| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.3 LAccepted-AOC GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹5.6 L+₹28,332 (5.34%)Rejected-Finance A 101 7 POLLOCK STREET KOLKATA KOLKATA WEST BENGAL 700001 | KOLKATA | WEST BENGAL | 700001 | L2 | Rejected-Finance HIGHER | |
| 3 | Rejected-Technical 205 LOTUS ENCLAVE PUNDAG ROAD ARGORA RANCHI JHARKHAND 834002 | RANCHI | JHARKHAND | 834002 | - | Rejected-Technical Not Qualified |
Tender Value
Refer Docs
EMD Value
₹12,193
Closing Date
27 Nov 2021, 2:30 pmClosed
The Executive Engineer (E), BSNL Electrical Divisi
O/o EE(E),ED-II,Kolkata,33 B.B.D. Bag South, Kolkata - 700001
SITC of addressable fire detection and alarm system in IAF NFS site at KALAIKUNDA, (Package-I and Package-II) in West Bengal
2021_BSNL_94862_2
102/TED-II/Kol/2021-22
Open Tender
Electrical Works
Item Rate
30 days
IAF STATION KALAIKUNDA
Please refer to Tender Document
4 documents required · 4 mandatory
₹590
Accounts Officer (Cash), BSNL, O/o the GMT, Cal SS
₹12,193
Yes
O/o EE(E),ED-II,Kolkata,33 B.B.D. Bag South, Kolka
29 Dec 2021
15 Nov 2021
29 Nov 2021
15 Nov 2021
27 Nov 2021
15 Nov 2021
15 Nov 2021 - 27 Nov 2021
26 Nov 2021
Amount
PART A
Main Fire Alarm Control Panel : SITC of Analogue addressable Micro Processor controlled, Standalone Main Fire Alarm Control Panel having 2 loop (2 Loop Card) (with minimum 126 devices capacity per loop card) capable of being networked to the central monitoring System to monitor and integrate with Access Control Panel, Detectors, LCP's, hooters, control modules, monitor modules Fault Isolation Modules, response indicators, fire/fault indicators, audio-visual signals, central processing units, complete with coloured TFT display, indicating LEDs, having multiple access levels, event history file in non-volatile memory (EEPROM) and colour screen as per the detailed specification, complete with PSU, Battery backup along with charger for 24 hours in non-alarm condition and 30 minutes in alarm condition etc. as required for each panel. [Make:- Apollo / Edward / Honeywell / Notifier / Cooper having listing with UL / FM / EN54 / VDS]
Addressable Multisensor Detector: Supply, Installation, Testing and Commissioning of Addressable Analogue MULTISENSOR / MULTICRITERIA type, photo cum thermal detectors (for smoke as well as heat) with solid state design, in-built fault isolator, indicating LEDs, single LED which covers 360º, mounting base, mounting bracket, base box, loop in & loop out gland as per requirement and detailed specifications attached. (Note :- Date of manufacturing of Detectors shall not be more than 6 months at time of supply also Make of Detectors and its base should be same) [Make:- Apollo / Edward / Honeywell / Notifier / Cooper having listing with UL/FM/EN54/VDS]
Addressable control modules: Supply Installation Testing and Commissioning of Addressable control module with in-built fault isolator complete with junction box etc. for control options for Hooters & for other control options like PA evacuation, Package AC trip etc. and hooters in case of emergency, etc., complete as required. [Make:- Apollo / Edward / Honeywell / Notifier / Cooper having listing with UL/FM/EN54/VDS]
Fault Isolator Module: Supply Installation Testing and Commissioning of Fault isolation module to electrically isolate different sections of detector loops (for every 20 detectors/devices) as per detailed specifications.etc complete as required. [Make:- Apollo / Edward / Honeywell / Notifier / Cooper having listing with UL / FM / EN54 / VDS]
Addressable Manual Call Point: Supply Installation Testing and Commissioning of addressable Manual call points with built-in fault isolator & NO/NC contacts slim type with Pull type/break glass with Reset Lock & Key arrangement suitable for addressable function, etc., complete as required. [Make:- Apollo / Edward / Honeywell / Notifier / Cooper having listing with UL / FM / EN54 / VDS]
Addressable Electronic Hooter Cum Strobe: Supply Installation Testing and Commissioning of addressable Hooter / sounder cum strobe having three distinct sounds with addressable relay module / Control module and strobe light with minimum 85 db from 1 Mtr distance, with built-in fault isolator, etc., complete as required. This strobe may be able to work as PA system sounders. [Make:- Apollo / Edward / Honeywell / Notifier / Cooper having listing with UL / FM / EN54 / VDS]
Response Indicators: Supply, Installation, Testing and Commissioning of Response Indicator having twin LEDs for mounting on false ceiling / wall / at the entries of the cabin for indicating the operation of detectors in the above false ceiling / below false flooring detectors, etc., as required. [Make:- Apollo / Edward / Honeywell / Notifier / Cooper having listing with UL / FM / EN54 / VDS]
Exit Signage : Supply Installation Testing and Commissioning of LED Emergency Exit signage with at least 3 hour battery backup etc. as required.
Copper Cable: Supplying and laying 2 x 1.5 sq. mm. FRLS PVC insulated PVC sheathed armoured single / multi strand copper conductor cable on surface as required. [Make: ISI marked]
CO2 Fire Extinguishers: Supplying and fixing wall mounted CO2 type fire extinguisher of 4.5 kg capacity complete with Valve, Bend with ABS horn, handle, wall Fixing bracket, discharge hose and including initial charge as required confirming to IS : 2878. (both body and valve shall be ISI marked) [Make:- Fireshield or similar superior make]
Fitech Engineers Pvt. Ltd.
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .