greater than 0.90, Input operating voltage: 140V to 277V AC and driver should be as per IEC: 62384/IS:16104. The LED fittings should be warranted for 5 years. | — | — | — | 69,600 | |
| — | 200.00 | — | — | ||
| Supply, testing of 1100 volt grade, 16 sq mm 4 core XLPE insulated and PVC sheathed aluminium multistrand armoured cable as per IS 7098(Part 1) 1988 with up to date amendments. | — | — | — | 72,924 | |
| — | 200.00 | — | — | ||
| Supply,testing of 1100 volt grade, 70 sq mm 4 core XLPE insulated and PVC sheathed aluminium multistrand armoured cable as per IS 7098(Part 1) 1988 with up to date amendments. | — | — | — | 2,23,000 | |
| — | 100.00 | — | — | ||
| — | 400.00 | — | — | ||
| — | 400.00 | — | — | ||
| — | 500.00 | — | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
ACS-09.pdf
ATTACHMENT
JPO8.5.24-CablediggingworksNFR.pdf
ATTACHMENT
GCC_April-2022_2022.pdf
ATTACHMENT
GCCUpdateduptoACS-11_1.pdf
ATTACHMENT
ACS-8_2.pdf
ATTACHMENT
Annexure_1.pdf
ATTACHMENT
ACS-10.pdf
ATTACHMENT
GCCACS11.pdf
ATTACHMENT
TechCircularwithDrgforEarthingandCableLayingUG.pdf Drawing for pipe earthing and cable lay
ATTACHMENT
RailwaysRB_TechnicalCircularofHighMast2.PDF
ATTACHMENT
TD-022026-27_1.pdf
ATTACHMENT
TechCircularwithDrgforEarthingandCableLayingUG.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .