Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.8 LAccepted-AOC 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹20.4 L+₹1.6 L (8.42%)Rejected-Finance | L2 | Rejected-Finance 2nd Lowest Bidder | |
| 3 | L3₹20.7 L+₹1.9 L (10.1%)Rejected-Finance 19B PANKAJINI CHATTERJEE ROAD CHARU MARKET KOLKATA WEST BENGAL 700033 UDYAM WB 10 0047115 | KOLKATA | WEST BENGAL | 700033 | L3 | Rejected-Finance 3rd Lowest Bidder |
Tender Value
Refer Docs
EMD Value
₹42,455
Closing Date
22 Nov 2024, 5:00 pmClosed
EE-I,WKED,PWDte.
New Secretariat Building, C Block, 4th floor 1, K.S Roy Road, Kolkata-700001
Replacement of damaged parts/devices incl. dismantling, refixing, re-commissioning and restoration of the existing Fire detection system at Sesquicentenary building of the Honble High Court, Calcutta.
2024_WBPWD_759144_1
WBPWD/EE-WKED/NIQ-14/2024-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
60 days
High Court, Calcutta
Please refer Tender documents.
5 documents required · 5 mandatory
₹42,455
27 Dec 2024
27 Sept 2024
26 Nov 2024
27 Sept 2024
22 Nov 2024
27 Sept 2024
Amount
Supply , Installation, Testing and commissioning of Multi sensor Detector with base[VDS/LPCB approved under EN listed/standards or UL/FM approved under NFPA listed/standards] as per IS:-2189 of latest ammendment with in-built optical smoke-sensor as well as additional heat detector sensors with decentalized intelligence and all necessary accessories as rqequired.( Make: Honeywell-Esser/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Honeywell-Notifier/Bosch/ Edwards/ Apollo/ Johnson Control/ Securiton)
Supply , Installation, Testing and commissioning of Heat Detector complete with base and all other necessary accessories[VDS/LPCB approved under EN listed/standards or UL/FM approved under NFPA listed/standards] as per IS:-2189 of latest ammendment with all necessary accessories as rqequired.( Make: Honeywell-Esser/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Honeywell-Notifier/Bosch/ Edwards/ Apollo/ Johnson Control/ Securiton)
Supply, installation, testing & commissioning of (VDS/LPCB approved under EN listed/standards or UL/FM approved under NFPA listed/ standards) Inteliigent addressable manual call point complete with all accessories and suitable for/matching with Fire Alarm panel as per IS-2189 of latest ammendment. ( Make: Honeywell-Esser/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Honeywell-Notifier/Bosch/ Edwards/ Apollo/ Johnson Control/ Securiton)
Supply, Installation, Testing & Commissioning of (VDS/LPCB approved under EN listed/standards or UL/FM approved under NFPA listed/ standards)Intelligent addressable loop powered sounder/Hooter (sound output of minimum 90db) cum strobe (having light intensity from 15 cd to 110 cd) complete with all accessories and suitable for/matching with the Fire Alarm panel as per IS-2189 of latest ammendment. ( Make: Honeywell-Esser/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Honeywell-Notifier/Bosch/ Edwards/ Apollo/ Johnson Control/ Securiton)
Supply & Installation of Response Indicator having 2 nos. red coloured LED lamps complete with all necessary accessories & connection and suitable for/maching with the Fire Alarm panel. [VDS/LPCB approved under EN listed/standards or UL/FM approved under NFPA listed/standards]. ( Make: Honeywell-Esser/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Honeywell-Notifier/Bosch/ Edwards/ Apollo/ Johnson Control/ Securiton)
Supply ,Installation, Testing and Commissioning of (VDS/LPCB approved under EN listed/standards or UL/FM approved under NFPA listed/ standards) Addressable fully networkable fire alarm control Panel suitable for the devices as stated in the previous item of this BOQ along with 20% spare capacity with each loop loading exceeding 80% of the capacity of detectors & devices taken together complying to per IS-2189 : 2008 or its latest ammendment and with minimum 600 character alpha-neumeric liquid crystal display. The panel should be soft addressable type and shall be able to give pin point location of all fire/fault conditions. Furthermore the Panel must be able to automatically switch-off the respective control switches with help monitor module whenever any module is triggered. The Panel must be able to store sufficient number of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal Printer (if required), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in-built surge protection facilty, integral SMF lead acid batteries with sealed cells of 24 V with integral battery charger complete as required and capable for 24 hrs normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. The FACP capable of being networked(future expansion) with other similar FACP located at different parts of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with Public Address system, remote computer and BMS interface. The system must be preloaded with licenced software. ( Make: Honeywell-Esser/ Siemens-Cerberus Pro/ Ravel/ Secutron/ Honeywell-Notifier/Bosch/ Edwards/ Apollo/ Johnson Control/ Securiton)
Supplying & laying of 2x1.5 sqmm FRLS shielded copper Conductor stranded cables in red/black color and generally confirming to IS-694-2010 and meet the signal cabling requirements (Make-Havells/Finolex/Polycab/Gloster/KEI as approved by E.I.C)
Supplying and fixing 20 mm PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works [E-16/7(a)]
NOTE : The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm & Signaling Code 5. Local Statutory Regulations 6. Manufacturer Recommendation.
TESTS : 1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done. 3. The Commissioning Manuals, Tools , Dongles, USB Token, Software, or whatever is required for the Commissioning of the FACP, in whatever name it called must be handed over to the EIC, along with the passwords of the panel. 4. Four copies of Single Line Diagram (SLD), Block Diagram with proper speification of whole system should be submitted to the E.I.C. Training programme for software installation, formatting, bypass defective devices, rectification of malfunctioning and all other essential process related to the operation of system should also be given to Engineers under this Division.
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
Add. G.S.T.@ 18% on total value.
Add. LWC.@ 1% on total value
Fire Shield Engineering & Equipments (BID ID -5776934)
BALAJI FIRE PROTECTION SYSTEMS (BID ID -5776415)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .