S/E of 33 KV, 1250A double break Line Isolator with Structure made of 125x65 mm. 13.1 Kg/M Channel at a height of 2.5 Mtr. above ground and 1 Mtr. below ground on a cement concrete pad of 75 mm. thick with 1:3:6 cement concrete foundation including excavation back filling, making plinth of required height & with required fabrication for bracing of M.S. Flat 50x6 mm. 2.4 Kg/m. and top of M.S. Angle 75x75x8 mm., 8.9 Kg/M as per drawing (for structure) Complete in all respects . Make: Jaipuria/Rama/UPPCL approved. as per direction of the E/I. (AOR)
Supply, Errection, Testing & Commissioning of 33 KV Outdoor VCB with required str, 1250A, 1500MVA, 25KA, Motorized 750MVA/1250Amp/ with transformer control & relay pannel including CT, PT with structure. complete in all respects Make: Crompton/ABB/Schneider as per specification and direction of E/I. (AOR)
S/E of Busbar Gantry Structure of 105 Lbs/Yard Rail pole 6.50 M long 5.2 Mtr. above the ground level and 1.30 Mtr. Below in 1:3:6 cement concrete foundation mounted on a stone pad of 300x300x75 mm. With M.S. angle 100x100x8mm (12.1Kg/M) mm suitable for Disc insulator including earth excavation, back filling, making plinth of required height and with required fabrication as per drawing complete in all respects as per direction of E/I.(AOR)
S/E of 33 KV, 1250A Bus Isolator with Structure made of 125x65 mm. 13.1 Kg/M Channel at a height of 2.5 Mtr. above ground and 1 Mtr. below ground on a cement concrete pad of 75 mm. Thick with 1:3:6 cement concrete foundation including excavation back filling, making plinth of required height & with required fabrication for bracing of M.S. Flat 50x6 mm. 2.4 Kg/M and top of M.S. Angle 75x75x8 mm., 8.9 Kg/M as per drawing (for structure) Complete in all respects Make: Jaipuria/Rama as per direction of the E/I. (AOR)
S/F of 33 KV fuse set out door type of Relco/Rama make complete including structure as per drawing. Complete in all respects.(AOR)
S/E of 33 KV Lightning Arrestors with Structure made of M.S. Channel 125x65 mm. 13.1Kg/M top of M.S. Angle 50x50x6 mm. 4.5 Kg/M Lightning Arrestors/Post Insulator are to be mounted on M.S. Plate of 200x150x8 mm. Height of structure is to be 3.5 Mtr. above ground and 1 Mtr. below ground on a 75 mm. thick cement concrete pad with 1:4:8 cement concrete foundation, making plinth of required height including all fabrication as per drawing complete in all respects Make: Elpro/Oblum/ W/S as per direction of E/I. (AOR)
Supply & fixing of 33 KV with 11KV 4 Nos Set B&S type strain Disc insulators 120KN E&M strength. as per drawing complete in all respects Make : Jaishree/BHEL/WS/RR as per direction of E/I.(AOR)
Supply & fixing of 33 KV tension fitting suitable for panther conductor and 120KN E&M 11KV disc insulator set of 4 complete in all respects as per direction of E/I. (AOR)
Construction of 33 KV transformer plinth as per drawing. with all material, labour and T&P etc. required for proper completion of the work as per specifications of UPPCL as per direction of E/I.(AOR)
Construction of boundary wall in brick work with cement mortar 1:6 (1 Cement : 6 Coarse Sand) for chain link including plaster in cement mortar 1:4 (1 Cement : 4 Coarse Sand) and finishing with water proofing cement paint complete as per attached drawing & complete in all respects as per direction of E/I.(AOR)
S/Fixing of 33 KV Post insulator 2x22KV of approved quality and make with all necessary material required for proper fixing including structure made of 125x65mm MS Channel (2.5Mtr above ground of 1 mtr below with ground with grouting 1:3:6 cement concrete including all labour, material, T&P etc. required for proper completion of the work. as per drawing. complete in all respects Make: Jai shree / BHEL as per direction of E/I (AOR)
Construction of control cable trench of required size 0.30x0.45 Mtr. bricks class designated-100 work including plastering etc. and covered with R.C.C. Slab (0.50x0.60 M) size complete with all material, labour and T&P etc. required for proper completion of work. complete in all respects. As per direction of E/I.(AOR)
S/Filling of 20 mm. stone grit in yard of size26x36mtr 75 mm. thick complete in all respects. (AOR)
S/F of 6" dia G.I. pipe B class for cable duly duly clamped with support by 1 no. with clamps for 20x3mm MS flat, bolt, nuts and washer required for proper completion of work (UPERC P-47)
Supply & laying of earth mat in the switch yard of the Sub-Station for all Electrical Equipments and structure by laying of M.S. Round bar of 32 mm. dia. in 750 mm. deep trenches and earth electrode 3.0 M. long of M.S. round bar 32 mm. dia 0.5 M below ground level. The work include welding/bending/flooring of M.S. round bar and connection all steel structure in switch yard with earth mat by means of M.S. Strip of size 50x6 mm. including all labour, materials, T&P etc. required for proper completion of the work as per details specification of UPPCL Complete in all respects as per direction of E/I. (AOR)
Painting of (Complete sub-station) Terminal Gantry, Lighting arrestor, Busbar Gantry, Line Isolator & Bus Isolator Structures, Post insulator, Fencing, Poles and other structure complete with two coats of Al. paint over red oxide. (AOR)
S/F of out door type 11KV fuse set Relco/Rama/Rastriya make with insulator Jai shree/BHEL make complete in all respects as per direction of E/I.(AOR)
(a) 2.5 Sq. mm. 2 Core Copper
(b) 2.5 Sq. mm. 4 Core Copper
(c) 2.5 Sq. mm. 10 Core Copper
Supply of Top MS Channel 100x50x2240mm as per design complete in all respects UPERC P-48
S/E of 125x65 mm. MS Channel (13.10 Kg/M) 1.5 M long fixing in control room for OCB/VCB pannel complete in all respects as per direction of E/I.(AOR)
Supply/Fixing of MS ladder of size 5 mtr long and 0.4m width with MS angle 40x40x6mm incl painting etc . complete in all respect as per direction of E/I.(AOR)
IS: 13947) IP-42/ maximum Permissible input volage ±10% of 230V AC, Electronic protection with auto reset against short circuit and overload , DC over voltage short circuit at charger output terminals, thyristor by fuseing with protection against over charging, efficiency of rectified >65% at rated load, Power factor 0.7 lag at D.C. Current 230V Input with ANC cooling type and Class F type insulation. For Battery : 240V/200AH Tubular type Battery Bank consisting 12 Cells of each 2V/200 AH dry & uncharged along with wooden stand & accessories (AOR)
a) 50 Sq.mm. 3½ Core
b) 25 Sq.mm. 3½ Core
Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. P.S. No. 1131
S/F of 6" dia G.I. pipe B class for cable duly duly clamped with support by 1 no. with clamps for 20x3mm MS flat, bolt, nuts and washer required for proper completion of work (UPERC P-47)
S/F of 6" dia G.I. pipe B class for cable duly duly clamped with support by 1 no. with clamps for 20x3mm MS flat, bolt, nuts and washer required for proper completion of work (UPERC P-47)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.15 MB
C.xls
Additional Documents • 0.04 MB
TD.pdf
Tender Documents • 1.43 MB
BOQ_1997515.xls
BOQ • 0.57 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .