Kenduadihi, Gobindanagar Hospital campus, Bankura-722102
Repair and Renovation of Day Care Unit of Radiotherapy Building, BSMCH, Bankura
2025_WBPWD_899535_1
WBPWDTE/AE/BMCESD/NIQ-18/Q of 2025-2026
Open Tender
ELECTRICAL WORKS ORG
Item Wise
14 days
AE//BMCESD/BANKURA
Please refer Tender documents.
3 documents required · 3 mandatory
₹4,899
Yes
31 Oct 2025
9 Sept 2025
19 Sept 2025
9 Sept 2025
17 Sept 2025
9 Sept 2025
Amount
Dismentling the existing damage, defective & non functioning Electrical accessories by Co's own tools & tackles by maintening normalcy as far as possible as per direction of EIC. and the agency have to submit the dismantled Electrical Installations at the BSMC&H Electrical sub division by their own arrangements with full list of items.
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as to GS. ( Legrand /Siemens / Schneider) ) 8 way Enclosure
Supplying and fixing 240/415 V Isolator on din rail of existing DBs and necessary connection Make-Legrand / Siemens, as to GS. 415 V, 63A FP
Supplying and fixing 240/415V, MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection Make-Legrand/ Siemens as to GS. 6A - 32A SP MCB
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FRLS' PVC insulated & unsheathed copper wire (Finolex/ Havells/KEI approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FRLS' PVC insulated & unsheathed copper wire for ECC, with drop Concealed type if reqd as per direction of EIC to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175 mm x 100 mm x 65 mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish. Average run 10 mtr
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FRLS' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FRLS' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box andmending good the damages to original finish. On Board
Supply & Fixing 240 V, 2 x 6A, plug socket with separate 2 x 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240 x 200 x 65 mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.
Supply & Fixing 240 V, 1 x 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F150 x 100 x 65mm MS (16SWG) switch board and bakelite /perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.
Distribution wiring in 1.1 KV single core stranded 'FRLS' PVC insulated & unsheathed copper wire (Finolex / Havells/ Gloster / R R kable /approved by EIC) in 25mm/32mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. 2 x 1.5 sqmm + 1 x 1.5sqmm (for Separate plug & pole lighting)
2 x 2.5 sqmm + 1 x 1.5sqmm (for Power plug )
2 x 6 sqmm + 1 x 2.5 sqmm ( for AC machine )
4 x 16 sqmm + 2 x 10 sqmm (from Panel to TPN MCB DBs)
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. as per G S. 1.5 sq mm
Supply & delivary of AC 240V 50 Hz 48" sweep (1200 mm) ceiling fan complete with down rod , Canopy, fork incl S & F of P - 2 type capacitor as per IS specification & proper Manufacturer certificate of the capacitor (supplied at the time of delivered the fans ) etc. with out regulator, (Make- USHA 1200mm Stiker PWD ISI 1st (Safty wire 53 capacitor)/ Orient Electric New brezze 320 RPM 44 watt, 3 star 5 year warretny) or equivant makr of Cromp ton Greaves as per direction of EIC
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire as per direction of EIC as per direction of EIC.
Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991)
Supply & Fixing Socket type fan regulator (Step type) (Anchor) on existing sheet metal switch board with bakelite/ perspex top cover by after making housing for regulator by cutting bakelite top cover incl. making necy. connections etc. as per G.S.
The additional Safety arragement of celling fans by stranded GI / MS strain wire of suitable gauge with special type socket / thimble / nut bolts which is througly crimped with the strain wire and the wire passing through down rod , also the other end connected with armature spindle by its existing jum nut hole with same specical arrangement as per direction of EIC.
Supplying & Fixing angular holder (Anchor) on 3" wooden double round block incl. S&F 9 Watt LED lamp (Make Philips / Wipro / Bajaj / Crompton/ Havells / PWD Approved ) as per direction of EIC
Supply & Delivery of 4 feet single commercial LED type fluorescent light fittings complete with all accessories similar to Philips make cat No. TMC 502 P1 x T - LED 22 W with Master LED Tube lamp of 1200 mm , 18W 865 T 81- 2100 ln corresponding to Wipro / Bajaj / Crompton/ Havells / PWD approved as per direction of EIC OR Crompton single of ctings IGP 162 L & T 161 x T8 with 1 nos LED tube of Crompton LTB -20- 865- (2)
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. as per G.S.
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections.
Supply & Fixing of 250V 50 HZ OLP- 30A single phase A.C Starter ( Make -Electron, / PWD Appvd ) suitable for 1.5 / 2.0 TR Airconditioner Machine incl S & F suitable size G I box (16 SWG) flushed in wall with voltage check, Amp check, Time check incl. making connection as per direction of EIC.
Supplying and fixing of 250 V AC timers fixed on wall with flat iron frame as per direction of EIC and the Box shuld be comprising with the following accessorise --- i) Double-door SPN MCB Distribution Board with IP-42/43 protection 2+10/12 way Enclosureas reqd . ( Make - Legrand / L & T ) – 1 no ii) 230 V , 50 Hz ,16 Amp Single dial 1 x 24 Hrs.Timer ( Microrex QT31 ) of quartz driven running reserve Day dial back up by nickle cadmium battery (Make - LK (L & T) AOSTO3ANA 00 ( Seiemens /Schnider ) – 1 no iii) 250 V, 50 Hz , 40 Amp DP Conctractor with ( 2 NO or 1 NO + 1 NC Aux. Contract ) ( Make - Legrand / L & T ) – 1 no iv) 250 V, 50 HZ , 32 Amp , DP MCB Isolator ( Make - Legrand / L & T ) – 1 no v) Auto / Manual By pass Toggle Switch arrangement – 1 no. vi) 250 V , Diode type neon Indicator lamp ( Make - Legrand / L & T ) – 1 no vii) Bakelite base with FP bolt type stud / Terminal block incl S & F Neutral Bar etc with this box for termination of power . viii) The complete arrangement must be wiring by 2.5 Sq mm PVC insulated Cu wire with suitable length incl socketing /lugs etc as per requirement & direction of EIC (Make - Legrand /L & T / Crabtree )
UJJWAL MUKHERJEE (BID ID -6925017)
MANDAL TRADERS (BID ID -6924991)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .