Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.7 CrAccepted-AOC | ₹9.7 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹9.9 CrRejected-AOC | ₹9.9 Cr | L2 | Rejected-AOC L2 |
| 3 | L3₹10.0 CrRejected-AOC | ₹10.0 Cr | L3 | Rejected-AOC L3 |
| Sl No | Description | Qty | Unit | Sai Electricals and Engineers L2 | Shivam Corporation L1 | CHAITRA ELECTRICALS AND ENGINEERING L3 |
|---|---|---|---|---|---|---|
| 1.00 | SITC OF D.G.SET WITH PANEL-200KVA | 2 | Nos | 25,31,400 ₹50.6 L | 25,05,000 ₹50.1 L | 25,78,250 ₹51.6 L |
| 2.00 | SITC OF AUTOMATIC MAINS FAILURE PANEL SUITABLE TO DG SET -200KVA | 2 | Nos | 3,49,250 ₹7.0 L | 3,45,500 ₹6.9 L | 3,55,700 ₹7.1 L |
| 3.00 | SITC OF D.G.SET WITH PANEL-140KVA | 3 | Nos | 19,14,690 ₹57.4 L | 18,95,000 ₹56.9 L | 19,50,110 ₹58.5 L |
| 4.00 | SITC OF AUTOMATIC MAINS FAILURE PANEL SUITABLE TO DG SET -140KVA | 3 | Nos | 2,60,220 ₹7.8 L | 2,57,500 ₹7.7 L | 2,65,050 ₹8.0 L |
| 5.00 | Cement concrete foundation using M-20 cement concrete | 70 | Cum | 9,350 ₹6.5 L | 9,255 ₹6.5 L | 9,523 ₹6.7 L |
| 6.00 | Excavation for foundation, substructures, basements, | 42.5 | Cum | 650 ₹27,625 | 620 ₹26,350 | 665 ₹28,262.50 |
| 7.00 | Earthing station 600 mm x 600 mm x 6 mm GI galvanised | 15 | Nos | 16,030 ₹2.4 L | 15,865 ₹2.4 L | 16,400 ₹2.5 L |
| 8.00 | 600 X 600 X 3.15 mm Copper Plate, 3000mm dip with | 10 | Mtr | 23,765 ₹2.4 L | 23,525 ₹2.4 L | 24,200 ₹2.4 L |
| 9.00 | Earthing Continuity Conductors -25 x 3mm Tinned copper | 100 | Mtr | 778 ₹77,800 | 770 ₹77,000 | 792 ₹79,200 |
| 10.00 | Earthing Continuity Conductors -25 x 3mm GI | 250 | Mtr | 46 ₹11,500 | 46 ₹11,500 | 50 ₹12,500 |
Tender Value
Refer Docs
EMD Value
₹12.5 L
Closing Date
20 Sept 2025, 4:00 pmClosed
M.H. Wankhede
Chief Engineer (M n E), BMC 1st Floor, Engineering Hub Building, Dr. E. Moses Road, Worli Naka, Worli, Mumbai- 400 018,
Upgradation of Backup Power System at various municipal healthcare facilities.
2025_MCGM_1213321_1
Ch.E./MnE/2751 dtd. 28.07.25
Open Tender
Electrical Works
Mumbai
Please refer Tender documents.
3 documents required · 3 mandatory
₹24,500
₹12.5 L
Engineering Hub Building, Worli
24 Dec 2025
27 Aug 2025
22 Sept 2025
27 Aug 2025
20 Sept 2025
27 Aug 2025
4 Sept 2025
Amount
SITC OF D.G.SET WITH PANEL-200KVA
SITC OF AUTOMATIC MAINS FAILURE PANEL SUITABLE TO DG SET -200KVA
SITC OF D.G.SET WITH PANEL-140KVA
SITC OF AUTOMATIC MAINS FAILURE PANEL SUITABLE TO DG SET -140KVA
Cement concrete foundation using M-20 cement concrete
Excavation for foundation, substructures, basements,
Earthing station 600 mm x 600 mm x 6 mm GI galvanised
600 X 600 X 3.15 mm Copper Plate, 3000mm dip with
Earthing Continuity Conductors -25 x 3mm Tinned copper
Earthing Continuity Conductors -25 x 3mm GI
1st category Al armoured cables FRLS outer sheathed- 3.5C x 185 Sq.mm
1st category Al armoured cables FRLS outer sheathed- 3.5C x 240 Sq.mm
1.1 kV grade stranded Cu conductor, XLPE insulated, extruded PVC inner and FRLS outer sheathed, galvanised steel round or strip armoured cables - 6C x 2.5Sq.mm
Cable End Termination For Aluminium Cables – 3.5C x 185 Sq.mm
Cable End Termination For Aluminium Cables – 3.5C x 240 Sq.mm
Cable End Termination For Copper Cables – 6C x 2.5
3 Noss. single core Cu PVC insulated flexible cable of 95 Sq.mm. for phases & 1 single core Cu PVC insulated flexible cable for neutral of 50 Sq.mm for 200 Amp TPNSS switch.
G.I. Cable tray with all other accessories 300 x 50mm (W x H) - (16 SWG - 1.6mm)with cover
Fire Extinguisher should be for all type of Fire A-B-C. It should have a delivery mechanism of multidirectional nozzle with conical deflector and SS 316 cap with black colour powder coating. It Shou ld have thickness of 1.22mm. It shoild have high metal strength which provides durability.
Fire bucket , stand,hook and First Aid Box-Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver Paint.
RUBBER MAT 2MM THICK SIZE 3X5 FEET
SITC of D.G.SET WITH PANEL -750KVA
Cement concrete foundation using M-20 cement concrete
Excavation for foundation, substructures, basements,
Earthing station 600 mm x 600 mm x 6 mm GI galvanised
600 X 600 X 3.15 mm Copper Plate, 3000mm dip with
Earthing Continuity Conductors -25 x 3mm Tinned copper
Earthing Continuity Conductors -25 x 3mm GI
1.1 kV grade stranded Cu conductor, XLPE insulated, extruded PVC inner and FRLS outer sheathed, galvanised steel round or strip armoured cables - 6C x 2.5Sq.mm
Cable End Termination For Copper Cables – 6C x 2.5
Fire Extinguisher should be for all type of Fire A-B-C. It should have a delivery mechanism of multidirectional nozzle with conical deflector and SS 316 cap with black colour powder coating. It Shou ld have thickness of 1.22mm. It shoild have high metal strength which provides durability.
Fire bucket , stand,hook and First Aid Box-Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver Paint.
RUBBER MAT 2MM THICK SIZE 3X5 FEET
heat Shrinkable LT straight joint kit for Aluminium Arm Cable from size 3C/3.5C upto 120 sqmm
heat Shrinkable LT straight joint kit from size 3C/3.5C from 150sqmm upto 300 sqmm
Cable End Termination with DC Glands, Washers & Bimetallic lugs for termination of Aluminum cables to copper busbar upto 120 SQ MM
Cable End Termination For Aluminium Cables – 3.5C x 630 Sq.mm
Hiring of 500 KVA DG Set with Operator (per shift 8 Hours)
Diesel charges for 500 KVA DG set
NOMINAL MIX OF 1:1.5:3 (1 CEMENT OPC:1.5 COARSE SAND : 3 GRADED STONE AGGREGATE 20 MM NOMINAL SIZE)
3 Noss. single core Cu PVC insulated flexible cable of 150 Sq.mm. for phases & 1 single core Cu PVC insulated flexible cable for neutral of 70 Sq.mm for 250 Amp TPNSS switch.
1st category Al armoured cables FRLS outer sheathed- 3.5C x 630 Sq.mm
1.1 kV grade stranded Cu conductor, XLPE insulated, extruded PVC inner and FRLS outer sheathed, galvanised steel round or strip armoured cables - 4C x 2.5Sq.mm
1.1 kV grade stranded Cu conductor, XLPE insulated, extruded PVC inner and FRLS outer sheathed, galvanised steel round or strip armoured cables - 2C x 2.5Sq.mm
1st category Al r armoured cables FRLS outer sheathed- 4C x 16 Sq.mm
1st category Al r armoured cables FRLS outer sheathed- 4C x 25 Sq.mm
1st category Al r armoured cables FRLS outer sheathed- 3.5C x 50 Sq.mm
1st category Al r armoured cables FRLS outer sheathed- 3.5C x 120 Sq.mm
Cable End Termination For Copper Cables – 4C x 2.5
Cable End Termination For Copper Cables – 2C x 2.5
Supply & Laying of double wall corrugated (DWC) pipe 175 mm OD / 148 mm I.D.
Supply & Laying of double wall corrugated ( DWC) pipe 63 mm OD / 51 mm I.D.
G.I. Cable tray with all other accessories 450 x 75mm (W x H) - (14SWG - 2mm) without cover
Supply and laying Hume pipe -150mm Dia.
DG Sync Panel INCOMER SECTION: a) 2 No. 2000 A, 4P EDO, ACB equipped with LSIG protection and Ethernet Enabled for communication and with suitable extension of breaker terminals for connection of Copper busduct with flange. b) 1 Set Surge Arrester (3P+N) + 100A, TPN, MCCB BUS COUPLER SECTION a) 1 No. 1600 A, 4P EDO, ACB equipped with LSIG protection and Ethernet Enabled for communication. OUTGOING SECTION: a) 2 No. 1600 A, 4P EDO, ACB equipped with LSIG protection and Ethernet Enabled for communication. METERING SECTION: a) 1 no. multifunction meter capable of reading various parameters like V,A,F,PF,W,VAR,etc including THD measurement with suitable communication port for BMS connectivity over Modbus RS 485 for all feeders. b) Set of LED based indication lamps for R, Y, B phase. PLC to be provided for changover Scheme All Electrical interlockings shall be provided & Load Management shall be provided.
1. Main LT Panel 01 (50kA) INCOMER SECTION: a) 2 Nos. 1600 A, 4P ACB equipped with LSIG protection and Ethernet Enabled for communication and with suitable extension of breaker terminals for connection of with flange/Cable. ( 1 Trafo + 1 DG ) b) 2 Set Surge Arrester (3P+N) + 100A, TPN, MCCB Bus Coupler : OUTGOING SECTION: a) 1 Nos. 400 A, TPN, ACB equipped with LSIG protection b) 2 Nos. 250 A, TPN, ACB equipped with LSIG protection c) 4 Nos. 200 A, TPN, MCCB equipped with LSIG protection d) 6 Nos. 125 A, TPN, MCCB equipped with LSIG protection e) 7 Nos. 100 A, TPN, MCCB equipped with LSIG protection f) 16 Nos. 63 A, TPN, MCCB equipped with LSIG protection g) 02 Nos. 32 A, TPN, MCCB equipped with LSIG protection METERING SECTION: a) 1 no. multifunction meter capable of reading various parameters like V,A,F,PF,W,VAR,etc including THD measurement with suitable communication port for BMS connectivity over Modbus RS 485 for all feeders. b) Set of LED based indication lamps for R, Y, B phase.
Main LT Panel 02 (50kA) INCOMER SECTION: a) 2 Nos. 1000 A, 4P ACB equipped with LSIG protection and Ethernet Enabled for communication and with suitable extension of breaker terminals for connection of with flange/Cable. ( 1 Trafo + 1 DG ) b) 2 Set Surge Arrester (3P+N) + 100A, TPN, MCCB Bus Coupler : OUTGOING SECTION: a) 08 Nos. 125 A, TPN, ACB equipped with LSIG protection b) 12 Nos. 100A, TPN, ACB equipped with LSIG protection c) 8 Nos. 63 A, TPN, MCCB equipped with LSIG protection f) 4 Nos. 32 A, TPN, MCCB equipped with LSIG protection METERING SECTION: a) 1 no. multifunction meter capable of reading various parameters like V,A,F,PF,W,VAR,etc including THD measurement with suitable communication port for BMS connectivity over Modbus RS 485 for all feeders. b) Set of LED based indication lamps for R, Y, B phase.
Supply & Installation of 1600A Copper (65kA for 1 sec) 4 pole IP 54 bus ducts including bends, T Joints,Expansion Joints, End Flanges, Flexibles, Outdoor Canopy, Adaptor boxes and all special install ation material.- Class B Mylar Insulation shall be provided.- The Integral Earth Bus Bar shall be wrap around construction and shall be rated for 50% of Phase Bus Bar.- External Earth Bus bar shall be provided as per the local certifying authorities.- Colour Shade of Bus Bar shall be ANSI 49 Grey.- The Joint Pak shall be provided with Double Headed Bolts in which the head should shear during final tightening. Make list of Bus duct : - Schneider/Siemens- Sentron/ ABB only
S.I.T.C of Wireless Temperature Sensor [Wireless and self-powered (no auxiliary supply, no battery)] Make - Schneider , Siemens, ABB
S.I.T.C of HMI for Displaying Meter data, ACB Data & Wireless temp sensor data. Make list of HMI : - Schneider ,Siemens , ABB
Liasioning charges and coordination for load sanction of the above scheme from BEST/ADANI/MSEDCL/Power Utility and CEIG approval.
Removal of switchgears / ELCB / RCCB from 63 Amp to 100 Amp.
Removal of switchgears / ELCB / RCCB from 100 Amp to 400 Amp.
Removal of busbar chamber above 100 Amp TPN to 800 Amp TPN.
Removal of DG set
Removal of cable from 1.5 sq.mm to 3-1/2 core x 35 sq.mm.
Removal of cable above 3-1/2 core x 35 Sq. mm. to 3-1/2 core x 70 sq. mm
Removal of cable above 3-1/2 core x 70 Sq.mm upto 3-1/2 core x 120 sq. mm.
Refixing of 2 core / 3 core / 3-1/2 core / 4 core/ 6 core copper / aluminium conductor armoured / unarmoured cable above 16 sq.mm. to 150 sq.mm. size on wall / ceiling etc.
Rebate for Switchgears upto 100 Amps (including 100 Amp.)
Rebate for Switchgears above 100 Amps to 200 Amps.
Rebate for Switchgears above 200 Amps to 800 Amps.
Rebate for Busbar chamber above 100 Amp TPN to 800 Amp TPN.
Rebate for DG set
Sai Electricals and Engineers (BID ID -6862256)
CHAITRA ELECTRICALS AND ENGINEERING (BID ID -6861342)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
BOQ_2097413.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid