Ventilation System Works in Basement Yogshala/Multipurpose Hall at CRSU, Jind, Haryana
NBCC/RBG/CRSU/HVAC/2023/52
NBCC/RBG/CRSU/HVAC/2023/52
Open Tender-Domestic
Miscellaneous Services
Jind, Haryana
₹11,800
₹48,678
1 Aug 2026
29 Dec 2023
12 Jan 2024
12 Jan 2024
19 Jan 2024
COST SUMMARY FOR VENTILATION SYSTEM WORKS IN BASEMENT YOGSHALA/MULTIPURPOSE HALL at CRSU, JIND
Digitally signed by RAHUL
DETAILED ESTIMATE FOR VENTILATION SYSTEM WORKS IN BASEMENT YOGSHALA/MULTIPURPOSE HALL at CRSU, JIND
SUB-HEAD 'A' - EQUIPMENT (NSR)
Supply, installation, testing and commissioning of Ceiling hang Vane axial flow type exhaust air fan for
basement ventilation with CO2 Sensor of following capacity with powder coated GSS casing and aluminium
alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction
motor (EFF- 2) and 'H' class insulation suitable for 3 Phase, 50 Hz, 415±10% Volt, ac supply, suitable
capacity of TP isolator with M.S enclosure box complete as required and as per specifications. Fans should be
AMCA certified for air & sound performance & should be statically & dynamically balanced upto G 2.5 as per
ISO 1940 & AMCA 204/3 standard.The sound pressure should not exceed 80 db(A) at a distance of 3 Mts.
Fan and Motor for Fire exhaust fans shall be suitable for operation at minimum 250 deg C for 2 hrs. (as per
EN12101-3: 2002 CE certified). complete in all respect.
TOTALSUB-HEAD 'A' - EQUIPMENT (NSR) 17,62,494.00
SUB-HEAD 'B' - AIR DISTRIBUTION
Supply, installation, and commissioning of factory/site fabricated GSS sheet metal rectangular/round
2 ducting complete with neoprene rubber gaskets, elbows, hangers, supports etc. as per approved drawings and
specifications of following sheet thickness complete as required.
TOTALSUB-HEAD 'B' - AIR DISTRIBUTION (HSR) 19,16,687.00
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene
rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
Supplying & fixing of powder coated extruded aluminium
4 NSR-3 Supply Air Grills with aluminium volume control dampers as per specifications. . Sqm 18 9,105.00 1,63,890.00
Supplying & fixing of powder coated extruded aluminium
5 NSR-4 Return Air Grills with louvers but without volume control Sqm 36 5,910.00 2,12,760.00
dampers complete as required.
Supply, installation & testing of GI back draught dampers similar construction of gravity louvers (Basement
6 NSR-5 fans- fire case as specified in the drawing.), provided with suitable links to prevent the back pressure of air as Sqm 4 11,796.00 47,184.00
per specifications complete in all respects.
TOTALSUB-HEAD 'B' - AIR DISTRIBUTION (NSR) 5,01,340.00
SUB-HEAD 'C' - ELECTRICAL
LSIG (Microprocessor Based) releases shall be used for incoming feeder.
ii MCCB :
All MCCB's shall be provided with door interlocked rotary handle with ON/TRIP/OFF position indicator,
continuous variable thermal magnetic O/C and S/C releases. The MCCB above 250A rating shall be provided
with microprocessor based releases (settable at site). i/c MCCB shall be provided with E/F release also.
iii All MCCB used in starter feeder shall be suitable for motor duty application.
iv All motor circuit MCB shall be motor duty with 'C' curve.
v Breaking capacity mentioned is Ics value.
vi All MCCBs shall be provided with rotary operating handle and ON/OFF lamps backed by 2Amp control MCB.
vii All meters shall be digital type (unless otherwise specified)
viii All current/voltage transformer shall be cast resin type.
Digitally signed by RAHUL
ix All indicating lamps shall be LED type.
Current density for bus bar shall not be more than 1.0A/Sqmm. Rating of Bus bar is after considering all
derating factors. (Bus bar sizing calculation to be submitted for approval.)
xi All internal control wiring shall be heat resistant type.
xii All TP feeders shall be provided with Isolable neutral link.
xiii All feeders shall be provided with door interlocked with door defeat, pad lock facility.
Live parts shall not be accessible after opening the door, Transparent acrylic sheet to be provided to cover the
xv Spare contacts of ACBs / MCCBs / Relay / Contactor shall be wired upto terminal block.
xvi 20% spare control terminal to be provided.
All MCCBs shall be provided with variable O/L & S/C releases. Incoming MCCB shall be provided with E/F
All incoming/outgoing cables shall be terminated on links/terminals.
xix TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate size of neutral link.
All switchgears used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit
manufacturers type-2 co-ordination chart for the make used.
xxi Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993.
a) IP 43 for indoor panels.
b) IP 55 for outdoor panels.
Supply, installation, testing and commissioning Ventilation Panel (Basement) :- Z1 & Z2 (TYPE-1)
as per specifications described below complete in all respects:
One (1) No. 250A 25KA, FP MCCB With micro processror release (O/C, S/C) Protection, ROH
Metering & Indication:
One (1) Nos. 0-250A digital Ammeter with selector switch protected by 6A control MCB's
One (1) Nos. 0-500 V Digital Voltmeter with Selector Switch and suitable ratio, Cl-1, 10VA CT's.
Set of R/Y/B Phase indicating lamps & On/Off/Trip indication, backed up with 6 Amps Control MCB.
300A TPN Al. Busbar of short circuit withstand capacity 25kA. Busbar shall be insulated with heat shrinkable
sleeves and shall be color coded.
6 Nos. Star Delta Starter for 11.0 KW, Complete with MPCB, contactor, SPPR, ON/OFF/Trip indication lamps
and push buttons, potential free contacts for remote operation in each feeder and Auto Manual Selector
Switch as required including auxiliary relay with contacts for smoke signal.
Set one (Complete with Programming/Internal wiring etc.)
One no. suitable UPS 500VA-1000VA/Power Pack as a part of ventilation panel. PLC will receive 'Modbus'
Signal from fire Panel and shall turn on the smoke time fresh air and exhaust air fans and shall control the
operation of jet fans from low to high speed.
PLC will control ventilation fans & jet fans of both fire zones. There are about 6 3 of these will run on normal
condition & fire condition , 3 fans which will have to be turned ON on fire signal.
Cabling & Conduiting
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of
Upto 35 sq. mm (clamped with 1mm thick saddle)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of
PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
TOTALSUB-HEAD 'C' - ELECTRICAL (NSR) 6,87,187.00
Digitally signed by RAHUL
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT.pdf
Tender Document
BOQ.pdf
Tender Document
CS_cover_2_Quotingsheet.xlsx
Tender Document
drawings.pdf
Tender Document
GCC Contracting PMC 2022 upto six Ammdment.pdf
Tender Document
SCC.pdf
Tender Document
TechnicalSpecs.pdf
Tender Document
Approvedmakes.pdf
Tender Document
corrigendum-2214-pricebidopening.pdf
pdf • 0.08 MB
addendum-50cf35193b30-Addendum01.pdf
pdf • 0.07 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .