| Sl No | Description | Qty | Unit | AMAN ENTERPRISES L2 | SAINI ELECTRIC STORE L1 |
|---|---|---|---|---|---|
| 1.00 | Comprehensive maintenance of VCB's installed at various pump houses of main canal (MGC) of any type, make & capacity complete to make functional in case of any type of fault occures at any site/pump house within prescribed time frame by providing skilled & expert mechanic/ engineer including following works involved:
(i) By Disconnecting of HT connections and DC connections from existing bus bar and disconnecting trolley including servicing of complete parts of VCB of any make any capacity , cleaning with carbo tetra chloride lubrication of mechanical parts , adjustment and calliberation of complete relays etc., checking complete parts including replacement of control wiring with single core copper conductor cable of existing size as required for VCB of any type any make for satisfactory running and repalcement of deffective parts with new one to make it fully functional , including one coat of H- class insulation paint on bus bar spouts and other connected parts including reassembling the VCB , reconnecting all HT & AC/DC connections complete in functional order including testing on existing load complete all as speified and directed .
(ii) Only fixing in replacement of all the deffective parts such as metering devices, relays,control devices,indicators,charging motors,mechanical gears/handle ,rotary swithes,CT 's,PT's ,bushes,control fuses,contactors,MCB's, Battery bank etc or all any left over items as shown in separate schedule of this tender on cost basis and separate payment shall be made on approved rates after approval by competant authority with maintaining proper record in document. Note:-( i) In case of any complaint , the agency shall provide expert engineer at respective site to attend the site i.e. MC-5 of MGC, NB-1 of NNL Branch for repair & rectification of deffect develloped in VCB's all of sudden within 24 Hours after complaint given by concerned JE/SDO .Penality charges @ 0.5% of particular work per week shall be levied in case of not attending the complaint. (ii) The quoted rates shall include for fixing of serviceable parts in position and repalcement of unserviceable parts with new parts. (iii)The new parts shall be measured and paid separately under appropriate item schedule part-II as supply only mentioned herein after.
(iv) Small items such as nut, bolts, screws & washers required at site are deemed to be included in the quoted rates by the contractor. (v) The complete work (repairing, servicing & calliberating ) shall be carried out by authorised skiled engineer of the approved agency. | 6 | Each Job | 18,000 ₹1.1 L | 16,700 ₹1.0 L |
| 2.00 | Supply & Fixing Vaccume Interrupter (bottle) model VG6-type complete for VCB 3.3 KV as per existing VCB complete of approved make | 3 | No. | 30,000 ₹90,000 | 28,700 ₹86,100 |
| 3.00 | Credit of old Copper scrap (Actual weight of old scrap will be measured by the committee)
Old scrap/parts shall be property of firm. | 5.5 | Kg. | 450 ₹2,475 | 417 ₹2,293.50 |
Tender Value
₹2.0 L
EMD Value
₹3,980
Closing Date
10 Feb 2026, 1:00 pmClosed
XEN M/GARH W.S MECH. DIVISION, NARNAUL
Executive Engineer, M/GARH W.S MECH. DIVISION, NARNAUL
Repair and Servicing of VCB Panels at Pump House MC-5 of M/Garh Canal in M/Garh W/S Mech. Division, Narnaul.
2026_HRY_500205_1
No. 267-83/9-A dated 30.01.2026
Open Tender
Pumps/Motors
60 days
XEN M/GARH W.S MECH. DIVISION, NARNAUL
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
₹3,980
Yes
26 Feb 2026
2 Feb 2026
10 Feb 2026
2 Feb 2026
10 Feb 2026
2 Feb 2026
Supply & Fixing Vaccume Interrupter (bottle) model VG6-type complete for VCB 3.3 KV as per existing VCB complete of approved make
Credit of old Copper scrap (Actual weight of old scrap will be measured by the committee) Old scrap/parts shall be property of firm.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.30 MB
BOQ_578810.xls
BOQ • 0.27 MB
bidbook1.pdf
Additional Documents • 4.35 MB
Annexures.pdf
Other Document • 0.54 MB
Download all tender documents and submit your bid