Office of the Executive Engineer Construction Division Leh
Electrification for Digital X-Ray Room and additional wiring in NICO Ward, Labour Room, Recovery word etc, providing and laying main cables to MRI and providing and fixing main panel with cable an existing Oxygen Plant in SNM Hospital Leh.
2021_PWD_5171_2
188 of CDL Leh of 2021-22
Open Tender
Electrical Works
Item Rate
30 days
Leh
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Construction Division Leh
₹29,600
27 Dec 2021
9 Nov 2021
22 Nov 2021
10 Nov 2021
20 Nov 2021
10 Nov 2021
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. a)2 x 2.5 Sq.mm + 1 x 2.5 Sq.mm earth wire
b)4 x 10 Sqmm + 2 x 6 Sq.mm earth wire ( with out earthing wire )
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required .1x 4 sq.mm
1x 2.5 sqmm
2 x 10 Sq.mm
1 x 16 Sq.mm
Supplying and fixing following modular type switch/socket on the existing switch box cover including connections etc. as required. 5/6 A switch
3 pin 5/6 A socket outlet
15/16 A switch
6 pin 15/16 A socket outlet
Suppling and fixing following size /modules ,GI box along with modular base & cover plate for modular switches in recess etc as required . 3 module
6 module
Supply and fixing following modular base & cover plate on existing modular metal boxes etc as required 3 Module
3 Module
6 Module
12 Module
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way (4+24) Double Door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required .Single pole 6/16 amp.
Supplying and Fixing following ratings , double pole ,240 V , isolator in the existing MCB .DB complete with connections , testing and commissioning etc as required 40 A
Supply and fixing of following sizes of PVC conduit alongwith accessories in surface/recessed including cutting the wall and making good the same in case of recessed conduit as required 25 mm
Supply, installation, testing & commissioning of GI Electrode Earthing with 50mm dia GI pipe ISI marked and 3 meter length, with 40mm x 5mm thick electrode, the electrode should be hot-dip galvinised. The GI Electrode shall be pre-filled with Cristaline Conductive Materila (CCM). The GI electrode shall be surrounded with BEE MOIST compound to provide maximum contact betwen the electrode and compound should be eco-friendly GI Electrode Earthing should be maintinance free and does not require regular manual addition of water . The earthing pit should be covered with PVC cover.
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. MCCB FP 100 Amp 30 KA
MCCB FP 200 Amp 36 KA
MCCB FP 250 Amp 36 KA
MCCB FP 320 Amp 50 KA
MCCB FP 400 Amp 36 KA
Change over Switch 200 Amp MCCB Type FP
Change over Switch 400 Amp MCCB Type FP
Fabrication ,supplying ,installation testing and commisssioning of following pannel made out of 2mm thick M.S sheet, wall mounted ,vermin & dust proof ,outdoor type with lockable type hinged doors,duly painted with provision for fixing of 1 no incomer MCCB,MCCB type change over switch -1 No including supply and fixing 2 set of Aluminium Bus bar ,and strip for housing MCB,s 24 Nos , MF Digital Meter and and other allied accessories as required .(Make as per annexure)
Fabrication ,supplying ,installation testing and commisssioning of following pannel made out of 2mm thick M.S sheet, wall mounted ,vermin & dust proof ,outdoor type with lockable type hinged doors,duly painted with provision for fixing of 1 no. incomer MCCB, 2 No.s MCCBs out going , MCCB type change over switch -1 No including supply and fixing 2 set of Aluminium Bus bar ,and strip for housing MCB,s 24 Nos , MF Digital Meter and and other allied accessories as required .(Make as per annexure)
Supplying and fixing of following rating 240/415 Volt's "C" Series miniature circuit breaker suitable for lighting and other loads of following poles in the existing MCB DB complete with connections, testing and commissioning (Above to 32 Amp.).SPN 40 Amp
TPN 63 Amp
Supplying and fixing of 1.1 KV PVC insulated and PVC sheathed XLPE at Power Cable of following sizes on surface/surface cable tray,/ 0.50 mtr bleow ground level etc. as required including carriage upto site of work. (Make as per annexure enclosed) 150 Sq mm 3.5 Core Armoured
240 Sq mm 3.5 Core Armoured
Supply and fixing following luminaries as required . 20 watt LED tube light fitting. LL20-221-XXX-65NE3 of wipro or equivalent make and model Philips/Crompton Greaves.
9 watt LED Lamp
Indicator red lamp with holder
LED type down lighter 15 Watt , including cutting of holes etc as required.
Supply and fixing single pole blanking plate in the existing MCB DB complete etc as required
Supply and fixing PVC casing and capping along with acceriories of following sizes etc as required 32mm
Supplying and drawing of FR PVC insulated copper conductor single core cable of following sizes etc as required 35 Sq.mm
Supply and making end termination with brass compression gland and aluminuin lugs for the following suze of PVC insulatedband PVC sheathed /XLPE aluminuin conductor cable of 1.1 KV grade as required 3 (1/2) x150 sq.mm ( 50 mm)
3 (1/2) x 240 Sq.mm ( 62mm )
Supply and making end termination with brass compression gland and copper lugs for the following size of PVC insulated copper conductor single core cable as required 35 sq.mm
Installation of split type air conditioner including testing and commissing etc as requried
Shifting of existing change over switch handle type after dismantelling cables to new place including drilling of holes nuts bolts including connections etc as required
Supply and fixing MCB DB PVC type two way .
Supply and drwaing 1.5 Sq.mm 3 core copper cable in the existing PVC conduit as required
Supplying, installation testing and commissioning of LED 2'x2' recess mounted fixture that delivers atleast 3000 lumens and wattage not more than 36 watt. The luminaries shall have a CRC a power coated body and a high efficiency diffuser. WIPRO CRCO10 RO 38HP57GL OR equivalent approved make.
M/S TASHI PHUNTSOG GOVT CONTRACTOR
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .