Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39,000Accepted-AOC | ₹39,000 Quoted ₹19.1 L | L1 | Accepted-AOC work done |
| 2 | L2₹19.4 LRejected-Finance 2 284 JANKIPURAM VISTAR LUCKNOW UTTAR PRADESH 226021 UDYAM UP 50 0011144 | LUCKNOW | UTTAR PRADESH | 226021 | ₹19.4 L | L2 | Rejected-Finance Second Lowest |
| Sl No | Description | Qty | Unit | Sarveshwari Electric Works L1 | Actech Engineers L2 |
|---|---|---|---|---|---|
| 1.00 | Providing and fixing of 750 KVA free standing floor mounting outdoor type, cooper bounded servo controlled voltage stabiliser (SCVS) naturally oil cooled, (including first filling of oil) suitable for voltage range of input phase voltage (184-276 volt i.e. 230 volt with 20% fluctuations) the output phase voltage should be maintained at 230 volt 1%, with a speed of correction not less than 7-8V/sec. phase to neutral voltage. The SCVS shall have an output voltage setting of 400 volts to 440 volts and shall be supplied with Digital voltmeter & Ammeter with selector switch to read input/output voltages & Currents, Auto/manual control selector switch, sensitivity control LED indication lamps within fuses & controls, and protection against OVER/UNDER voltages, OVERLOAD, Single phasing & protection for sensing elements. SCVS shall have all accessories like cable end boxes, earthing terminals oil gauge silica gel breather, earthing terminal and complete as required. The SCVS shall conform to IS 9815 (with latest amendments) The AVR shall be suitable for unbalanced loads and unbalanced input voltage with individual correction in all three phases. The AVR shall be provided with the following protection like Overload, Short Circuit, Earth fault, Over voltage, Under voltage, Single Phase Prevention, High Temperature Spike and surge
CONTROL AND INDICATION
The following alarm and annunciation shall be provided Alarm
1 Low / High Voltage (out of input range)
2 Single Phase Prevention Alarm
3 High Temperature Alarm Indication LED Indications for Input Voltage ‘High’ /’ Low’
DEGREE OF PROTECTION The degree of protection for the enclosure shall be IP55 as it is an outdoor installation.
COOLING METHOD Cooling method shall be Natural / Oil cooled
TESTS
All routine tests as per standards shall be conducted, for proper functioning of the equipment in presence of Departmental representative | 1 | Job | 19,10,000 ₹19.1 L | 19,40,000 ₹19.4 L |
Tender Value
₹19.5 L
EMD Value
₹39,000
Closing Date
3 Feb 2024, 5:00 pmClosed
EXECUTIVE ENGINEER MLCD JAUNPUR
EXECUTIVE ENGINEER MLCD JAUNPUR
Manufacture and supply of 750 KVA Automatic Voltage Regulator supply constant voltage to panel board at Khurahat Pump Canal of Minor Lift Canal Division Jaunpur
2024_UPIDM_886132_1
07/E.E./2023-24(LOT-05)
Open Tender
Electrical Works
30 days
EXECUTIVE ENGINEER MLCD JAUNPUR
Please refer Tender documents.
2 documents required · 2 mandatory
₹854
₹39,000
Yes
22 Jan 2026
27 Jan 2024
5 Feb 2024
27 Jan 2024
3 Feb 2024
27 Jan 2024
Amount
Actech Engineers
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid