Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.8 LAdmitted-Finance | ₹7.8 L | L1 | Admitted-Finance |
| 2 | L2₹7.9 LAdmitted-Finance | ₹7.9 L | L2 | Admitted-Finance |
| 3 | L3₹7.9 LAdmitted-Finance | ₹7.9 L | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | ENERGETIC CORPORATE L1 | Nugenix Robotics L2 | Impulse Solutions L3 |
|---|---|---|---|---|---|---|
| 1.00 | LIGHT POINT WIRING WITH MODULAR ACCESSORIES (CONCEALED) (RAB13:B58W+UPS)
Light Point Wiring (Modular, Concealed) Light point wiring in concealed manner using 1sq.mm CU/ PVC wires for phase, neutral and earth drawn in minimum 20 mm heavy-duty PVC conduit, including modular 6A switch, modular front plate and concealed metal box, complete as directed. Length up to 7.5 meters per point.
Make of wire: ISI grade best quality
Make of modular accessories: Legrand – Myrius NexGen
If LED luminaires are connected, the LED drivers shall be low RF noise type suitable for studio environment. | 1 | Nos | 20,256 ₹20,256 | 20,356 ₹20,356 | 20,400 ₹20,400 |
| 2.00 | FAN POINT WIRING in 1.5 Sq.mm CU/PVC wires (PNE) as above for with BEE 5 Star rated 1200mm BLDC
fan with remote control (Without Regulator) , which shall be suitable for studio environment and shall not generate
RF interference. Make of wire: ISI grade best quality Make of modular accessories: Legrand – Myrius NexGen Make of
Fan : Orient, Crompton, Atomberg - Nut Brown Color | 1 | Nos | 3,050 ₹3,050 | 3,150 ₹3,150 | 3,300 ₹3,300 |
| 3.00 | 6A SOCKET POINT WIRING (RAW+UPS) (Modular, Concealed) with socket points on Boards , wiring in concealed manner using 2 × 2.5 sq.mm PVC copper conductor wires for phase and neutral with 1 × 1.5 sq.mm copper earth wire drawn in PVC conduit, including modular 6A switch and 6A socket outlet with safety shutter, modular plate and concealed metal box, complete as directed.
Length up to 7.5 meters per point.
Make: ISI grade best quality & Legrand Myrius NexGen modular accessories. | 1 | Nos | 43,020 ₹43,020 | 43,120 ₹43,120 | 43,200 ₹43,200 |
| 4.00 | 16A Power Plug Point Wiring (Modular) (RAW+UPS)
16 Amp power plug point wiring in concealed manner using 2 × 2.5 sq.mm copper wire with 1 × 1.5 sq.mm earth wire, including modular 16A switch and 16A socket with safety shutter, modular plate and concealed metal box complete.Make: Polycab + Legrand MyriusNexGen | 1 | Nos | 6,100 ₹6,100 | 6,200 ₹6,200 | 6,300 ₹6,300 |
| 5.00 | MAIN DISTRIBUTION BOARD 8 Way TPN : 8 Way TPN Main Distribution Board (MDB), wall mounted, IP-42, powder coated sheet steel enclosure, complete with: 40A TPN MCCB outgoing feeder for RAW DB 32A TPN MCCB outgoing feeder for UPS DB
Provision for Type-2 SPD (415V, 3P+N) Adequately rated copper busbars Separate neutral and earth bars. Internal wiring, ferruling and circuit identification Complete as per IE Rules and relevant IS standards. Make: Legrand / L&T / Schneider (Approved Equivalent) | 1 | Nos | 40,950 ₹40,950 | 41,050 ₹41,050 | 41,100 ₹41,100 |
| 6.00 | DISTRIBUTION BOARDS & PROTECTION (RAW Power) Distribution Board : 24 Way SPN RAW Power Distribution Board, sheet steel enclosure, surface mounted, IP-42 protection, powder coated finish, complete with:• 40A Double Pole (DP) Isolator as incomer• 40A, 30mA DP RCCB (Type-A recommended for mixed loads)• Outgoing SP MCBs, C-Curve, 10kA breaking capacity• Separate full-size neutral bar and earth bar• Proper internal interconnections using FRLS copper links• Ferrule marking, circuit identification and neatly typed directory chart pasted inside DB door• Phase identification sleeves and danger board• All accessories required for complete installationComplete as per IE Rules, IS standards and site requirements.Make: Legrand DX³ / Schneider Acti9 / L&T . | 1 | Nos | 6,825 ₹6,825 | 6,925 ₹6,925 | 6,950 ₹6,950 |
| 7.00 | DISTRIBUTION BOARDS & PROTECTION (UPS Supply) Distribution Board : 12 Way SPN UPS Distribution Board, surface mounted, sheet steel enclosure, IP-42, powder coated, complete with: 32A Double Pole (DP) Isolator as incomer• 32A, 30mA DP RCCB (Type-A recommended)• Outgoing SP MCBs, C-Curve, 10kA• Independent full-size neutral bar (no common neutral with RAW DB)• Separate earth bar connected to Clean Earth System• Internal copper links with ferruling and circuit identification• Directory chart inside DB doorComplete as per IE Rules and site requirements.Make: Legrand DX³ / Schneider Acti9 / L&T Use: Studio equipment, critical loads and UPS circuits only. | 1 | Nos | 4,375 ₹4,375 | 4,475 ₹4,475 | 4,490 ₹4,490 |
| 8.00 | MCBs (Outgoing) - Total 29 Nos
Supplying and fixing SP MCB, C-Curve, 10 kA breaking capacity, ISI marked, suitable for lighting, socket, UPS and power circuits, complete. Make: Legrand Series: DX³ -Details as below: –
SP MCB 10A – Lighting Circuits 7 Nos
SP MCB 16A – RAW Socket Circuits 5 Nos SP MCB 16A – UPS Circuits 6 Nos
SP MCB 20A/25A – AC / Power / Tx 5 Nos
SP MCB 10A/16A – Spare 6 Nos | 1 | Nos | 13,550 ₹13,550 | 13,650 ₹13,650 | 13,680 ₹13,680 |
| 9.00 | Surge Protection Device (SPD) : Type-2 SPD, 415V, 3P+N, minimum 40kA discharge capacity, suitable for installation in existing TPN panel, complete with backup MCB, termination and testing.Make: OBO / Schneider / Legrand | 1 | Nos | 34,580 ₹34,580 | 34,680 ₹34,680 | 34,730 ₹34,730 |
| 10.00 | MCB Circuit Identification & Labelling:
Identification labels for all outgoing MCBs inside Distribution Boards, including typed directory chart pasted inside DB door, ferrule marking on wires, phase identification sleeves, and proper numbering of circuits, complete as per IE rules. 2 Nos (Per DB) | 1 | Nos | 3,650 ₹3,650 | 3,750 ₹3,750 | 3,800 ₹3,800 |
Tender Value
Refer Docs
EMD Value
₹20,000
Closing Date
6 Mar 2026, 5:30 pmClosed
registrar shivaji university kolhapur
shivaji university kolhapur
Supply, Installation, Testing and Commissioning of Proposed - A) Electrical and AC Wiring Work and B) Audio and Data Wiring Works at Shiv Vani Community Radio, Shivaji University, Kolhapur
2026_SUK_1282539_1
2025_2026_170
Open Tender
Electrical Works
work
Please refer Tender documents.
3 documents required · 3 mandatory
₹4,720
₹20,000
Yes
13 Mar 2026
27 Feb 2026
10 Mar 2026
27 Feb 2026
6 Mar 2026
27 Feb 2026
LIGHT POINT WIRING WITH MODULAR ACCESSORIES (CONCEALED) (RAB13:B58W+UPS) Light Point Wiring (Modular, Concealed) Light point wiring in concealed manner using 1sq.mm CU/ PVC wires for phase, neutral and earth drawn in minimum 20 mm heavy-duty PVC conduit, including modular 6A switch, modular front plate and concealed metal box, complete as directed. Length up to 7.5 meters per point. Make of wire: ISI grade best quality Make of modular accessories: Legrand – Myrius NexGen If LED luminaires are connected, the LED drivers shall be low RF noise type suitable for studio environment.
FAN POINT WIRING in 1.5 Sq.mm CU/PVC wires (PNE) as above for with BEE 5 Star rated 1200mm BLDC fan with remote control (Without Regulator) , which shall be suitable for studio environment and shall not generate RF interference. Make of wire: ISI grade best quality Make of modular accessories: Legrand – Myrius NexGen Make of Fan : Orient, Crompton, Atomberg - Nut Brown Color
6A SOCKET POINT WIRING (RAW+UPS) (Modular, Concealed) with socket points on Boards , wiring in concealed manner using 2 × 2.5 sq.mm PVC copper conductor wires for phase and neutral with 1 × 1.5 sq.mm copper earth wire drawn in PVC conduit, including modular 6A switch and 6A socket outlet with safety shutter, modular plate and concealed metal box, complete as directed. Length up to 7.5 meters per point. Make: ISI grade best quality & Legrand Myrius NexGen modular accessories.
16A Power Plug Point Wiring (Modular) (RAW+UPS) 16 Amp power plug point wiring in concealed manner using 2 × 2.5 sq.mm copper wire with 1 × 1.5 sq.mm earth wire, including modular 16A switch and 16A socket with safety shutter, modular plate and concealed metal box complete.Make: Polycab + Legrand MyriusNexGen
MAIN DISTRIBUTION BOARD 8 Way TPN : 8 Way TPN Main Distribution Board (MDB), wall mounted, IP-42, powder coated sheet steel enclosure, complete with: 40A TPN MCCB outgoing feeder for RAW DB 32A TPN MCCB outgoing feeder for UPS DB Provision for Type-2 SPD (415V, 3P+N) Adequately rated copper busbars Separate neutral and earth bars. Internal wiring, ferruling and circuit identification Complete as per IE Rules and relevant IS standards. Make: Legrand / L&T / Schneider (Approved Equivalent)
DISTRIBUTION BOARDS & PROTECTION (RAW Power) Distribution Board : 24 Way SPN RAW Power Distribution Board, sheet steel enclosure, surface mounted, IP-42 protection, powder coated finish, complete with:• 40A Double Pole (DP) Isolator as incomer• 40A, 30mA DP RCCB (Type-A recommended for mixed loads)• Outgoing SP MCBs, C-Curve, 10kA breaking capacity• Separate full-size neutral bar and earth bar• Proper internal interconnections using FRLS copper links• Ferrule marking, circuit identification and neatly typed directory chart pasted inside DB door• Phase identification sleeves and danger board• All accessories required for complete installationComplete as per IE Rules, IS standards and site requirements.Make: Legrand DX³ / Schneider Acti9 / L&T .
DISTRIBUTION BOARDS & PROTECTION (UPS Supply) Distribution Board : 12 Way SPN UPS Distribution Board, surface mounted, sheet steel enclosure, IP-42, powder coated, complete with: 32A Double Pole (DP) Isolator as incomer• 32A, 30mA DP RCCB (Type-A recommended)• Outgoing SP MCBs, C-Curve, 10kA• Independent full-size neutral bar (no common neutral with RAW DB)• Separate earth bar connected to Clean Earth System• Internal copper links with ferruling and circuit identification• Directory chart inside DB doorComplete as per IE Rules and site requirements.Make: Legrand DX³ / Schneider Acti9 / L&T Use: Studio equipment, critical loads and UPS circuits only.
MCBs (Outgoing) - Total 29 Nos Supplying and fixing SP MCB, C-Curve, 10 kA breaking capacity, ISI marked, suitable for lighting, socket, UPS and power circuits, complete. Make: Legrand Series: DX³ -Details as below: – SP MCB 10A – Lighting Circuits 7 Nos SP MCB 16A – RAW Socket Circuits 5 Nos SP MCB 16A – UPS Circuits 6 Nos SP MCB 20A/25A – AC / Power / Tx 5 Nos SP MCB 10A/16A – Spare 6 Nos
Surge Protection Device (SPD) : Type-2 SPD, 415V, 3P+N, minimum 40kA discharge capacity, suitable for installation in existing TPN panel, complete with backup MCB, termination and testing.Make: OBO / Schneider / Legrand
MCB Circuit Identification & Labelling: Identification labels for all outgoing MCBs inside Distribution Boards, including typed directory chart pasted inside DB door, ferrule marking on wires, phase identification sleeves, and proper numbering of circuits, complete as per IE rules. 2 Nos (Per DB)
Manual 2 Way Change Over switch: with mounting box 32A TPN 440V/ 2 Way (UPS/RAW Power)
Danger Board & Rubber Mat: Approved electrical Danger Board & 3 mm thick insulated Rubber Mat each of standard size near Main Electrical Panel and Distribution Boards as per IE Rules, in front of electrical panel for operator safety, complete as directed.
Four Core CU Studio Main Feeder Cable: – 4 Core × 6 sq.mm PVC copper unarmoured cable along with 1 Core × 4 sq.mm copper earth wire, laid in heavy-duty PVC conduit (minimum 32 mm) / perforated cable tray from Main Electrical Panel to Studio Main Distribution Board (MDB), including termination with suitable glands, tinned copper lugs, proper dressing, clamping, ferruling, identification marking, testing and commissioning, complete as directed by Engineer-in-Charge. Cable shall be 1100V grade, ISI marked, suitable for indoor installation.
Four Core CU DB Feeder Cable (Unarmoured- RAW Power): 4 Core × 6 sq.mm PVC copper unarmoured cable along with 1C × 4 sq.mm earth wire, laid inside PVC conduit from Main Panel to RAW Distribution Board, including termination with glands & lugs, complete. As per actual distance
Four Core CU DB Feeder Cable (Unarmoured- UPS Power): 4 Core × 4 sq.mm PVC copper unarmoured cable along with 1C × 2.5 sq.mm earth wire, laid inside PVC conduit from UPS Output to UPS Distribution Board, complete with termination and accessories. Cable shall be laid in heavy duty PVC conduit (minimum 32mm for 10 sqmm feeder) or on perforated cable tray as required.
Lightining Circuits in CU-PVC wires (RAW Power): 3 × 1.5 sqmm PVC Cu (L+N+E) (MCB-10A SP)Separate neutral, no looping of Neutral
6A Socket Circuits in CU-PVC wires (RAW Power): - 3 × 1.5 sqmm PVC Cu (L+N+E) (MCB-10A SP)Separate neutral, no looping of Neutral
6A Socket Circuits in CU-PVC wires (UPS Power): Socket Circuits 2 × 2.5 sqmm + 1 × 1.5 sqmm FRLS (MCB-16A SP) -Independent neutral from UPS DB -No looping in points
16A Power Socket Circuits in CU-PVC wires (RAW Power): 2 × 4 sqmm + 1 × 2.5 sqmm (MCB-20A SP) -Independent neutral-No looping
Lightining Circuits in CU-PVC wires (UPS Power): 3 × 1.5 sqmm FRL (SP MCB-10A SP) Separate neutral from UPS DB without looping.
Transmitter Circuits in CU-PVC wires (UPS Power): Heavy Load Cuircuit 2 × 6 sqmm + 1 × 2.5 sqmm PVCS MCB-25A SP - Separate neutral from UPS DB without looping.
Equipment Earthing (Clean Equipment Earth Wiring) : 1.5 sq.mm ISI grade - Best quality wires copper single core green colour earth wire (Polycab or approved equivalent) drawn inside PVC conduit / trunking from Copper Clean Earth Bus Bar to individual audio equipment, studio racks, consoles and sensitive electronic equipment, including termination with suitable lugs, ferruling, identification marking and continuity testing, complete as directed by Engineer-in-Charge. The equipment earth shall be independent from RAW power earth and connected only to the Clean Earth (Copper Plate Earth Pit Box).
Supplying & Fixing of Ceiling Fan : Supply & Installation of BLDC Ceiling FanSupplying and installing 1200 mm sweep BLDC energy efficient ceiling fan complete with mounting bracket, canopy, downrod, safety shackle, and necessary hardware, including connection to existing fan point, testing and commissioning complete as directed.Fan shall be suitable for studio environment and shall not generate RF interference.Make: Crompton / Havells / Orient
Providing & fixing Anchor fastner : with Rods from Ceiling suitable for Ceiling Fans with fan hook
CCTV :- IP Dome Camera (Indoor) 2MP IP Dome Camera (3.6 mm fixed lens), Full HD (1920×1080), IR night vision minimum 20–30 meters, IP-based, suitable for indoor installation, complete with mounting accessories, bracket, power supply through PoE, necessary wiring and configuration with NVR as directed. Make: D-Link / CP Plus / Hikvision
8 Channel Network Video Recorder (NVR) : Fully Compatible with IP cameras, supporting minimum 1080P recording, HDMI/VGA output, LAN connectivity, USB backup facility, complete with configuration and integration with cameras, as directed.Make: D-Link/ Hikvision / Dahua / CP Plus
2TB Surveillance Hard Disk: Supplying and installing 2TB surveillance grade SATA hard disk suitable for 24×7 CCTV recording, optimized for video surveillance applications, compatible with supplied NVR, complete with installation and testing. Make: WD Purple / Seagate SkyHawk
Data Network, CAT-6 UTP Cable for Computers & CCTV : Supplying, laying and terminating CAT-6 UTP cable for interconnection of IP CCTV cameras, drawn inside suitable size PVC conduit, including saddles, bends, junction boxes, terminations with RJ-45 connectors, testing and commissioning complete as directed.Make: D-Link
Data Network - PoE Network Switch : Supplying, installing and commissioning 8 Port PoE + 2 Uplink Gigabit Network Switch, IEEE 802.3af/at compliant, suitable for powering IP cameras, complete with rack mounting / wall mounting accessories and testing. Make: D-Link / TP-Link
Network and Telephone cable:-CAT-6 UTP LAN Cable Supplying, laying and terminating CAT-6 UTP cable (4 Pair, 23 AWG), suitable for Gigabit Ethernet, drawn inside suitable size PVC conduit / trunking, including saddles, bends, proper dressing, testing with LAN tester and commissioning complete as directed. Make: D-Link
Smoke Detector System Complete : 4 Optical type smoke detector, complete with mounting base, single zone wiring, necessary accessories and integration & Alarm system, complete as directed. Make: Honeywell / Agni
RJ-11 Telephone Sockets: Supplying and fixing modular RJ-11 telephone socket outlet, complete with front plate and concealed metal box, interconnection using 2-pair unarmoured telephone cable, termination, testing and commissioning complete.
5 Pair Telephone Cable : Supplying and laying 5-pair unarmoured telephone cable inside PVC conduit / trench with proper protection, including termination, testing and commissioning complete as directed.
TV Socket : Supplying and fixing ISI marked modular TV socket (single outlet), complete with concealed box, front plate, wiring connection and testing.
RG-11 Coaxial Cable : Supplying and laying low-loss RG-11 coaxial cable inside PVC conduit, including connectors, termination, testing and commissioning complete.
Ceiling Speakers : Supplying and installing circular ceiling / wall mounted speakers suitable for discussion hall use, complete with mounting arrangement, testing and commissioning. Make: Ahuja / Bosch / JBL
Speaker Wiring : Supplying and laying 2 Core 1.5 sq.mm copper flexible speaker cable (or 23/36 twin flat copper flexible wire as specified), drawn inside 20 mm PVC conduit from amplifier to speaker points, including termination and testing complete.
D-Link I/O Box : Supplying and installing D-Link I/O Box (Dual Line – 2 Nos, Single Line – 4 Nos), complete with mounting, cable termination, configuration and testing
Audio & Data Cable Trench : Cutting, making and finishing cable trench in existing floor/wall for laying Audio, Network, Telephone and HDMI cables as per approved layout drawing, including:Machine cutting of floor tiles / wall surfaceTrench size approximately 150 mm width × 75 mm depth (or as required at site)Providing and fixing heavy-duty PVC casing/trunking ( 50 × 38 mm X Two Nos. ) Laying of Audio, LAN, Telephone and HDMI cables with proper segregation from power routesProviding warning tape inside trenchRefilling with sand / cement mortarRe-fixing tiles with matching finishDisposal of debris and surface cleaningComplete as per site requirement and direction of Engineer-in-Charge.
Supply & Installation of 1.0 TR Split Air Conditioner (Low Noise Type) 1.0 TR Inverter Split Air Conditioner, 230V, 50Hz, complete with indoor and outdoor units, copper interconnecting refrigerant piping with insulation, drain piping, control cable, mounting brackets, vibration pads and all necessary accessories. Unit shall be low noise type, suitable for studio environment. Indoor unit sound level ≤45-50 dB(A) at maximum speed. Make: Daikin / Mitsubishi (Approved Equivalent)
36W LED Ceiling Panel Light (2’ × 2’): 36 Watt LED Ceiling Panel Light, 2’ × 2’ size, slim recessed type, powder coated housing, high efficiency diffuser, complete with LED driver suitable for studio use (low RF noise), mounting accessories and connections. Make: Havells / Wipro / Philips (Approved Equivalent)
15W LED Downlight : 15 Watt LED recessed downlight, suitable for false ceiling installation, complete with driver, housing and wiring connections. Make: Havells / Wipro (Approved Equivalent)
LED Wall Lamp : Supplying and installing 12 watt LED Wall Mounted Light Fixture, decorative type, complete with mounting hardware and internal driver. Make: Havells / Wipro / Philips (Approved Equivalent)
EARTHING SYSTEM with 40mm GI Pipe, Supply, installation, testing and commissioning of GI pipe Earthing by providing 40 mm dia, 3.0 m long B-class GI pipe electrode, including excavation, Minimum 25Kg Bentonite Power fill, watering arrangement, masonry chamber with CI cover, testing earth resistance less than 1 ohm, complete as directed. Use: Earthing for UPS DB, lighting, sockets, AC body. etc
Neutrik XLR Connector Male, 3-Pin, Silver Plated
Neutrik XLR Connector Female, 3-Pin, Silver over Nickel Plated
Neutrik 1/4" Mono Jack Plug, Ultra Slim
Floor/Surface Mount Stage Box with 4 XLR Female & 4 TRS Female
Professional Balanced Audio Cable 2 Core x 24 AWG OFC, ≥90% Shielding, PVC Jacket (Make: Belden 8412 / 9451 or Equivalent – Mogami / Canare)
24 x 1/4" Audio Patch Panel, Suitable for 19" Rack Mounting, make-- Neutrik / Mouser
Work of laying and testing of cables between all Studios & Transmitter incliding, /interconnections, terminations with connectors, fixing in conduits and trays as required complete job work. & Commissioning Charges
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
Tendernotice_2.pdf
PDF • 1.17 MB
BOQ_2205862.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid