Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.5 LAdmitted-Finance 133 131 | GORAKHPUR | UTTAR PRADESH | 273001 | ₹2.5 L | L1 | Admitted-Finance |
| 2 | L2₹4.1 LAdmitted-Finance | ₹4.1 L | L2 | Admitted-Finance |
| 3 | L3₹5.5 LAdmitted-Finance | ₹5.5 L | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | QualityEngineers L2 | ADITI ENTERPRISES L1 | BE LIGHTNING SYSTEM PVT LTD L3 |
|---|---|---|---|---|---|---|
| 1.00 | Enclosed AUTO/Manual CHANGEOVER SWITCH WITH CONTROLLERS 4 POLE 415 V AC 3 PH, CAPACITY 630A make -HPL, SIEMENS,L&T,HAVELLS.
Rating & Service630 A, 4-pole, 415 V ±10%, 50 Hz, 3-phase 4-wire (TPN), TN-S earthing.Continuous transfer capacity 630 A; short-circuit withstand ≥ 50 kA (1 s) or site fault level.
Contactor-based ATS (2 × 4P power contactors) — fast transfer (100–300 ms).
busbars & Termination
ETP copper busbars sized for 630 A (neutral 100%, earth ≥50%), tinned palms, torque-marked lugs, top/bottom gland plate.
Controls & Logic
AMF controller with mains/alternate supply, phase loss/sequence, programmable delays (start, warm-up, transfer, re-transfer, cool-down), retries.
Local Auto/Manual/Test selector, start/stop, indicators (Mains, alternate source), alarms.
Safety & Interlocks
Mechanical + electrical interlock (no paralleling), door interlock, emergency stop.
Metering & Interface (optional)
Multifunction meter (V, A, kW, kWh)
Standards & Tests
IEC 61439-1/2, IEC 60947 series, IS 3043 wiring; routine tests: IR ≥1 GΩ (500 V), 2.5 kV AC dielectric, functional simulation. | 1 | EA | 1,11,805 ₹1.1 L | 1,16,551 ₹1.2 L | 3,54,000 ₹3.5 L |
| 2.00 | Submersible Pump 1.1KW/1.5HP, Discharge Range = 400 - 65 LPM, Power - 0.75/1.0KW/HP, HEAD = 5-11M,Speed = 2900rpm, Single Phase.MAKE-KIRLOSKAR,CROMPTON GREAVES,HAVELLS. | 2 | EA | 26,550 ₹53,100 | 9,379 ₹18,758 | 17,700 ₹35,400 |
| 3.00 | Technical Requirement
Item: 3×32-Way 800 A Enclosed Bolted Bus Bar Chamber with MCCB 800 A
Bus Bar Chamber
Type: Enclosed, bolted type, dust & vermin proof.
Rating: 800 A, 3-phase, 4-wire system, 50 Hz.
Ways: 3 rows × 32 ways each.
Material: High conductivity electrolytic copper / ETP grade aluminium bus bars, tinned plated.
Insulation: Heat-shrink / PVC sleeve, rated for 1100 V.
IP-55 protection.
Supports: Non-hygroscopic, non-tracking, high strength insulating supports.
Terminations: Suitable for cable lug connections.
Circuit Breaker (Incoming)
Type: MCCB, 800 A, 3-pole, 50 kA breaking capacity (minimum).
Trip Unit: Thermal-magnetic or electronic with adjustable overload & short circuit protection.
Conforms to IS/IEC 60947-2.
General
All equipment to comply with IS/IEC standards.
Proper earthing arrangement as per IS 3043.
Nameplate & identification marking for incoming & outgoing feeders.
All connections to be accessible for maintenance.
MAKE-HAVELLS,HPL,L&T,SCHNEIDER,C&S,ABB. | 1 | EA | 1,51,040 ₹1.5 L | 82,004 ₹82,004 | 1,20,360 ₹1.2 L |
| 4.00 | Item: 3×8-Way 200 A Enclosed Bolted Bus Bar Chamber with MCCB 200 A
Bus Bar Chamber
Type: Enclosed, bolted type, dust proof.
Rating: 200 A, 3-phase, 4-wire system, 50 Hz.
Ways: 3 rows × 8 ways each.
Bus Bar Material: High-conductivity electrolytic copper or ETP-grade aluminium, tinned plated.
Insulation: Heat-shrink / PVC sleeves rated for 1100 V.
Enclosure: CRCA steel sheet, min. 14 SWG, powder coated, IP-55 protection class.
Supports: Non-hygroscopic, non-tracking, high-strength insulating supports.
Terminations: Suitable for cable lug connections.
Circuit Breaker (Incoming)
Type: MCCB, 200 A, 3-pole, min. 36 kA breaking capacity at 415 V AC.
Trip Unit: Thermal-magnetic or electronic with adjustable overload & short-circuit protection.
Conforms to IS/IEC 60947-2.
General
All equipment to comply with relevant IS/IEC standards.
Earthing arrangement as per IS 3043.
Nameplates & identification markings for incoming and outgoing feeder
MAKE-HPL,SCHNEIDER,ABB,C&S,HAVELLS,L&T | 1 | EA | 90,860 ₹90,860 | 34,161 ₹34,161 | 41,300 ₹41,300 |
Updated dates
Tender Value
Refer Docs
EMD Value
₹5,000
Closing Date
31 Dec 2025, 9:00 amClosed
SE, MMC, PTPP, PARICHHA
O/o SE, MMC, PTPP, PARICHHA
Supply of Portable submersible pumps, Automatic changeover Switch and bus bar chamber in PTPP, Parichha, Jhansi (UP)-284305.
2025_RVUNL_1083416_1
N-PAR/B/MMC1/PD01/6000009452
Open Tender
Electrical Work/ Equipment
180 days
PTPP, PARICHHA
As per tsd
3 documents required · 3 mandatory
₹590
DY CAO CFA BO PTPP PARICHHA
₹5,000
29 Jan 2026
17 Oct 2025
3 Jan 2026
17 Oct 2025
31 Dec 2025
17 Oct 2025
17 Oct 2025 - 31 Dec 2025
Submersible Pump 1.1KW/1.5HP, Discharge Range = 400 - 65 LPM, Power - 0.75/1.0KW/HP, HEAD = 5-11M,Speed = 2900rpm, Single Phase.MAKE-KIRLOSKAR,CROMPTON GREAVES,HAVELLS.
Technical Requirement Item: 3×32-Way 800 A Enclosed Bolted Bus Bar Chamber with MCCB 800 A Bus Bar Chamber Type: Enclosed, bolted type, dust & vermin proof. Rating: 800 A, 3-phase, 4-wire system, 50 Hz. Ways: 3 rows × 32 ways each. Material: High conductivity electrolytic copper / ETP grade aluminium bus bars, tinned plated. Insulation: Heat-shrink / PVC sleeve, rated for 1100 V. IP-55 protection. Supports: Non-hygroscopic, non-tracking, high strength insulating supports. Terminations: Suitable for cable lug connections. Circuit Breaker (Incoming) Type: MCCB, 800 A, 3-pole, 50 kA breaking capacity (minimum). Trip Unit: Thermal-magnetic or electronic with adjustable overload & short circuit protection. Conforms to IS/IEC 60947-2. General All equipment to comply with IS/IEC standards. Proper earthing arrangement as per IS 3043. Nameplate & identification marking for incoming & outgoing feeders. All connections to be accessible for maintenance. MAKE-HAVELLS,HPL,L&T,SCHNEIDER,C&S,ABB.
Item: 3×8-Way 200 A Enclosed Bolted Bus Bar Chamber with MCCB 200 A Bus Bar Chamber Type: Enclosed, bolted type, dust proof. Rating: 200 A, 3-phase, 4-wire system, 50 Hz. Ways: 3 rows × 8 ways each. Bus Bar Material: High-conductivity electrolytic copper or ETP-grade aluminium, tinned plated. Insulation: Heat-shrink / PVC sleeves rated for 1100 V. Enclosure: CRCA steel sheet, min. 14 SWG, powder coated, IP-55 protection class. Supports: Non-hygroscopic, non-tracking, high-strength insulating supports. Terminations: Suitable for cable lug connections. Circuit Breaker (Incoming) Type: MCCB, 200 A, 3-pole, min. 36 kA breaking capacity at 415 V AC. Trip Unit: Thermal-magnetic or electronic with adjustable overload & short-circuit protection. Conforms to IS/IEC 60947-2. General All equipment to comply with relevant IS/IEC standards. Earthing arrangement as per IS 3043. Nameplates & identification markings for incoming and outgoing feeder MAKE-HPL,SCHNEIDER,ABB,C&S,HAVELLS,L&T
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.03 MB
tsd.pdf
Tender Documents • 0.75 MB
BOQ_1984593.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid