EE(EnM)M-11
Apollo BPS Near Apollo Hospital Sarita Vihar Mathura Road New Delhi - 110076
Improvement of Power factor of A-Block Sewage Pumping Station Sarita Vihar under Okhla Constituency AC-54.
2022_DJB_233546_6
NIT No. 29/EE(EnM)M-11/2022-23
Open Tender
Miscellaneous Works
Works
30 days
EE(EnM)M-11
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Delhi Jal Board
₹13,800
30 Dec 2022
22 Dec 2022
28 Dec 2022
22 Dec 2022
28 Dec 2022
22 Dec 2022
(A) REPAIR/RENOVATION OF APFC PANEL: - Dismantling of defective component of APFC panels such as capacitors, relays, lights, contactors including dismantling of incoming and outgoing connection etc. as required at site.
Supply of Super Heavy duty Round type capacitors of various capacities rated at 440V, 50 Hz, 3 phase AC , complete with terminal cover and discharge device -make standard
Banking of capacitor units to form banks of suitable capacity by electrical interconnection with multistrand copper wires/Al. bus bars using necessary mountings and hardware , etc. as required at site.
Supply of microprocessor based APFC relay with digital display of power factor and other parameters for sensing power factor and giving phased impulses to contactor coils for switching ON-OFF required no. of capacitors on receiving signals from Control CT in the main line- Make Standard
Supply of MNX-50 triple pole capacitor duty contactors to replace defective contactors in APFC panel. , make L&T/Schneider/Havells
Supply of MNX-32 triple pole capacitor duty contactors to replace defective contactors in APFC panel. , make L&T/Schneider/Havells
Supply of triple pole MCB up to 63A to replace defective MCB in the capacitor panel- make L&T/Schneider/Havells
Supply of triple pole MCB up to 32A to replace defective MCB in the capacitor panel- make L&T/Schneider/Havells
Supply of LED indication light of various colors to replace defective lights in various stages of capacitor panel - Make : FTC/standard
Supply of digital Voltmeter0-500V to replace defective ammeter in the capacitor panel. Make : AE/L&T/Havells
Servicing of panels including complete dusting of all components, cleaning of contact point with CTC solution ,decarbonizing of various joints , tightening of all nut bolts , sleeving of live parts , alignment of doors to prevent ingress of moisture and vermin’s and touching of rusted parts of the panels etc. as required at site.
Installation of all above components in the existing capacitor banks with suitable fabrication work to accommodate new items in the existing enclosure / structure for alignment of components and ease of termination complete with hardware on the mounting structure and termination of existing cables with lugs, tapes etc. complete with earthling of the capacitor banks etc. as required at site.
Testing & commissioning of APFC panels as per required parameters including following :- (1) Meggering of all equipment’s for phase to phase, Phase to neutral and phase to earth (2) Programming of APFC relays for target power factor (3) All function tests (4) Monitoring of power factor
(B) S.I.T.C. OF FIXED CAPACITOR BANKS OF MOTORS :- Supply of LT capacitor panel for housing Capacitors for 2 nos. 150 HP & 2 nos. 60 HP motor, made out of 14/16 SWG sheet steel duly painted in Siemens grey shade and ventilated with louvers for cooling and consisting of following switchgears for switching and protection of capacitor banks -make STANDARD
Supply of TP aluminum bus bars links complete with mounting insulators , PVC heat shrinkable covering sleeves in red blue and yellow color as per standard practice and necessary hardware as required.
Installation of various components as described below in the panel with alignment of components for ease of servicing and operation , complete with hardware , mounting structure to hold the capacitor banks and other components in place etc. as required.
Complete power wiring for electrical interconnection of capacitor banks and MCCBs with multistrand copper wire of various capacities using lugs, tapes, cleats etc. as required and dressing of the wires with ties to hold the same in place for neatness and safety of the equipment as required
Supply of Heavy duty capacitor unit rated at 60kVAr, for 2 nos. 150 HP& 25kVAr 2 nos. Heavy Duty 60 HP motors rated at 440v , 3 phase, 50 Hz system complete with terminal cover , cable end entry, mounting structure and hardware etc. -make STANDARD
Banking of capacitor units to form banks of suitable rating by electrical interconnection using aluminum bus bars or copper multistrand cables with lugs , tapes etc. to form banks as per requirement of various capacitor banks
Supply of triple pole MCCB of 125 A capacity for operation and safety of individual capacitor bank - make L&T/Schneider/Havells
Supply of Red ON indication LED lights to indicate status of capacitor banks -make FTC/Teknik
Installation of complete panel on ground with civil work , if required, and necessary hardware to fix the panel on the ground , ensuring vertical alignment and double earthling of the panel with 25x5 mm GI strip and connecting the same to the main earthling system
Supply of 95 mm sq. 3.5 core aluminumarmored cable 1.1 kV grade-make Syntron/Paragon/Polycab/Any ISIS marked
Laying and termination of 95 mm sq. cable using necessary clamps, hardware, brass compression glands , lugs etc. as required at site
Charging of the panel after conducting megger test on capacitor bank , tightening of all nut-bolts, ensuring alignment of various components for ease of servicing , checking of earth resistance for safety of men and material.
(C) REPAIR OF STATIC CAPACITORS OF TRANSFORMER: - Checking of capacitors and dismantling of defective capacitors from static capacitor banks including dismantling of terminations, wirings, hardware, as required at site.
Supply of Heavy duty capacitors of various capacities rated at 440V, 50 Hz, 3 phase AC complete with terminal cover and discharge device for replacement of defective capacitors of static capacitor banks -make standard
Supply of digital Voltmeter0-500Vto replace defective ammeter in the capacitor panel. Make : AE/L&T/Havells
Banking of capacitor units to form banks of suitable capacity by electrical interconnection with multistrand copper wires/Al. bus bars using necessary mountings and hardware , etc. as required at site.
Installation & connection of capacitors as described above using necessary hardware, mounting arrangement and termination with multistrand copper wires, lugs, tapes etc. as required at site.
STANDARD CAPACITORS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .