Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.5 LAccepted-AOC | L1 | Accepted-AOC SINCE L1 | |
| 2 | L2₹25.4 L+₹4.4 L (20.9%)Rejected-Finance PLOT NO 106 MIDC SATPUR SATPUR MIDC AREA SATPUR NASHIK MAHARASHTRA 422007 UDYAM MH 23 0018515 | NASHIK | MAHARASHTRA | 422007 | L2 | Rejected-Finance SINCE NOT L1 | |
| 3 | L3₹26.6 L+₹5.6 L (26.7%)Rejected-Finance | L3 | Rejected-Finance SINCE NOT L1 |
Tender Value
₹29.9 L
EMD Value
₹59,800
Closing Date
19 Aug 2021, 6:00 pmClosed
GE DEOLALI
GE DEOLALI, 422401
REPAIR/ REPLACEMENT/IMPROVEMENT TO EARTHING AND LIGHTENING CONDUCTORS AND ASSOCIATED WORKS UNDER THE AOR OF GE DEOLALI
2021_MES_462436_1
8996/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE DEOLALI
CLASS D CAT b i
8 documents required · 8 mandatory
₹500
Yes
GE DEOLALI
₹59,800
Yes
27 Oct 2021
24 Jul 2021
21 Aug 2021
24 Jul 2021
19 Aug 2021
7 Aug 2021
Amount
Excavating in trenches in soft/ loose soil n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. nexc 10 sq m on plan and n exc 1.5 m in depth and getting out
Returning, filling in, approved earth including spreading, levelling, watering and well ramming in layers n.exc 250mm thick after cable are laid and tested complete all as specified and directed.
Removing excavated material (Surplus soil) to a distance not exc 50m and depositing where directed at level not exc. 1.5m above the starting point all as specified and directed.
M&L for sand cushioning to under ground cable providing with a layer of and 05 cm thick before laying of cable and 18 cm after laying of cable in trenches complete all as specified and directed by Engr-in-charge (Note :- Thickness of sand after punning down shall be measured and paid separately)
S & L sub class B bricks having minimum compressive strength 75 Kg/Sqcm laid in trenches for cable protection etc complete all as directed by Engineer -in-Charge.
Cutting through existing bituminous road /PCC/floor/approx size width 50cm X 60cm depth along cross section of the road for laying of GI tubing/RCC pipe for encasing of cable and repairing the road to match with the original finish, M&L complete complete all as specified and directed.
M & L for cement concrete 1 :3 :6 type C-1 using 20 mm graded stone aggregate incl necessary form work all as specified
M&L for Supply, laying & testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sqmm 3.5 Core
All as item No- 8 above but of cross sectional area 35 Sqmm 3.5 Core
All as item No- 8 above but of cross sectional area 25 Sqmm 4.0 Core
All as item No- 8 above but of cross sectional area 16 sq mm 4 core
All as item No- 8 above but of cross sectional area 10 Sqmm 4 core
All as item No- 8 above but of cross sectional area 16 sqmm 2 core
S&F Tubes, 'light grade' 50mm bore galvanised,with all fitting and fixed complete to walls and ceilings or laid in floors
All as item No 14 above but 40 mm dia
M&L for earthing complete with galvanized steel plate electrode 600 mm x 600 mm x 6.3 mm thick, burried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 32 x 6 mm size by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both way for cover and MS frame etc., complete complete all as specified and directed.(set of two) NOTE: The unit rate includes earth strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point.
M & L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground all as specified and directed (earth pit not less than 2.25m below normal ground level) with top edge of the plate not less than 1.5m below normal ground level connected to GI wire 4mm dia by means of bolts, nuts, check nuts & washers of galvanized iron all as shown in Electrical Plate No. 3 connected to earth test point all as specified or indicated and testing on completion including necessary excavation and earth work in any type of strata, PCC pit and RCC cover, GI protection pipe 15mm bore light grade , watering pipe, wire mesh etc. all as specified and directed by Engineer-in-Charge.
All as item No 17 above but using copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead
M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire
Supply and fix aluminium strip 25 x 3.15mm with saddles and fixing screws, insulators rawal plugs etc for conductor for roof and fixed on wall upto test point complete all as specified and directed.
Supply and fix galvanized iron strip 32 x 6mm fixed with saddles & fixing screws, PVC dash fastners, insulators fixed from test point to earth on walls or burried in ground / drawn into hume pipe.
Supply and fix single pointed air termination Aluminium rod 12mm dia, 300 mm long
M&L for test point terminal block made of gun metal or phosphorous bronge 75 x 75 x 25mm of 6mm thickness drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head brass screws including box of size 90 x 90 x 90mm made of 1.6mm plain sheet and screwed to wall for protection of test point completed complete all as specified and directed.
Taking down carefully by unscrewing from clamp/ saddles plates air termination rods with GI supporting pipe for re use at site or carrying the MES store complete all as spesified and directed by Engr- in -Charge
Refixing Air termination rod with G I supporting pipe retrieved against item no-1 complete all as specified and directed by Engr-in-Charge
Taking down carefully by unscrewing from clamp /back plates strips any type of aluminium/ GI for reuse at site or refifing at same or other locations complete all as spesified and directed by Engr- in -Charge
Refixing Gi/ aluminium strips retrieved against item no-36 complete all as specified and directed by Engr-in-Charge
M&L for replacement of Electronic dirver suitable for LED street light 120 Make : Havells/ Philips/Bajaj
M&L for replacement of Electronic dirver suitable for LED street light 80/90 Watt Make : Havells/Philips/Bajaj
M&L for replacement of Electronic dirver suitable for LED street light 60/72 Watt Make : Havells /Philips/Bajaj
M&L for replacement of Electronic dirver suitable for LED street light 45/48 Watt Make : Havells /Philips/Bajaj
M&L for replacement of Electronic dirver suitable for LED street light 20/30 Watt Make : Havells /Philips/Bajaj
S&F PVC flat twin core unarmoured Aluminium cable of size 10 Sqmm complete all as specified and directed.
S&F PVC flat twin core unarmoured Aluminium cable of size 6.0 Sqmm complete all as specified and directed.
S&F PVC flat twin core unarmoured Aluminium cable of size 4.0 Sqmm complete all as specified and directed.
M & L for bracket made out of GI tubing 40 mm dia,light grade 1.5 mtr long including fixing with MS clamps -2 Nos made out of 40 mm wide 4 mm thick flat iron with M.S nuts bolts 75 mm long 12 mm dia -4 Nos with flat washer (3mm thick) -02 No for each including painting with aluminium paint over one coat of red oxide to the M.S clamps & bracket etc complete all as directed at site.
Supply & fix Thermo plastic street light sintex box of size 280 X 170 X 130 mm Cat No GS-JB-2817 top Hinged ( or equivalent make of National) wiith 4 way connector mounted on epoxy insulators for looping of cable for 3 Phase and 1 neutral fixed on pole with the help of MS nuts bolts and MS clamps-1 Nos of size 40 mm X 4 mm thick with one No MCB SP 6 Amp capacity mounted on din rail inside box.
M & L for breaking the plinth of street light pole, taking out loop of existing UG cable of any size, cutting the damaged portion of cable and reconnecting it to the New/ existing street light junction box with and including proper aluminium lugs clearing the site complete all as specified and as directed at site.
All as item No 30 above but with following accessories:- a) Aluminium bus bar of capacity 200 Amps for Phase-R-Y-B & 100 Amps for neutral -1 No b) MCCB 4 Pole 536 KA , 160 Amp - 1 No (I/C) c) MCB TPN 63 Amp ,10 KA - 4 Nos d) MCB SPN 40 Amps-02
M&L for out door type bus bar chamber fabricated by MS sheet of size 3mm and mounted on MS angle iron frame suitable for 415 Volt 3 phase 4 wire AC supply comprising of Aluminium bus bar of capacity 200Amps installed on epoxy insulators consisting of MCB TPN 63 Amps-01 No & MCB SPN-32 Amps-06 Nos. the bus bar chamber should be dust proof, vermi proof and made out of 3 mm CRCA sheet and mounted on 40x40x6mm angle iron,.door is front opening with locking arrange ment. duly powder coated.
Disconnecting electrically , taking out from trenches and relaying after rectifying defects LT cables any size from 6 Sqmm to 185 Sqmm 2 / 3.5 core. Relaying only or fixing or passing through pipe 1100 volt grade heavy duty cable with PVC insulated multi stranded Al conductor of size of 6 Sqmm to 185 Sqmm/2/3.5 core armoured with galganised steel strip or wire all specified and direct by Engr-in-Charge. NOte:- excavation and Earth work and othe material reqd will be measured and paid separetaly under the respective item of schedule
Re use old sub class "B" bricks covering protection to the electic cable laid dry flat transversly along the length of cable on sand cushioning with width equal to length of brick comlete all as specified and directed as required.
M & L for scrubbing out old paint,rust etc from 9 Mtr long pole and making smooth and even suface then painting with one coat of anti rust paint and two coats of superior quality aluminium paint on entire exposed portion of pole structure including all fitments on pole and writing pole number with 2'' size with white paint lettering on black base all as directed at site .(work shall be completed in the stipulated period as directed).
Dismantling carefully the existing OH line of worn out/ defective ACSR conductor of any size from its position by necessary disconnecting of conductor.
Dismantling of cross arms of MS fabricated complete with all accessories viz nut, bolts, washer etc. complete all as specified and directed.
S&F Automatic street light switch using NATURE SWITCH for automatic switching of street Lights based on LUX level of Natural Light. The sensor (Nature Switch) along with suitable Power Contactor, MCB and Support Terminals should be enclosed in pole/ wall mountable enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade special moulding compound (Sintex make SMC Junction box) conforming to IP54 degree of ingress. The contactor, MCB and Circuit wiring should suitable enough to take load of 18 KW equally distributed over 3 Phase (4KW /Phase). Model No- Swadeep-02-EC, Contactor Rating : 40 Amps (AC3), MCB (single-pole) Rating :32 Amps 3 Nos. Make : Nature Switch : Kakatiya Energy Systems Pvt Ltd Hyderabad or Equivalent of Bajaj /L&T/Legrand
Supplying, fixing, jointing and testing heat shrinkable Straight through joint, with including jointing materials suitable for 1100 V , XLPE LT cable of size 25-50 sqmm , 3.5 core , Incl excavation upto 7 mtrs and returning fillin in after jointing of cable complete all as specified and directed
Supplying, fixing, jointing and testing heat shrinkable Straight through joint, with including jointing materials suitable for 1100 V , XLPE LT cable of size 70-120 sqmm , 3.5 core , Incl excavation upto 7 mtrs and returning fillin in after jointing of cable complete all as specified and directed
Supplying, fixing, jointing and testing heat shrinkable Straight through joint with including jointing materials suitable for 1100 V, XLPE LT cable of size 150-185 sqmm , 3.5 core , complete all as specified and directed
Note: Amount of sch of credit of Rs.46,770.00/-will be deducted from total amount of BOQ.
KOYNA ENGINEERS PVT LTD
M/S S T KUNDARIYA
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .