Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹67.4 LAccepted-AOC | ₹67.4 L Quoted ₹67.9 L | L-1 | Accepted-AOC Being L1 |
| 2 | L-2₹69.8 L+₹1.8 L (2.68%)Rejected-AOC | ₹69.8 L+₹1.8 L (2.68%) | L-2 | Rejected-AOC Other than L-1 |
| 3 | L-3₹70.1 L+₹2.2 L (3.18%)Rejected-AOC | ₹70.1 L+₹2.2 L (3.18%) | L-3 | Rejected-AOC Other than L-1 |
| 4 | L-4₹72.7 L+₹4.8 L (7.04%)Rejected-AOC | ₹72.7 L+₹4.8 L (7.04%) | L-4 | Rejected-AOC Other than L-1 |
| 5 | L-5₹73.9 L+₹6.0 L (8.77%)Rejected-AOC 1ST FLOOR SCO 35 CHAURA BAZAR ZIRAKPUR PUNJAB | BATHINDA | PUNJAB | 151001 | ₹73.9 L+₹6.0 L (8.77%) | L-5 | Rejected-AOC Other than L-1 |
Tender Value
₹83.0 L
EMD Value
₹1.5 L
Closing Date
20 Jun 2024, 6:00 pmClosed
CWE Chandimandir
CWE Chandimandir PIN-134107
CWE/CHM-10/2024-25 SPECIAL REPAIR OF BER AIR CONDITIONER AT CHANDIMANDIR CANTT
2024_MES_653659_1
CWE/CHM-10/2024-25
Open Tender
Miscellaneous Works
Item Rate
180 days
GE Chandimandir
Class C cat c(I)
8 documents required · 8 mandatory
₹1,000
Yes
GE Chandimandir
₹1.5 L
Yes
3 Sept 2024
13 May 2024
22 Jun 2024
13 May 2024
20 Jun 2024
13 Jun 2024
14 May 2024 - 21 May 2024
Amount
Supply, Installation, testing and commissioning of air conditioners which shall be either ceiling mounted Ductable type, cassette type, High wall unit as specified here-in-after. The air conditioner shall have independent electronic control valve to control the refrigerant flow rate respond to variations of the air-conditioning load of the room. The fan shall be aerodynamically designed turbo multi blade type, Statically and dynamically balanced to ensure lowest noise, The cooling coil shall be made of seamless copper tube, The tube shall be hydraulically or mechanically expanded and tested for 21 Kg/sqcm. Indoor units shall have a wired remote control. They shall be operated through from the wired remote control from the respective rooms including taking down of old air conditioner and depositing to MES store yard complete all as specified and as directed by Engineer-in-charge. Note :- The Drain pump as a standard accessory and shall be deemed to be included in the rate quoted against Cassette/ FCU unit of Non-VRV unit.
3 TR Ductable type unit (R-410)
5.5 TR Ductable type unit (R-410)
8.5 TR Ductable type unit (R-410)
3 TR Cassette type unit
4 TR Cassette type unit
Supply, Installation, testing and commissioning in replacement of MS stand for the following types of air conditioners, powder coated, heavy duty complete all as specified and as directed by Engineer-in-charge.
3 TR Ductable type unit (R-410)
5.5 TR Ductable type unit (R-410)
8.5 TR Ductable type unit (R-410)
3 TR Cassette type unit
4 TR Cassette type unit
Supply, Installation, testing and commissioning in replacement of Inter connecting refrigerant pipe work with closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger and all external piping shall run in covered cable tray as per specification complete all as specified and as directed by Engineer-in-charge. Note: The contractor has to get the route and sizing approved from GE before starting the work at site.
Copper pipe 28.6 mm outer dia with insulation of 19 mm
Copper pipe 22.6 mm outer dia with insulation of 19 mm
Copper pipe 15.9 mm outer dia with insulation of 13 mm
Copper pipe 12.7 mm outer dia with insulation of 13 mm
Copper pipe 9.5 mm outer dia with insulation of 13 mm
Supply, Installation, testing and commissioning in replacement of UPVC piping of following sizes with 6 mm nitrile rubber insulation O class complete with fittings, supports as per specifications complete all as specified and as directed by Engineer-in-charge.
40 mm Dia
32 mm Dia
M&L of Sub main wiring with four runs of single core PVC insulated and unsheathed multistranded, copper conductor (FRLSH) cable of size 6.0 sqmm, 1100V grade, and incl adequate sizes PVC non metallic conduit of appropriate dia with accessories and fittings and one run of 6.0 sqmm single core multi stranded copper conductor (FRLSH) cable as earth continuity conductor complete all as specified and as directed by engineer-in-charge.
M&L of Sub main wiring with four runs of single core PVC insulated and unsheathed multistranded, copper conductor (FRLSH) cable of size 10.0 sqmm, 1100V grade, and incl adequate sizes PVC non metallic conduit of appropriate dia with accessories and fittings and one run of 10.0 sqmm single core multi stranded copper conductor (FRLSH) cable as earth continuity conductor complete all as specified and as directed by engineer-in-charge.
M&L of Sub main wiring with four runs of single core PVC insulated and unsheathed multistranded, copper conductor (FRLSH) cable of size 16.0 sqmm, 1100V grade, and incl adequate sizes PVC non metallic conduit of appropriate dia with accessories and fittings and one run of 16.0 sqmm single core multi stranded copper conductor (FRLSH) cable as earth continuity conductor complete all as specified and as directed by engineer-in-charge.
Notes for item No 5 to 7 :- (i) for payment purpose, Four runs runs of cable, one run of earth wire and one run of PVC non metallic conduit shall be measured as one running meter length. (ii) Color code shall be Red for phase, black for neutral and green for earth. (iii) Earth wire shall run inside the conduit pipe.
Supply and fixing in replacement of 3 core, 2.5 sqmm, FRLSH, PVC insulated, unseathed, multistranded copper conductor wire for communication from outdoor unit to indoor unit including PVC conduit of suiable size complete all as specified and as directed by engineer-in-charge.
Supply, installation, testing and commissioning in replacement of Site fabricated rectangular 24 gauge sheet GI ducting, complete with supports, dampers etc. as per IS 655 and approved drawing and as per specifications complete all as specified and as directed by engineer-in-charge.
Supply, installation, testing and commissioning in replacement of Site fabricated rectangular 22 gauge sheet GI ducting, complete with supports, dampers etc. as per IS 655 and approved drawing and as per specifications complete all as specified and as directed by engineer-in-charge.
Supply, install, testing and commissioning of LT Panel board, Factory made, CPRI approved, outdoor type double door, suitable for floor mounting of size not less than 1500 x 900 x 450 mm with locking arrangement, fabricated out of 2mm thick CRCA sheet, powder coated, dust/water & vermin proof, suitable for 415 volts 3 phase 50 Hz with 4 No's heat shrinkable insulated copper bus bars of capacity not less than 1.5 times of incoming MCCB's including all MCCB connections, having ISMC 75 for base frame, 750 mm long legs of 80mm x 10 mm angle iron (04 Nos) grouted in PCC 1:2:4 including taking down old unserviceable panel, complete all as specified and as directed by engineer-in-charge, with and including the following accessories :-
(a) Four pole MCCB, 630 Amps, 415 volts, 50 HZ, with adjustable thermal & magnetic release capacity 50 KA and Ics = 100 % of Icu - 01 Nos - As INCOMING (b) Four pole MCCB, 63 amps, 415 volts, 50 HZ, with adjustable thermal & magnetic release capacity 25 KA and Ics = 100 % of Icu - 10 Nos - As OUTGOING (c) Phase indicator lamp complete with copper control wiring with suitable size of CT complete - 01 (set of three). (d) Earthing terminals - 02 Nos. (e) Digital type LCD display voltmeter and ammeter of size 96mm x 96mm- 01 set. (f) Danger notice plate dully rivetted/ fixed on front door - 01 No
Supply, Installation, Testing and Balancing of Powder coated aluminum construction extruded Grills as per approved drawings and specifications including of volume control damper at the location of air collar complete all as specified and as directed by engineer-in-charge. Note: (i) Quoted Rates shall be deemed to include volume control damper at the location of air collar. (ii) Contractor shall submit drawing of grills to GE through Engr-in-Charge for approval before placing order for procurement.
Supply, Installation, Testing and Balancing of Powder coated GI volume control damper at the location of air collar complete all as specified and directed by Engineer-in-charge.
Supply, Installation, Testing and Balancing of Powder coated Fire damper complete all as specified and directed by Engineer-in-charge.
Supply, Installation, Testing and Balancing of Powder coated actuator motor complete all as specified and directed by Engineer-in-charge.
Supply & Fixing in replacement of Triple pole and earth encolsure with a three pin and earth plug with socket complete with one triple pole MCB 32 Amp, 415 volt complete all as specified and directed by Engineer-in-charge.
Supply & Fixing in replacement of Triple pole and earth encolsure with a three pin and earth plug with socket complete with one triple pole MCB 63 Amp, 415 volt complete all as specified and directed by Engineer-in-charge.
Supply and fixing in replacement of miniature circuit breaker (MCB) of TPN 40 to 100 Amp, 415V, 10KA 'C' curve with and inclding connection tp DB, testing and commissioning complete all as specified and directed by Engineer-in-charge.
Supply, install, testing and commissioning of LT Panel board, Factory made, CPRI approved, outdoor type double door, suitable for floor mounting of size not less than 540 x 440 x 250 mm with locking arrangement, fabricated out of 2mm thick CRCA sheet, powder coated, dust/ water & vermin proof, suitable for 415 volts 3 phase 50 Hz with 4 No's heat shrinkable insulated copper bus bars of capacity not less than 1.5 times of incoming MCCB's including all MCCB connections, including framework having ISMC 75 for base frame, 750 mm long legs of 80mm x 10mm angle iron (04 Nos) grouted in PCC 1:2:4 including taking down old unserviceable panel, all as specified and directed by Engr-in-charge, complete with and including the following accessories :-
(a) Four pole MCCB 200 amps, 415 volts, 50 HZ, with adjustable thermal & magnetic release capacity 50 KA and Ics = 100% of Icu - 01 Nos - As INCOMING (b) Four pole MCCB 63 Amps, 415 volts, 50 HZ, with adjustable thermal & magnetic release capacity 25 KA and Ics = 100% of Icu - 04 Nos - As OUTGOING (c) Phase indicator lamp complete with copper control wiring with suitable size of CT complete - 01 (set of three). (d) Earthing terminals - 02 Nos. (e) Digital type LCD display voltmeter and ammeter of size 96mm x 96mm- 01 set. (f) Danger notice plate duly rivetted/ fixed on front door - 01 No
Supply & Fixing in replacement of Cable tray, stainless steel, perforated, of width 12 inch complete all as specified and as directed by Engineer-in-charge.
Supply and fixing in replacement of (2X2) GRID false ceiling board complete all as specified and directed by Engr-in-charge.
Supply, installation, testing and commissioning Canvas connection for ductable AC unit complete all as specified and as directed by Engineer-in-charge.
shivrefrigeration
Shree Karni Electrovision
M/S W R traders
Projenix Private Limited
UNITED ENGINEERING CORPORATION
HVAC Engineering Co
M/s BHUPINDRA ENGINEERING WORKS
M/S BALWINDER SINGH
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .