Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹50.3 LAccepted-AOC | 1 | Accepted-AOC Lowest Bidder | |
| 2 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical EMD/Fee not received |
Tender Value
₹47.1 L
EMD Value
₹94,284
Closing Date
13 Apr 2022, 6:00 pmClosed
CE and Head, TSD
TSD, BARC, Trombay, Mumbai-400085
Bi-ennial maintenance of fire hydrant system of BARC, Trombay, Mumbai-400085.
2022_BARC_679430_1
BARC/TSD/102/2021-22
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
730 days
BARC, Trombay, Mumbai
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹94,284
Yes
Conference Room, TSD bldg.
11 Jul 2022
22 Mar 2022
20 Apr 2022
22 Mar 2022
13 Apr 2022
6 Apr 2022
22 Mar 2022 - 7 Apr 2022
5 Apr 2022
Amount
Supply, installation, testing and commissioning of diesel engine operated pump-engine set of capacity 3300 lpm at 40 m WC as per clause no. 1 of technical specification.
Supply, installation, testing and commissioning of first aid hose reel of 20 mm dia X 30 meters long having swinging drum with cut off outlet nozzle and other assesories as per clause no. 2 of technical specification.
Supply and Installation of FRP hose cabinet of size 750 mmX 650 mm X 250mm along with hose pipe (2 nos) and branch pipe (1 no) as per clause no. 3 of technical specification.
Supply, installation, testing and commissioning of following sizes CI gate valves of existing fire hydrant network after removing existing defective valve, non return valve and fire hydrant valves and other accessories as per clause no. 4 of technical specification.
80 mm dia CI gate valve
100 mm dia CI gate valve
150 mm dia CI gate valve
150 mm dia CI NRV
80 mm landing type GM fire hydrant valve with 63 mm outlet.
150 mm dia butterfly valve
Routine testing and Maintenance of following fire hydrant system as per clause no. 5 of technical specification.
Fire Hydrant System Near CSU
Fire Hydrant System at PP Nursery
Fire Hydrant System at New IMS
Fire Hydrant System at North Gate
Overhauling of fire pumps of following type, capacity & head as per clause no. 6 of technical specification.
Main electric pump (vertical turbine pump), HP-40, Flow-2250 lpm, Head-70 m at North Gate.
Jockey pump (vertical turbine pump), HP-10, Flow-200 lpm, Head-70 m at North Gate.
Main electric pump (vertical turbine pump), HP-60, Flow-2250 lpm, Head-70 m at New IMS.
Jockey pump (vertical turbine pump), HP-10, Flow-200 lpm, Head-70 m installed at New IMS.
Diesel engine operated pump (vertical turbine pump), HP-105, Flow-2250 lpm, Head-70 m at New IMS.
Main electric pump (end suction pump), HP-100, Flow-3350 lpm, Head-70 m near CSU.
Main electric pump (end suction pump), HP-40, Flow-3350 lpm, Head-40 m near CSU.
Diesel Engine operated pump (end suction pump), HP-120, Flow-3350 lpm, Head-70 m near CSU.
Jockey pump (mono block pump), HP-5, Flow-200 lpm, Head-70 m at CSU.
Main electric pump (end suction pump), HP-120, Flow-4450 lpm, Head-80 m installed at PP Nursery.
Diesel Engine operated pump (end suction pump), HP-167, Flow-4450 lpm, Head-80 m at PP Nursery.
Jockey pump (end suction pump), HP-20, Flow-300 lpm, Head-80 m at PP Nursery.
Supply and installation of mechanical seal of fire pumps of following type, capacity & head as per clause no. 7 of technical specification.
Main electric pump (vertical turbine pump), HP-40, Flow-2250 lpm, Head-70 m at North Gate.
Jockey pump (vertical turbine pump), HP-10, Flow-200 lpm, Head-70 m at North Gate.
Main electric pump (vertical turbine pump), HP-60, Flow-2250 lpm, Head-70 m at New IMS.
Jockey pump (vertical turbine pump), HP-10, Flow-200 lpm, Head-70 m installed at New IMS.
Diesel engine operated pump (vertical turbine pump), HP-105, Flow-2250 lpm, Head-70 m at New IMS.
Main electric pump (end suction pump), HP-100, Flow-3350 lpm, Head-70 m near CSU.
Main electric pump (end suction pump), HP-40, Flow-3350 lpm, Head-40 m near CSU.
Diesel Engine operated pump (end suction pump), HP-120, Flow-3350 lpm, Head-70 m near CSU.
Jockey pump (mono block pump), HP-5, Flow-200 lpm, Head-70 m at CSU.
Main electric pump (end suction pump), HP-120, Flow-4450 lpm, Head-80 m installed at PP Nursery.
Diesel Engine operated pump (end suction pump), HP-167, Flow-4450 lpm, Head-80 m at PP Nursery.
Jockey pump (end suction pump), HP-20, Flow-300 lpm, Head-80 m at PP Nursery.
Monthly maintenance of fire hydrants valves installed at various locations in side BARC Complex as per clause no.8 of technical specification.
Routine mainentance of fire hydrants valves including accessories such as lugs, wheels, outlet washers etc.
Isolation of internal/external fire hydrant valves from main network for repair / replacement / maintenance of valves.
Supply and installation of rubber/leather washer (seat).
Replacement of GM/brass spindle with acessories
Leakages Identification and rectification in fire hydrant network as per clause no. 9 of technical specification.
Emergency break down/repair jobs on fire hydrant network including supply of required material as per clause no. 10 of technical Specifications.
Supply, fabrication, installation, testing & commisssioning of schedule-40, CS seamless pipe along with fittings up to 150 mm dia.
Installation, testing & commisssioning of schedule-40, CS seamless pipe along with fittings of size 150 mm dia.
Supply of welding material for emergency breakdown repair by welding of MS/CS pipe lines complete with final run and DP test.
Supply of material and wrapping of anti corrosive coating over CS pipes of varous sizes after cleaning and applying one coat of bituminous compound as per clause no. 11 of technical specification.
Monthly servicing/maintenance and breakdown maintenance of fire automation panel installed at New IMS, Nursary, near CSU and North Gate as per clause no 12 of technical specification.
Monthly servicing/maintenance of fire automation panel installed at New IMS, Nursary, near CSU and North Gate.
Breakdown maintenance of fire automation panel by replacement of defective parts.
Control panel battary 12V, 45ah with cables
Pressure switch
Power supply
Timer switch
Preventive maintenance of spinkler system installed at New IMS having pendent type sprinkler-40 nos, deludge valve, turbine type hooter etc. as per clause no. 13 of technical specification.
Monthly
Yearly
Miscellaneous civil works for repairing/attending breakdown on fire hydrant network as per clause no. 14 technical specification.
Manual excavation of soil including murram etc.
Excavation of rock/road/RCC.
Disposal of surplus earth.
Supply of material and casting of PCC (1:2:4).
Shahabad/locking tiles removing and re-installation.
Supply of material and miscellaneous fabrication/ mechanical works as per clauser no. 15 of technical specification.
Providing one coat of red oxide followed by two coats of enamel painting on fire hydrants and pipe line.
Supply, fabrication and installation of MS structure complete with two coats of red oxide and two coats of enamel paint.
Supply and installation of 3.0mm/5.0 mm thick rainforced rubber gasket for installation of valves, NRV, hydrant valve etc.
Supply and installation of MS/GI nut, bolt and washers for installation of valves, flanges etc.
Repairing/maintenance of automation panel of water level controller at IMS as per clause no. 16 of technical specification.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .