| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.7 LAccepted-AOC 25 A RR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | L1 | Accepted-AOC Admitted | |
| 2 | L2₹12.0 L+₹27,514.50 (2.35%)Rejected-AOC | L2 | Rejected-AOC Admitted | |
| 3 | L3₹14.0 L+₹2.3 L (19.2%)Rejected-AOC H NO 111 553 64 CATTLE POUND TOWARDS AVA HILL CAMP ROAD ARUVANKADU NILGIRIS DIST TAMIL NADU 643 202 | THE NILGIRIS | TAMIL NADU | 643202 | L3 | Rejected-AOC Admitted |
Tender Value
Refer Docs
EMD Value
₹24,200
Closing Date
20 Mar 2021, 6:00 pmClosed
GE Wellington
Garrison Engineer Wellington Barrack Post Nilgiris Pin code-643231
SPECIAL REPAIR REPLACEMENT FOR CONVERSION OF OVERHEAD LINE INTO LT UG CABLE FOR CSQ MD ACCN AND JCOs ORs MD ACCN AT MANDIR LINE UNDER GE WELLINGTON
2021_MES_421685_1
8626/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Wellington
As per Tender Documents
4 documents required · 4 mandatory
₹500
GE Wellington
₹24,200
Yes
20 Apr 2021
12 Feb 2021
22 Mar 2021
13 Feb 2021
20 Mar 2021
27 Feb 2021
Amount
Excavation in trenches not exceeding 1.5 meter deep and not exceeding 1.5 meter wide and gettting out in Soft/ Loose soil for laying of under ground cable, and foundation of poles, etc complete all as specified and as directed
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each, complete all as specified and directed.
Removing of excavated soil/ material not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Spreading clean dry riddled sand in trenches for cushioning all as specified for cable protection in trenches / ducts complete all as specified and as directed. Note: Punned thickness only shall be measured and paid.
Bricks sub class ‘B’ to be laid over dry sand cushioning in trenches as protection to cable all as specified and directed.
Cutting PCC/ road 200mm thick for laying of cable all as specified and directed.
Supply, lay and testing in trench, ducts or floor or along the surface of wall, cable XLPE insulated screened PVC bedded, galvanised Steel Strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 3.5Core x 150Sqmm complete all as specified and directed.
Supply, lay and testing in trench, ducts or floor or along the surface of wall, cable XLPE insulated screened PVC bedded, galvanised Steel Strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 3.5Core x 120Sqmm complete all as specified and directed.
Supply, lay and testing in trench, ducts or floor or along the surface of wall, cable XLPE insulated screened PVC bedded, galvanised Steel Strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 4Core x 25Sqmm complete all as specified and directed.
Supply, lay and testing in trench, ducts or floor or along the surface of wall, cable XLPE insulated screened PVC bedded, galvanised Steel Strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 4Core x 16Sqmm complete all as specified and directed.
Supply, lay and testing in trench, ducts or floor or along the surface of wall, cable XLPE insulated screened PVC bedded, galvanised Steel Strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 2Core x 16Sqmm complete all as specified and directed.
Supply, install, testing and commissioning of factory made CPRI approved LT panel board 415 Volts, 50 Hz, 250 Amps capacity outdoor cubical type LT disribution switch gear and control gear, leg mounted, totally enclosed, cubical type modular compartment , dust and vermin proof IP-54 with neoprene gasket, fabricated out of CRCA sheet of thick ness not less than 3.15 mm complete with 2 mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50mmx50mmx6mm with cable chamber for incoming, outgoing connections comprising for the following including necessary PCC foundation of minimum 0.20 Mtr height positioned and fixed with suitable nuts, bolts, washers etc to the pedestal and connecting all incoming and outgoing cables all as specified and directed. (a) Aluminium Bus bar four wire system 415 volts mounted on procelain heat shrinkable insulator & sleeve suitable for 400 Amps for phases and 200 Amps for neutral . (b) LED type Indicating lamps for all the three phase with different colour lamp red,yellow and green.- 1 set (c) Digital multi function panel meter measuring voltage, Amps and frequency with suitabe CTs and backup protection - 1 No (d) Danger notice board of size 200mm x 150mm x 1.6mm thick of mild steel sheet vitreous enamelled white and letter figur and convention skull and bones of signal red colour and fixed/revited with panel- 02 Nos (e) Incoming (i) MCCB 3 pole with nuetral link, 35 KA, 250 Amps 415 volts - 01 No (f) Outgoing (i) MCCB 3 pole with nuetral link, 35 KA, 160 Amps 415 volts - 01 No (ii) MCCB 3 pole with nuetral link, 25 KA, 63 Amps 415 volts - 02 Nos (iii) MCCB 3 pole with nuetral link, 25 KA, 40 Amps 415 volts - 01 No (iv) MCCB 3 pole with nuetral link, 16 KA, 40 Amps 415 volts - 01 No
Supply, install, testing and commissioning of factory made LT panel board No. 02, TPN 415 Volts, 50 Hz, 320 Amps capacity outdoor cubical type LT disribution switch gear and control gear, leg mounted, totally enclosed, cubical type modular compartment , dust and vermin proof IP-54 with neoprene gasket, fabricated out of CRCA sheet of thick ness not less than 3.15 mm complete with 2 mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50x50x6mm with cable chamber for incoming outgoing connections comprising for the following including necessary PCC foundation of minimum 0.20 Mtr height positioned and fixed with suitable nut, bolts, washers etc to the pedestal and connecting all incoming and outgoing cables all as specified and directed. (a) Aluminium Bus bar four wire system 415 volts mounted on procelain heat shrinkable insulator & sleeve suitable for 500 Amps for phases and 250 Amps for neutral . (b) LED type Indicating lamps for all the three phase with different colour lamp red,yellow and green.- 1 set (c) Digital multi function panel meter measuring voltage, Amps and frequency with suitabe CTs and backup protection - 1 No (d) Danger notice board of size 200mm x 150mm x 1.6mm thick of mild steel sheet vitreous enamelled white and letter figur and convention skull and bones of signal red colour and fixed/revited with panel- 02 Nos (e) Incoming (i) MCCB 3 pole with nuetral link , 35 KA, 320 Amps 415 volts - 01 No (f) Outgoing (i) MCCB 3 pole with nuetral link 35 KA, 160 Amps 415 volts - 02 Nos (ii) MCCB 3 pole with nuetral link, 25 KA, 100 Amps 415 volts - 02 Nos (iii) MCCB 3 pole with nuetral link, 16 KA, 40 Amps 415 volts - 01 No
Supply, install, testing and commissioning of factory made CPRI approved 415 Volts, 50 Hz, 250 Amps capacity outdoor cubical type LT disribution switch gear and control gear, leg mounted, totally enclosed, cubical type modular compartment , dust and vermin proof IP-54 with neoprene gasket, fabricated out of CRCA sheet of thick ness not less than 3.15 mm complete with 2 mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50mmx50mmx6mm with cable chamber for incoming, outgoing connections comprising for the following including necessary PCC foundation of minimum 0.20 Mtr height positioned and fixed with suitable nuts, bolts, washers etc to the pedestal and connecting all incoming and outgoing cables all as specified and directed. (a) Aluminium Bus bar four wire system 415 volts mounted on procelain heat shrinkable insulator & sleeve suitable for 400 Amps for phases and 200 Amps for neutral. (b) LED type Indicating lamps for all the three phase with different colour lamp red,yellow and green.- 1 set (c) Digital multi function panel meter measuring voltage, Amps and frequency with suitabe CTs and backup protection - 1 No (d) Danger notice board of size 200mm x 150mm x1.6 mm thick of mild steel sheet vitreous enamelled white and letter figur and convention skull and bones of signal red colour and fixed/revited with panel- 02 Nos (e) Incoming (i) MCCB 4 pole , 35 KA, 250 Amps 415 volts - 01 No (f) Outgoing (i) MCCB 4 pole, 35 KA, 160 Amps 415 volts - 02 Nos (ii) MCCB 4 pole, 25 KA, 100 Amps 415 volts - 01 No (iii) MCCB 4 pole, 25 KA, 63 Amps 415 volts - 01 No (iv) MCCB 4 pole, 16 KA, 40 Amps 415 volts - 01 No
Supply, install, testing and commissioning of factory made LT panel board No. 04, TPN 415 Volts, 50 Hz, 200 Amps capacity outdoor cubical type LT disribution switch gear and control gear, leg mounted, totally enclosed, cubical type modular compartment , dust and vermin proof IP-54 with neoprene gasket, fabricated out of CRCA sheet of thick ness not less than 3.15 mm complete with 2 mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50mmx50mmx6mm with cable chamber for incoming, outgoing connections comprising for the following including necessary PCC foundation of minimum 0.20 Mtr height positioned and fixed with suitable nuts, bolts, washers etc to the pedestal and connecting all incoming and outgoing cables all as specified and directed. (a) Aluminium Bus bar four wire system 415 volts mounted on procelain heat shrinkable insulator sleeve suitable for 400 Amps for phases and 200 Amps for neutral. (b) LED type Indicating lamps for all the three phase with different colour lamp red,yellow and green.- 1 set (c) Digital multi function panel meter measuring voltage, Amps and frequency with suitabe CTs and backup protection - 1 No (d) Danger notice board of size 200mm x 150mm x 1.6mm thick of mild steel sheet vitreous enamelled white and letter figur and convention skull and bones of signal red colour and fixed/revited with panel- 02 Nos (e) Incoming (i) MCCB MCCB 3 pole with nuetral link, 35 KA, 200 Amps 415 volts - 01 No (f) Outgoing (i) MCCB MCCB 3 pole with nuetral link, 25 KA, 63 Amps 415 volts - 03 Nos (iii) MCCB MCCB 3 pole with nuetral link, 16 KA, 40 Amps 415 volts - 01 No
Supply, install, testing and commissioning of factory made CPRI approved 415 Volts, 50 Hz, 250 Amps capacity outdoor cubical type LT disribution switch gear and control gear, leg mounted, totally enclosed, cubical type modular compartment , dust and vermin proof IP-54 with neoprene gasket, fabricated out of CRCA sheet of thick ness not less than 3.15 mm complete with 2 mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50mmx50mmx6mm with cable chamber for incoming, outgoing connections comprising for the following including necessary PCC foundation of minimum 0.20 Mtr height positioned and fixed with suitable nuts, bolts, washers etc to the pedestal and connecting all incoming and outgoing cables all as specified and directed. (a) Aluminium Bus bar four wire system 415 volts mounted on procelain heat shrinkable insulator & sleeve suitable for 400 Amps for phases and 200 Amps for neutral. (b) LED type Indicating lamps for all the three phase with different colour lamp red,yellow and green.- 1 set (c) Digital multi function panel meter measuring voltage, Amps and frequency with suitabe CTs and backup protection - 1 No (d) Danger notice board of size 200mm x 150mm x 1.6mm thick of mild steel sheet vitreous enamelled white and letter figur and convention skull and bones of signal red colour and fixed/revited with panel- 02 Nos (e) Incoming (i) MCCB MCCB 3 pole with nuetral link, 35 KA, 250 Amps 415 volts - 01 No (f) Outgoing (i) MCCB MCCB 3 pole with nuetral link, 25 KA, 100 Amps 415 volts - 02 Nos (ii) MCCB MCCB 3 pole with nuetral link, 25 KA, 63 Amps 415 volts - 03 Nos (iii) MCCB MCCB 3 pole with nuetral link, 16 KA, 40 Amps 415 volts - 01 No
Earthing complete with galvanized steel earth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanized earth strip 32 x 6mm from earth plate to body of the equipment by means of nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 connected to earth testing point on completion with and including 15mm bore light grade GI protection pipe (7.5mtr long) for earth including PCC (1:2:4) type B1 chamber pit with cover slab pre cast RCC (1:2:4) type B1, 40mm thick reinforced with 6mm dia MS bars @ 100 c/c bothway, lifting hooks made out of 6mm MS bars, watering arrangement with funnel, wire, common salt, charcoal filling, necessary excavation and earth work in any type of soil complete all as specified and directed
Dismantling of ACSR complete all as specified and directed.
Dismantling of cross Arms of MS channel or angle sections etc complete all as specified and directed.
Dismantling of Insulator any type and size etc complete all as specified and directed.
Saket Enterprises
sree devi construction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .