| Sl No | Description | Qty | Unit | Gee Sab Electricals H3 | INDUSTRIAL ELECTRICALS H1 | M/S ROHIT ASSOCIATES H2 |
|---|---|---|---|---|---|---|
| 1.00 | 10 MVA, 33/11 kV, 3 ph, 50 Hz, ONAN, 99.9% pure electrolytic grade copper wound, with high permeability PRIME GRADE, CRGO with M4 Grade or Better core, Outdoor Conventional type Power Transformer (PTR) along with transformer oil, motorised On Load Tap Changer , RTCC & AVR to be supplied along with the OLTC , Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank with air cell, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end), isolating link, isolation with insulators}, pressure relief device, with smart breather, control wiring between sensing equipment and marshalling box, cable supporting tray on the body of transformer, transformer wheels, LV/HV bushing etc as required as per technical specifications, approved drawings and scope of the work. Mandatory Minimum Weight of Core as 6500 kg & Mandatory Minimum Weight Coils as 3000 kg & Mandatory Minimum weight of oil as 5500 kg, & Warranty period of PTR shall be 5 years | 1 | No. | 1,20,00,000 ₹1,20,00,000 Lowest | 1,30,00,000 ₹1,30,00,000 | 1,30,00,000 ₹1,30,00,000 |
| 2.00 | 12 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC sheathed cable with water swellable tape ( water tolerant) , 1.1 kV Grade, ISI, FRLS , including their termination materials like glands, lugs etc. (Polycab/Havells/LS/KEI) | 300 | Mtr. | 250 ₹75,000 Lowest | 800 ₹2,40,000 | 250 ₹75,000 Lowest |
| 3.00 | 6 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC sheathed cable with water swellable tape ( water tolerant) , 1.1 kV Grade, ISI, FRLS , including their termination materials like glands, lugs etc. (Polycab/Havells/LS/KEI) | 300 | Mtr. | 200 ₹60,000 | 400 ₹1,20,000 | 130 ₹39,000 Lowest |
| 4.00 | 2 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC sheathed cable with water swellable tape ( water tolerant) , 1.1 kV Grade, ISI, FRLS , including their termination materials like glands, lugs etc. (Polycab/Havells/LS/KEI) | 350 | Mtr. | 200 ₹70,000 | 200 ₹70,000 | 65 ₹22,750 Lowest |
| 5.00 | HDPE Pipe Outer Dia 180 mm Inner Dia 152 mm for laying of 11kV XLPE Cable from Power Transformer to Control Room | 110 | RM | 900 ₹99,000 | 800 ₹88,000 Lowest | 800 ₹88,000 Lowest |
| 6.00 | RCC Foundation as per approved Drawing for Power Transformer and Allied Equipments/Structures | 70 | Cum. | 900 ₹63,000 Lowest | 10,000 ₹7,00,000 | 3,500 ₹2,45,000 |
| 7.00 | Exacavation of Earth work & Filling(upliftment) of low Lying land( Yard as prone to Flash Flood/water logging) | 30 | Cum. | 1,200 ₹36,000 | 1,000 ₹30,000 | 110 ₹3,300 Lowest |
| 8.00 | 33 kV SCADA compatible line C&R Panel alongwith O/F,E/F numerical relays with inrush blocking feature, IEC 61850 complaint , with minimum 16 DIs & 8 DOs , electrical reset master trip relay, mimic diagram , voltmeter, Ammeter, Annunciation windows with annuciation relays, mandatorily without Tri vector meter | 1 | No. | 3,80,000 ₹3,80,000 | 4,00,000 ₹4,00,000 | 3,55,000 ₹3,55,000 Lowest |
| 9.00 | 33 kV SCADA compatible Transformer C&R Panel alongwith Differential numerical relay & separate back up O/F,E/F numerical relays, IEC 61850 complaint ,with inrush blocking feature in both relays, with minimum 16 DIs & 8 DOs each , electrical reset master trip relay, mimic diagram , voltmeter, Ammeter, Annunciation windows with annuciation relays,without Tri vector meter. | 1 | No. | 4,10,000 ₹4,10,000 | 5,00,000 ₹5,00,000 | 3,55,000 ₹3,55,000 Lowest |
| 10.00 | Digital multifunction load manager in 3-phase 4-wire, Accuracy Class: Standard 0.5S (as per IEC 62053-22). Measurement Parameters: measures over 28 parameters including Voltage (L-L, L-N), Current, Frequency, Power & Energies (Active, Reactive, Apparent), Power Factor, and Phase Angle. THD and individual harmonics measurement up to the 31st harmonic for both voltage and current. Display: Large, back-lit LCD with user-assignable screens (1 to 10 screens can be selected for auto-scrolling). Input Ranges: Voltage: On-site programmable from 100 V L-L to 600 V L-L. Current: On-site programmable for 1A or 5A secondary. Dimensions: 96 x 96 mm (DIN Quadratic).Enclosure Protection: IP54 for the front side and IP20 for terminals. ( Rishab/Secure/Schneider) | 2 | No. | 7,000 ₹14,000 Lowest | 8,00,000 ₹16,00,000 | 10,000 ₹20,000 |
Tender Value
₹2.0 Cr
EMD Value
₹4.0 L
Closing Date
23 May 2026, 4:00 pmClosed
Executive Engineer, STD-II, JPDCL, Jammu
Office of Executive Engineer, STD-II, JPDCL, Jammu
Replacement of 10 MVA Power Transformer at R/stn Ban Sultan
2026_PDD_308626_1
STD-II/Tenders/2026-27/07
Open Tender
Electrical and Maintenance Works
Turn-key
100 days
Ban Sultan
Please refer Tender documents.
4 documents required · 4 mandatory
₹4,000
Executive Engineer, STD-II, JPDCL, Jammu
₹4.0 L
Jammu
6 Jun 2026
24 Apr 2026
25 May 2026
24 Apr 2026
23 May 2026
24 Apr 2026
4 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | 10 MVA, 33/11 kV, 3 ph, 50 Hz, ONAN, 99.9% pure electrolytic grade copper wound, with high permeability PRIME GRADE, CRGO with M4 Grade or Better core, Outdoor Conventional type Power Transformer (PTR) along with transformer oil, motorised On Load Tap Changer , RTCC & AVR to be supplied along with the OLTC , Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank with air cell, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end), isolating link, isolation with insulators}, pressure relief device, with smart breather, control wiring between sensing equipment and marshalling box, cable supporting tray on the body of transformer, transformer wheels, LV/HV bushing etc as required as per technical specifications, approved drawings and scope of the work. Mandatory Minimum Weight of Core as 6500 kg & Mandatory Minimum Weight Coils as 3000 kg & Mandatory Minimum weight of oil as 5500 kg, & Warranty period of PTR shall be 5 years | 1 | No. | - | - |
| 2 | 12 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC sheathed cable with water swellable tape ( water tolerant) , 1.1 kV Grade, ISI, FRLS , including their termination materials like glands, lugs etc. (Polycab/Havells/LS/KEI) | 300 | Mtr. | - | - |
| 3 | 6 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC sheathed cable with water swellable tape ( water tolerant) , 1.1 kV Grade, ISI, FRLS , including their termination materials like glands, lugs etc. (Polycab/Havells/LS/KEI) | 300 | Mtr. | - | - |
| 4 | 2 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC sheathed cable with water swellable tape ( water tolerant) , 1.1 kV Grade, ISI, FRLS , including their termination materials like glands, lugs etc. (Polycab/Havells/LS/KEI) | 350 | Mtr. | - | - |
| 5 | HDPE Pipe Outer Dia 180 mm Inner Dia 152 mm for laying of 11kV XLPE Cable from Power Transformer to Control Room | 110 | RM | - | - |
| 6 | RCC Foundation as per approved Drawing for Power Transformer and Allied Equipments/Structures | 70 | Cum. | - | - |
| 7 | Exacavation of Earth work & Filling(upliftment) of low Lying land( Yard as prone to Flash Flood/water logging) | 30 | Cum. | - | - |
| 8 | 33 kV SCADA compatible line C&R Panel alongwith O/F,E/F numerical relays with inrush blocking feature, IEC 61850 complaint , with minimum 16 DIs & 8 DOs , electrical reset master trip relay, mimic diagram , voltmeter, Ammeter, Annunciation windows with annuciation relays, mandatorily without Tri vector meter | 1 | No. | - | - |
| 9 | 33 kV SCADA compatible Transformer C&R Panel alongwith Differential numerical relay & separate back up O/F,E/F numerical relays, IEC 61850 complaint ,with inrush blocking feature in both relays, with minimum 16 DIs & 8 DOs each , electrical reset master trip relay, mimic diagram , voltmeter, Ammeter, Annunciation windows with annuciation relays,without Tri vector meter. | 1 | No. | - | - |
| 10 | Digital multifunction load manager in 3-phase 4-wire, Accuracy Class: Standard 0.5S (as per IEC 62053-22). Measurement Parameters: measures over 28 parameters including Voltage (L-L, L-N), Current, Frequency, Power & Energies (Active, Reactive, Apparent), Power Factor, and Phase Angle. THD and individual harmonics measurement up to the 31st harmonic for both voltage and current. Display: Large, back-lit LCD with user-assignable screens (1 to 10 screens can be selected for auto-scrolling). Input Ranges: Voltage: On-site programmable from 100 V L-L to 600 V L-L. Current: On-site programmable for 1A or 5A secondary. Dimensions: 96 x 96 mm (DIN Quadratic).Enclosure Protection: IP54 for the front side and IP20 for terminals. ( Rishab/Secure/Schneider) | 2 | No. | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.50 MB
SBDBansultan.pdf
Tender Documents • 0.88 MB
TechSpecs33KV.pdf
Other Document • 7.79 MB
BOQ_999915.xls
BOQ • 0.42 MB
ExtBanSultan.pdf
PDF • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .