Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.7 LAccepted-Finance | ₹2.7 L | L1 | Accepted-Finance Lowest |
| 2 | L2₹2.8 LRejected-Finance | ₹2.8 L | L2 | Rejected-Finance 2nd. Lowest |
| 3 | L3₹2.8 LRejected-Finance 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | ₹2.8 L | L3 | Rejected-Finance 3rd. Lowest |
Tender Value
Refer Docs
EMD Value
₹5,600
Closing Date
12 Jan 2026, 4:00 pmClosed
Assistant Engineer, AHESD
West Bengal Legislative Assembly South Annex Building Gr Floor Kolkata 700 001
SITC of 6 nos Air conditioning machine in the room of 4 nos Officers and 2 nos P.S. or P.A.s at the 1st Floor of New Administrative Building Assembly House Kolkata
2025_WBPWD_974534_1
eNIQ No. - 07 /WBPWD/AE/AHESD of 2025-26
Open Tender
ELECTRICAL WORKS ORG
10 days
Assembly House Elect Sub Divn
Please refer Tender documents.
6 documents required · 6 mandatory
₹5,600
Yes
2 Feb 2026
26 Dec 2025
15 Jan 2026
31 Dec 2025
12 Jan 2026
2 Jan 2026
Dismantling of existing outdoor and indoor unit of air-conditioning system, including disconnection of refrigerant piping, electrical connections, supports, brackets and necessary accessories, removing the unit carefully without causing any damage, and stacking the serviceable materials safely at site, complete as directed by the Engineer-in-Charge.
Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180 - 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42°C ambient temperature. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per direction of EIC. The system shall be able to operate up to 50 0C (out door ambient temperature). [Make Daikin /Hitachi /Mitsubishi /O-General) - 1.0 TR with 3 Star BEE Rating
CPWD Item-P-240/31.14: Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
CPWD Item-P-240/31.14.3: 12.7 mm (1/2") dia (OD) (Soft drawn) with tube thickness 1.2 mm
CPWD Item-P-240/31.14.1: 6.4 mm (1/4") dia (OD) (Soft drawn) with tube thickness 1.2 mm
Supplying & drawing of 4 core x 2.5 sq.mm. PVC insulated copper cable for interconnecting the indoor & outdoor unit. (Make: Havells)
Supplying, fitting & fixing of 5/8 th. Inch dia Heavy duty PVC drain pipe for condensed water as per direction of EIC.
Supplying, fitting and fixing PVC pipes of approved make (medium duty) conforming to ASTMD - 1785 and threaded to match with GI Pipes as per IS: 1239 (Part - I). with all necessary accessories, specials viz. socket, bend, tee, union, cross, elbow, nipple, long screw, reducing socket, reducing tee, short piece etc. fitted including cost of all materials ,jointing materials, cutting pipes, making threads ,etc as directed complete in all respect.
Fabrication and installation of outdoor unit wall bracket suitable for 1.0 TR air-conditioning system, fabricated from 75X35 MS C-section, ISA 50 mm angle and 40 × 5 mm MS flat including cutting, welding, grinding, drilling of holes, providing necessary stiffeners, anti-corrosive red oxide primer and two coats of synthetic enamel paint, complete with supply of all materials, labour and T&P. The bracket shall be installed firmly on the wall with suitable anchor fasteners/bolts, ensuring proper alignment, level and load-bearing capacity to facilitate installation and future maintenance of the outdoor unit, as per direction of the Engineer-in-Charge. (Size of platform 1200 x 900 mm)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.53 MB
Tendernotice_2.pdf
PDF • 1.35 MB
BOQ_2372555.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid