Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.7 LAccepted-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹37.8 L+₹53,875.67 (1.45%)Rejected-Finance | L2 | Rejected-Finance Other than L1 bidder | |
| 3 | L3₹42.1 L+₹4.8 L (13.0%)Rejected-Finance PRAGARI NAGAR BYE LANE 3 HOUSE NO 05 SATGAON UDAYAN VIHAR GUWAHATI 781171 | KAMRUP METRO | ASSAM | 781171 | L3 | Rejected-Finance Other than L1 bidder |
| Sl No | Description | Qty | Unit | PURBANCHAL BUILDERS L1 | MAC ENGINEERS L3 | VISHWAKARMA ELECTRICAL L2 |
|---|---|---|---|---|---|---|
| 1.00 | Material and labour for dismantling the cable connections of four pole/ three pole air circuit breaker of capacity 630 to 1200 Amps ,415 V 50 HZ of L&T Make/C&S/GE/ABB make, strip opening the air circuit breaker, inspecting the parts for serviceability/overhauling complete and carrying out the following repairs/maintenance :- (a) Cleaning the insulation parts including bushings with CTC solution.(b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual (c) Check the bolts, nuts, washers, cotter pins and all terminal connections are in place and tights. Replace the worn-out parts.(d) Check arc chutes for damage and replace damaged parts.(e) Clean and lubricate the operating mechanism with a light machine oil (SAE-20 or 30) for pins and bearings and with a non-hardening grease for the wearing surfaces . Adjust breaker operating mechanism all as per manufacturer's instructional manual . Replace if there is excessive wear and tear.(f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. (g) Replacing the badly worn or burned contacts. Checking control device free for operation.(j) Check after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functional Note : The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts/bolts/washers/ pins etc. Major spares like contacts, shunt trip coil , relays, CTs etc will be measured & paid separately under relevant schedule items | 2 | Each Job | 2,999 ₹5,998 | 5,000 ₹10,000 | 1,000 ₹2,000 Lowest |
| 2.00 | Supply only cluster contact suitable for air circuit breakers of rating 630 to 1200 Amps rated all as per existing complete all as specified and directed. | 2 | Each | 1,999 ₹3,998 Lowest | 4,500 ₹9,000 | 2,400 ₹4,800 |
| 3.00 | Supply only trip coil / closing coil suitable for air circuit breakers of rating 630 to 1200 Amps rated all as per existing complete all as specified and directed. | 2 | Each | 2,999 ₹5,998 | 2,400 ₹4,800 Lowest | 3,800 ₹7,600 |
| 4.00 | Supply only auxiliary contact block suitable for air circuit breakers of rating 630 to 1200 Amps rated as all per existing complete all as specified and directed. | 2 | Each | 999 ₹1,998 Lowest | 5,500 ₹11,000 | 4,400 ₹8,800 |
| 5.00 | Supply only arc chutes (for 415 V) suitable for air circuit breakers of rating 630 to 1200 Amps rated as all per existing complete all as specified and directed. | 2 | Each | 999 ₹1,998 Lowest | 3,500 ₹7,000 | 3,800 ₹7,600 |
| 6.00 | Supply only rating plug suitable for air circuit breakers of rating 630 to 1200 Amps rated all as per existing complete all as specified and directed. | 2 | Each | 1,999 ₹3,998 Lowest | 2,650 ₹5,300 | 2,100 ₹4,200 |
| 7.00 | Supply only shunt release (110 /220 V DC or 240 V/415 V AC) suitable for air circuit breakers of rating 630 to 1200 Amps rated complete all as specified and directed. | 2 | Each | 2,999 ₹5,998 | 2,500 ₹5,000 | 2,100 ₹4,200 Lowest |
| 8.00 | Supply only arcing contacts (fixed/ moving) suitable for air circuit breakers of rating 630 to 1200 Amps rated as all per existing complete all as specified and directed. | 2 | Each | 1,999 ₹3,998 Lowest | 2,000 ₹4,000 | 2,300 ₹4,600 |
| 9.00 | Material and labour for removing electric / mechanical connections of old LT UG cable from MCCB of existing LT Panel of size from 16 sqmm to 100 Sq mm, 3.5 / 4.0 core including cutting/removing the burnt end/ jointed area and after refixing with new aluminium thimble /lugs set , incl covered with proper insulated tape, clamps, nut bolts etc if required etc complete all as specified and directed. Note : One Panels cable will measured as one Job | 20 | Each Job | 299 ₹5,980 Lowest | 600 ₹12,000 | 800 ₹16,000 |
| 10.00 | Material and labour for removing electric / mechanical connections of old LT UG CABLE from MCCB of existing LT Panel of size from 120 sqmm to 240 Sq mm, 3.5 / 4.0 core including cutting/removing the burnt end/ jointed area and after refixing to MCCB/ACB with new aluminium thimble /lugs set , incl covered with proper insulated tape, clamps, nut bolts etc if required etc complete all as specified and directed. Note : One Panels cable will measured as one Job | 15 | Each Job | 499 ₹7,485 Lowest | 1,000 ₹15,000 | 1,000 ₹15,000 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
30 Jul 2025, 6:00 pmClosed
GE Narangi
GE Narangi C/o 99 APO
CERTAIN REPAIR MAINT DAY TO DAY COMPLAINT OF LT DISTRIBUTION SYSTEM LT PANELS AND ALLIED WORKS UNDER GE NARANGI
2025_MES_718222_1
8095/B/E8
Open Tender
Civil Works
Item Rate
180 days
Guwahati
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE Narangi
₹90,000
Yes
8 Sept 2025
3 Jul 2025
1 Aug 2025
3 Jul 2025
30 Jul 2025
17 Jul 2025
Amount
Material and labour for dismantling the cable connections of four pole/ three pole air circuit breaker of capacity 630 to 1200 Amps ,415 V 50 HZ of L&T Make/C&S/GE/ABB make, strip opening the air circuit breaker, inspecting the parts for serviceability/overhauling complete and carrying out the following repairs/maintenance :- (a) Cleaning the insulation parts including bushings with CTC solution.(b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual (c) Check the bolts, nuts, washers, cotter pins and all terminal connections are in place and tights. Replace the worn-out parts.(d) Check arc chutes for damage and replace damaged parts.(e) Clean and lubricate the operating mechanism with a light machine oil (SAE-20 or 30) for pins and bearings and with a non-hardening grease for the wearing surfaces . Adjust breaker operating mechanism all as per manufacturer's instructional manual . Replace if there is excessive wear and tear.(f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. (g) Replacing the badly worn or burned contacts. Checking control device free for operation.(j) Check after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functional Note : The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts/bolts/washers/ pins etc. Major spares like contacts, shunt trip coil , relays, CTs etc will be measured & paid separately under relevant schedule items
Supply only cluster contact suitable for air circuit breakers of rating 630 to 1200 Amps rated all as per existing complete all as specified and directed.
Supply only trip coil / closing coil suitable for air circuit breakers of rating 630 to 1200 Amps rated all as per existing complete all as specified and directed.
Supply only auxiliary contact block suitable for air circuit breakers of rating 630 to 1200 Amps rated as all per existing complete all as specified and directed.
Supply only arc chutes (for 415 V) suitable for air circuit breakers of rating 630 to 1200 Amps rated as all per existing complete all as specified and directed.
Supply only rating plug suitable for air circuit breakers of rating 630 to 1200 Amps rated all as per existing complete all as specified and directed.
Supply only shunt release (110 /220 V DC or 240 V/415 V AC) suitable for air circuit breakers of rating 630 to 1200 Amps rated complete all as specified and directed.
Supply only arcing contacts (fixed/ moving) suitable for air circuit breakers of rating 630 to 1200 Amps rated as all per existing complete all as specified and directed.
Material and labour for removing electric / mechanical connections of old LT UG cable from MCCB of existing LT Panel of size from 16 sqmm to 100 Sq mm, 3.5 / 4.0 core including cutting/removing the burnt end/ jointed area and after refixing with new aluminium thimble /lugs set , incl covered with proper insulated tape, clamps, nut bolts etc if required etc complete all as specified and directed. Note : One Panels cable will measured as one Job
Material and labour for removing electric / mechanical connections of old LT UG CABLE from MCCB of existing LT Panel of size from 120 sqmm to 240 Sq mm, 3.5 / 4.0 core including cutting/removing the burnt end/ jointed area and after refixing to MCCB/ACB with new aluminium thimble /lugs set , incl covered with proper insulated tape, clamps, nut bolts etc if required etc complete all as specified and directed. Note : One Panels cable will measured as one Job
Material and labour for taking out the loose or separated Door / canopy / front & back sheet covers for existing the LT panel and refixing the same after welding, provn of nut bolts / hinges if required as per site, proper locking arrangement and fixing of proper earth connection etc complete all as specefied and directed.
Material and labour for replacement of out door panel board canopy door, made CRCA sheet with 3.15 mm thick, duly power coated with removable door hinges, water proof rubber beading and , locking arrangement with SS aldrop & pad lock/ concealed locking arrangement, Danger notice boards, Panel details including gas welding for fixing the door complete all as specified and directed
Material and labour for replacement of out door/in door panel board, made CRCA sheet with 2 mm thick, duly notched/punched cavity for operation of switch gear and duly power coated with removable door hinges, water proof rubber beading and , locking arrangement, Danger notice boards, switch gear details including gas cutting and welding for fixing the door complete all as specified and directed
Supply and fix danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20 cm size complete all as specified and directed
Repairs/Maint of LT Panel board/box of various sizes including disconnecting all incoming and outgoing connection after taking necessary shut down, cleaning the carbon/rust from bus-bar, re-thimbling with new lugs/thimble of existing size,replacing burnt DMC insulator or bus bar supports as per exsiting one, removing old burn out wiring and re-wiring with new cable of exsiting size, including replacement of un-serviceable parts complete all as specified & directed. Note :- (i)New spares required shall be measured and paid separately under relevants items . (ii) cost of unsheathed multistranded copper conductor of size upto 2.5sqmm for internal wiring like connection of CTs and DMC insulators are deemed to be included in quoted rate. (iii) For item No. 16 to 22 fixing charge of items are considered in item no. 6. (v)Suitable size of copper/AL cable lugs to be provided by contractor for for fixing /jointing the cable in bus bar etc.
Supply only 3 phase single function LED Voltmeter flush mounting 96X96mm of input voltage measurement range 50-520 VAC(P-P) , 5A,accuracy class 1 for LT panel board, complete all as specified and directed.
Supply only 3 phase VAF+ PF digital meter flush mounting 96X96mm of input voltage measurement range 50-520 VAC(P-P) , 5A,accuracy class1 for LT panel board, complete all as specified and directed
Supply only Indoor tape insulated ring type low tension current transformers of ratio 100-500/5A accuracy class 1.0 for LT panel board, complete all as specified and directed
Supply only LED Indicator lamps to be mounted on LT panel for R,Y,B phase (of colour Red,green,yellow) operates on 240V AC for fixing in the existing place in LT panel board, complete all as specified and directed
Supply only FR-LSH PVC insulated single core unsheathed multistrand copper conductor for voltage grade 1100 V of size 25 Sqmm single core complete all as specified and as directed.
Supply only FR-LSH PVC insulated single core unsheathed multistrand copper conductor for voltage grade 1100 V of size 50 Sqmm single core complete all as specified and as directed.
Material and labour for cement concrete 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) as in foundation complete all as specified and directed
Material and labour for PCC 1: 3 : 6 type C-1 (using 20 mm graded mechanically crushed stone aggregate) as in mass concrete including necessary form work for coping to the new/existing steel poles complete all as specified and directed.
Dismantling unserviceable steel poles of any size including demolition of foundation concrete and removing from site complete all as specified and directed.
Material and labour for erection of steel tubular steel tubular swaged pole type 410 SP - 31 (9.00 metres long) including cast iron base plate, finial taper plug and and painted with two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
Supply and fix MCCB with Thermal - magnetic release of 80-100 Amps, 4 Pole, 415V, 25 kA, Ics=100%Icu including all accessories and taking down old unserviceable one complete all as specified and directed
Supply and fix MCCB with Thermal - magnetic release of 160-250 Amps, 4 Pole, 415V, 36 kA, Ics=100%Icu including all accessories and taking down old unserviceable one complete all as specified and directed
Supply and fix MCCB with Thermal - magnetic release of 268-400 Amps, 4 Pole, 415V, 36 kA, Ics=100%Icu with adjustable over load setting and adjustable short circuit setting including all accessories and taking down old unserviceable one complete all as specified and directed.
Material and labour for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 6-16 Sqmm 4 core complete all as specified and directed.
Material and labour for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 25-50 Sqmm 3.5 core complete all as specified and directed.
Material and labour for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 70-120 Sqmm 3.5 core complete all as specified and directed.
Material and labour for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 150-185 Sqmm 3.5 core complete all as specified and directed.
Material and labour for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 240-300 Sqmm 3.5 core complete all as specified and directed.
Taking out old unserviceable UG cable of any size/ type from trenches / wall / roof etc. for necessary repair/ replacement / re-laying works complete all as specified and as directed. ( Note : Excavation and earth work shall be measured and paid seperately).
Material and labour for relaying of faulty UG XLPE cable of size 3.5 core , 120 to 240 sqmm alongwith brick protection, sand cushioning etc as obtained from taking up/down old cable here in before in trenches/ wall/ roof etc. including cutting and jointing through cable jointing kit as required and connecting to the main switches/cut outs MCB/MCCB with necessary lugs after cutting to required length complete all as specified and as directed.
Material and labour for relaying of faulty UG XLPE cable of size 4 core ,16 to 95 sqmm alongwith brick protection, sand cushioning etc as obtained from taking up/down old cable here in before in trenches/ wall/ roof etc. including cutting and jointing through cable jointing kit as required and connecting to the main switches/cut outs MCB/MCCB with necessary lugs after cutting to required length complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 10 sqmm 2 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 10 sqmm 4 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 16 sqmm 4 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 25 sqmm 4 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 50 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 70 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 95 sqmm 4 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 120 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 150 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Material and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 185 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, complete all as specified and as directed.
Excavation in trenches not exc 1.50 m wide and not exc 1.50 m deep for foundation or for shafts, wells cesspits,man holes etc not exc 10 Sqm on plan and n exc 1.5m in depth and getting out in soft / loose soil complete all as specified and as directed.
Excavation in trenches n.exc 1.5m wide and depth exceeding 1.5 m and not exceeding 3.00m beyond first 1.50m and getting out in soft / loose soil etc complete all as specified and as directed.
Returning filling in including spreading, levelling, watering and well ramming in layers n.exc. 25cm thick complete all as specified and directed.
Removing excavated soil to distance not exc. 50 m and depositing where directed at a level not exc. 1.5 m above the starting point etc complete all as specified and as directed.
Supply and spreading clean dry river sand in cable trenches as in cable cushioning complete all as specified and as directed. (Note: Punned thickness shall be measured and paid)
Material and labour for Sub class ‘B’ old size well burnt brick laid flat in trenches over the cable for protection of LT cable complete all as specified and as directed.
Refixing only serviceable GI pipe light grade 40mm bore as obtained from taking up/down cablewith provision of new fittings as in protection of cable at road crossing/hard standing/pole protection fixed with clamps, including taking up/ down old pipe complete all as speciffied and as directed
Refixing only serviceable GI pipe light grade 50mm bore as obtained from taking up/down cablewith provision of new fittings as in protection of cable at road crossing/hard standing/pole protection fixed with clamps, including taking up/ down old pipe complete all as speciffied and as directed
Material and labour for complete removal of old paint by scrapping and removing for preparing surfaces of existing old steel tubular poles 8.5m/9.00m long including scrapping, brushing down old paint with emery paper and applying one coat of aluminium paint including cross arms, street light brackets etc and making strip upto 1.5m above ground level by black/yellow paint in alternate layers with numbering of poles complete all as specified and directed.
Material and labour for GI pipe light grade 40mm bore dia with all fittings to be laid in trenches or in floors,including taking down rusted one complete all as speciffied and as directed.
Material and labour for GI pipe light grade 50mm bore dia with all fittings to be laid in trenches or in floors,including taking down rusted one complete all as speciffied and as directed.
Material and labour for Manual boring under roads/hard standing by reqd T&P without disturbing the top surface of the road for throughing the cable in GI Pipe of n exc 80 mm dia all as specified and directed.
Dismantling unserviceable steel poles of any size including demolition of foundation concrete and removing from site complete all as specified and directed.
Material and labour for erection of steel tubular steel tubular swaged pole type 410 SP - 31 (9.00 metres long) including cast iron base plate, finial taper plug and and painted with two coat of synthetic enamel paint over a coat of red oxide primer all as specified and as directed.
Material and labour for cement concrete 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) as in foundation complete all as specified and directed by Engineer- in-charge.
Material and labour for PCC 1: 3 : 6 type C-1 (using 20 mm graded mechanically crushed stone aggregate) as in mass concrete including necessary form work for coping to the new/existing steel poles complete all as specified and directed.
Supply and fix SS enclosure for MCCB of rating 250Amp In-built neutral Link for TPN system l IK08 and IP30 Protection having Louvers for better heat dissipation Suitable to accommodate upto 185 sq. mm. 3 1/2 core Aluminum armoured cable incl taking down unsv one and refixing serviceable/ new MCCB in enclosure and connectiing existing IC/OG cable with proper dimension lugs all as specified and directed complete all as specified and directed.
Supply and fix street light junction box of made of high quality polycarbonate with IP-66 protection (Dust and vermin proof according to IEC-60529) Totally insulated made of halogen and silica free recyclable material having high quality gasket made out of polyurethane Din rail , with locking arrangement with cable gland suitable upto 10 sqmm cable and necessary fixing arrangements such as clamps, nuts, bolts etc complete all as specified and directed.
Material and labour for connection of junction box to street light luminaire using wiring with two runs (P-N) of single core 1.5 Sqmm (nominal area) (FR-LSH) PVC insulated and unsheathed multi-stranded copper conductor cable 1100 volts grade and one run of ( FR -LSH) PVC insulated and unsheathed multi-stranded copper conductor of size 1.5sqmm single core as earth continuity wire drawn through PVC conduit(Heavy grade) and tiding the same by aluminium strip with the pole complete all as specified and directed. (Two single core 1.5 Sqmm cable and one single core 1.5 Sqmm earth conductor cable and one run of PVC conduit shall be measured as one run).
Supply and fixing in repairs street light bracket made of GI pipe 40 mm bore light grade(bend to shape) , 2 metre long and fixed with Ms flat iron clamp(clamp shall be 40 X 5mm ), nuts, bolts and washers on pole complete all as specified and directed.
Dismantling unserviceable cross arms, clamps etc complete all as specified and directed.
Material and labour for cross arms, bracings, supports, clamps, eye hook and back plates fabricated from structural steel sections including pole clamps, stay clamps, D clamps nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including painting with two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
Refixing only serviceable cross arms, bracings, supports, clamps, eye hook and back plates as obtained from dismantling of old cross arms including provision of new bolts, nuts etc . in any shape or size as indicated or directed including painting with one coat of aluminium paint complete all as specified and as directed.
Material and labour for prunning / trimming the branches of trees if any along overhead line, 3 m on all side below/ above/ sides of overhead line and removing the same upto 150 m away each span not exceeding 45 m complete all as specified and as directed.
Material and labour cutting grasses, shrubs/herbs surrounding LT poles, feeder pillar box installations by mechanical or manual T&P, removing the debris at a distance not exceeding 50m and depositing where directed complete all as specified and as directed.
Dismantling of old insulator any type and description from existing poles complete all as specified and as directed.
Material and labour for pin type insulators LT 1100 Volts grade porcelain vitreous white or brown including one galvanized mild steel spindle, two galvanized iron washers, iron nut, 100 mm height, 65 mm dia complete all as specified and as directed.
Refixing only serviceable pin type insulators as obtained from dismantling of old insulator including provision of one galvanized mild steel spindle, two galvanized iron washers, iron nut, etc complete all as specified and as directed.
Material and labour for shackle type insulator LT 1100 volt grade porcelain vitreous white or brown including galvanised mild steel straps, washers, insulator bolts, nuts 12 mm dia, 75 mm height and 90 mm dia, section of straps 31mmx3mm of insulator complete all as specified and as directed.
Refixing only serviceable shackle type insulators as obtained from dismantling of old insulator including provision of new bolts, nuts, washers , etc complete all as specified and as directed.
Dismantling of old earth wire, craddle guard etc of any description and size complete all as specified and as directed.
Material and labour for galvanised steel wire 3.15mm or 4.00mm dia as earth continuity conductor and fixed to pole, binding with aluminium binding wires complete all as specified and as directed.
Material and labour for Stringing / stretching, including jointing in situ of each span not more than 45 m between two electric poles having 4 Nos of ACSR of any size including GI earth continuity wire, with/ without guarding wires on electric poles of any size at different locations all as ordered to the extent of permissible sag or tension by removing jumpers or bindings from insulators and making fresh binding with aluminium tapes after stringing complete as ordered . (Note :- One span including 4 wire of LT over head line and 2 Nos of earth wire.)
All as per item No 80 here in before but for 2 Nos of ACSR.
Supply and fix PVC/Fibre seperator for LT lines 1100 volts overhead conductors 2 wire system for horizontal spacing between the conductors fixed with nuts, bolts, washer etc. complete all as specified and as directed.
Supply and fix PVC/Fibre seperator for LT lines 1100 volts overhead conductors 4 wire system for horizontal spacing between the conductors fixed with nuts, bolts, washer etc. complete all as specified and as directed.
Dismantling unserviceable/old ACSR conductors of any size from over head lines, poles by removing binding wire, service wire, cables and removal from site complete all as specified and directed.
Material and labour for aluminium conductor, steel reinforced (ACSR) of any size as approved on HT/LT Poles including straining, binding to insulators with aluminium binding wire with connectors, etc, providing PVC sleeves for jumpers as in OH conductors including dismantling of old ACSR or AAD conductors complete all as specified and as directed.
Material and labour for Refixing only of aluminium conductor, steel reinforced (ACSR) of any size as approved on HT/LT Poles including straining, binding to insulators with aluminium binding wire with connectors, etc, including dismantling of old ACSR or AAD conductors complete all as specified and as directed.
Material and labour for complete removal of existing treatment of LT Panel, box, board, cross arms etc and applying two coats synthetic enamel paint over a coat of red oxide primer, complete all as specified and as directed.
Dismantling unserviceable stay assembly complete including demolition of foundation concrete & removing from site complete all as specified and directed.
Material and labour for stay assembly comprising 14mm dia iron stay bow, stay strand wire of size 7/3.15mm with stay rod of diameter 16mm complete with all accessories as shown in electrical plate no. 1 of SSR part-I 2009 including dismsntling of old stay assembly of any description with foundation, etc. complete all as specified and as directed.
Material and labour for loop type insulator, vitreous porcelain, white, brown or green with overall dimension 95mmX65mm, clearence of hole 16mm suitable for 1100 Volts complete all as specified and as directed.
VISHWAKARMA ELECTRICAL (BID ID -3373279)
MAC ENGINEERS (BID ID -3376447)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .