EE ETD Banda
220 KV Substation Tindwari Road Banda
Electrical Work
2025_UPTCL_1023015_1
T-57/ETDB/2024-25
Open Tender
Electrical Works
Lump-sum
90 days
Banda
Having Experiance to do similar work in UPPTCL
2 documents required · 2 mandatory
₹590
EE ETD Banda
₹2,000
15 Apr 2025
27 Mar 2025
15 Apr 2025
27 Mar 2025
10 Apr 2025
27 Mar 2025
27 Mar 2025 - 10 Apr 2025
Amount
Details of Work.
Repairing and overhauling of 145 KV SF-6 CB of 40 MVAR Capacitor Bank (GE Make) AT 220KV S/S BANDA. Work consist of : (a) Complete dismantling of mechanism assemby, main spring, ratchet gear and other connected part. Necessary repairing/rectification of defective part. (b) Replacement of closing latch assembly, trip latch, close coil and its proper adjustment. Cleaning & greasing. (c) Check SF-6 gas and fill upto specified limit if require. (d) Dismentling of all pole linkage, pins and rod assembly, cleaning, greasing and its proper adjustment. (e) Check statisfactory close/trip operation of the breaker both by local remote . (f) Check close/trip timing by digital timer
Measurement of Contact Resistant (CRM) ,closing tripping time analyses and operation time of 145KV SF-6 CB.
Overhauling of 33KV VCB AT 220 BANDA a) Checking & Adjustment of Snatch gap travel of drive Insulators rod and tie rod of each Pole. (b) Replacement of all damaged and defective parts closing latch assembly, trip latch, close coil etc and its proper adjustment. Cleaning & greasing. (c) Oiling and Greasing of CRANK gear by opening of lock, circlip etc. (d) Dismentling of all pole linkage, pins and rod assembly, cleaning, greasing and its proper adjustment. (e) Check statisfactory close/trip operation of the breaker both by local remote . (f) Check close/trip timing by digital timer (g) Repairing of mechanism for solving the mechnical problem.After Overhauling of VCB following test to be carried out. (i) Opening & Closing time of breaker of each Pole (ii) carring of contact resistance measurement of each Pole. (iii) Checking of Megger value of breaker Pole.
Overhauling of 33KV VCB AT 132KV S/S Karvi- a) Checking & Adjustment of Snatch gap travel of drive Insulators rod and tie rod of each Pole. (b) Replacement of all damaged and defective parts closing latch assembly, trip latch, close coil etc and its proper adjustment. Cleaning & greasing. (c) Oiling and Greasing of CRANK gear by opening of lock, circlip etc. (d) Dismentling of all pole linkage, pins and rod assembly, cleaning, greasing and its proper adjustment. (e) Check statisfactory close/trip operation of the breaker both by local remote . (f) Check close/trip timing by digital timer (g) Repairing of mechanism for solving the mechnical problem.After Overhauling of VCB following test to be carried out. (i) Opening & Closing time of breaker of each Pole (ii) carring of contact resistance measurement of each Pole. (iii) Checking of Megger value of breaker Pole.
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
M/S SAI RAM ENTERPRISES (BID ID -5109725)
Calculation Enterprises (BID ID -5110626)
SWITCHGEAR AND TRANSFORMER CARE CENTRE (BID ID -5110377)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .