Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1st₹88.9 CrAccepted-AOC | ₹88.9 Cr Quoted ₹93.3 Cr | 1st | Accepted-AOC 1st Lowest hence Accepted |
| 2 | 2nd₹95.6 CrAccepted-AOC | ₹95.6 Cr | 2nd | Accepted-AOC 2nd Lowest hence Rejected |
Tender Value
₹84.9 Cr
EMD Value
₹42.4 L
Closing Date
4 Oct 2024, 6:00 pmClosed
Office of the Executive Engineer, P.W. Division, A
Office of the Executive Engineer, P.W. Division, Alibag
200 Bed General Hospital, Alibag Tt. Alibag Dist. Construction Of Said hospital building by Upgrading Raigad to 300 Beds
2024_PWR_1088336_1
Notice No. 21 for 2024-25/ AD/Tender/ 4804/2024
Open Tender
Civil Works - Buildings
730 days
Alibag
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
₹42.4 L
Office of the Chief Engineer, (P.W.) Region, Konka
10 Mar 2025
20 Sept 2024
7 Oct 2024
20 Sept 2024
4 Oct 2024
20 Sept 2024
24 Sept 2024
Amount
Civil Works - Trimming of grass, shurbs and weeds from the shoulders/berms and disposing off the same to suitable locations etc. complete Ground Floor Ground Floor
Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removing the excavated material up to a distance of 50 m. beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5 m.) By Mechanical Means Ground Floor
Excavation for foundation in earth, soils of all types, sand,gravel and soft murum,including removing the excavated material upto a distance of 50 metres beyond thebuilding area and stacking and spreading as directed, dewatering, preparing the bedfor the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5m to 3.0m) By Manual Means Ground Floor
Excavation for foundation in earth, soils of all types, sand, gravel, soft murum including shoring and strutting, dewatering as necessary and disposing off excavated stuff as directed etc. complete. ( By /manaual Means ) Ground Floor a) Upto 1.50m lift Normal Rate b) 1.50m to 3.00m lift, Add 10% c) 3.00m to 4.50m lift, Add 20% d) 4.50m to 6.0m lift, Add 30%
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) by treating the bottom surface and sides of excavation at the rate of 5 litres of emulsion concentrate of 1.0 percent of chlorophyrifos per square meter of surface area covering 10 years guarantee on bond paper Ground Floor
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) treatment by treating the backfill in immediate contact with foundation at the rate of 5 litres of emulsion concentrate of 1.0 percent of clorophyrifos per One Square Metre of vertical surface area covering 10 years guarantee on bond paper. Ground Floor
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) by treating the top surface of plinth filling at the rate of 5 litres of emulsion concentrate at 1.0 percent of clorophyrifos per One Square Metre of surface area covering ten years guarantee on bond paper Ground Floor
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-I) to the soil along the external face of building by punching holes of 1.2 of 1.5 C.M. diametre about 30 -60 cm deep at 15 cm c/c as close to the wall as possible and to inject 0.5 percent of aldrin or clorophyrifos at the rate of 7.5 litres per hole and sealing the same with proper filling and covering 10 years guarantee on bond paper. Ground Floor
Filling in plinth and floors with approved excavated material in 15cm. to 20cm. layers including watering and compacting etc. complete. Ground Floor
Filling in plinth and floors with contractors material/brought from outside and approved by Engineer incharge in layers of 15 cm to 20 cm including watering and compaction etc. complete Ground Floor
Providing dry/ trap/ granite/ quartzite/ gneiss rubble stone soling 15 cm to 20 cm thick including hand packing and compacting etc. complete Ground Floor
Empty boring for 725 to 1050 mm dia. bored R.C.C. cast in situ piles including withdrawal of shell, removal of earth to a distance of 50 metres etc. complete. Spec :(As directed by Engineer in Charge) Ground Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M15 of trap/ granite/quartzite/gneiss metal for foundation and bedding / steps including steel centering, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface, only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.),with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Ground Floor
Providing and laying cast in situ / Ready Mix Cement Concrete M-30 for bored piles each of load capacity and as per design and of 900 mm diameter or as directed placed through steel shells sunk to the required epth through all strata except rock excluding provision of reinforcement as per detailed drawings and design approved by the Engineer-in- charge includingplacing with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) by tremie arrangements, compaction of concrete including chipping and dressing and withdrawal of shell etc. complete. (Excluding steel reinforcement) Ground Floor
Providing and laying cast in situ / Ready Mix Cement Concrete M-30 for bored piles each of load capacity and as per design and of 750 mm diameter or as directed placed through steel shells sunk to the required depth through all strata except rock excluding provision of reinforcement as per detailed drawings and design approved by the Engineer-in- charge includingplacing with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) by tremie arrangements, compaction of concrete including chipping and dressing and withdrawal of shell etc. complete. (Excluding steel reinforcement) Ground Floor
Chiseling through pile shells in hard strata like boulders, soft and hard rocks Beyond 550 mm and upto and inclusive of 750 mm dia. including removing and stacking the loose materials etc. complete and disposing of the unserviceable materials outside complete. Ground Floor
Chiseling through pile shells in hard strata like boulders, soft and hard rocks Beyond 750 mm and upto and inclusive of 900 mm dia including removing and stacking the loose materials etc. complete and disposing of the unserviceable materials outside complete. Ground Floor
Providing placing and Driving in position 6 millimeter mild steel liner for R.C.C. Piles upto required depth with 12mm thick mild steel cutting edge of 0.50m length at bottom including fabricating cutting the mild steel sheet to required diameter and shape ,welding the joints and driving with the help of required machineries including all materials labours and lifts etc. complete as directed by the Engineer in charge. Upto 3.00 meter deep liner Ground Floor
Providing placing and Driving in position 6 millimeter mild steel liner for R.C.C. Piles upto required depth with 12mm thick mild steel cutting edge of 0.50m length at bottom including fabricating cutting the mild steel sheet to required diameter and shape ,welding the joints and driving with the help of required machineries including all materials labours and lifts etc. complete as directed by the Engineer in charge. Spec :(As directed by Engineer in Charge From 3.00 to 9.50 meter deep liner Ground Floor
Carrying out load test for 1.5 times the proposed safe working load on the pile in driven position above 650 mm and upto 750 mm diameter including construction of test cap, use of accessories and instruments including providing graphs as per I.S. code or Std.Specifications and dismantling the test cap after testing and cleaning the site complete. Ground Floor
Carrying out load test for 1.5 times the proposed safe working load on the pile in driven position above 825 mm and upto 900 mm diameter including construction of test cap, use of accessories and instruments including providing graphs as per I.S. code or Std.Specifications and dismantling the test cap after testing and cleaning the site complete Ground Floor
Providing bentonite slurry process for various diameter of piles vide Item Nos 1 (i to xxiv) above. Spec : (As directed by Engineer in Charge) Ground Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap metal for R.C.C. pile caps as per detailed designs and drawings, including bailing out water manually, centering, formwork, laying/ pumping, compacting, finishing and curing etc. with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) complete (Excluding steel reinforcement) Ground Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-35 of trap / granite/quartzite/ gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. columns as per detailed designs and drawing or as directed including Steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Ground Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-35 of trap / granite/quartzite/ gneiss metal for R.C.C. columns as per detailed designs and drawing or as directed including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC without SCAD Aenabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate(Crushed sand VSI Grade) Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
ISixth Floor
Seventh Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mixcement concrete M-35 of trap / granite /quartzite/ gneiss metal for R.C.C. beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc.complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-35 of trap/ granite/ quartzite/ gneiss metal for R.C.C. slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-20 of trap/ granite/ quartzite/ gneiss metal for R.C.C.coping to plinth or parapet and sill of doors and windows moulded as per detailed drawings or chamfered as approved by the Engineer including steel centering, formwork, cover blocks, laying/pumping, compacting , curing , finishing and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap / quartzite/granite /gneiss metal for R.C.C. Waist slab, and steps of staircases as per detailed design and drawings or as directed including steel centering, plywood/ steel formwork, steel props, laying/pumping, compaction, finishing uneven and honeycombed surface with C.M. 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding einforcement, including cover block).(Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc.) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mixcement concrete M-25 of trap/ granite/ quartzite/ gneiss metal for R.C.C. chajja as per detailed design and drawings includingsteel centering, formwork, cover blocks, laying/pumping, compacting and roughening the surface if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc.complete. With fine aggregate (Crushed sand VSI Grade) Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing in position HCRM / CRS (Corrosion Resistant Steel) bar reinforcement of various diameters for R.C.C. pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches etc. as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing fly ash brick masonry with conventional / I.S. type fly ash bricks in C.M. 1:6 in foundation and plinth including bailing out water manually striking joints, racking out joints watering and scaffolding etc. complete. Ground Floor
Providing Autoclaved areated concrete block masonry of approved manufacture confirming to IS 2185 Part III 1984 of size 600 mm x 200mm and thickness 100,150, 200 or 250 mm using Ready to use BLOCK JOINT MORTAR1:6 in foundations and plinth of inner walls / external walls including bailing out water, striking joints on unexposed faces, racking out joints on exposed faces and watering complete. With Prior Approval of Concerned S.E. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing internal cement plaster 12mm thick in single coat in cement mortar 1:4 without neeru finish to concrete or brick surfaces, in all positions including scaffolding and curing etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and applying plaster / wall punning with plaster of paris ( with plaster of paris material) in 10 to 13 millimeter thickness to previously plastered surface / or on newly brick surface ( Excluding rough cast plaster ) in all position including preparing and Finishing the surface scaffolding etc.complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and applying plaster with plaster of paris in 6mm thickness to previously plaster surface in all position including preparing the surface scaffolding etc. complete.As directed by Engineer in Charge. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing sand faced plaster externally in cement mortar using approved screened sand, in all positions including base coat of 15 mm thick in cement mortar 1:4 using waterproofing compound at 1Kilogramper cement bag curing the same for not less than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 6 to 8 mm thick in cement mortar 1:4 finishing the surface by taking out grains and curing for fourteen days scaffolding etc.complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing patti/ band 100mm wide on plastered surface 12 mm to 15 mm thick in C.M. 1:3 line and level including neat finishing scaffolding curing etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Dry wall cladding with clay tile; Designing, supplying and fixing of Clay tile of Wienerberger (Red Series or Grey Series) or Equivalent with suitable size and thickness not less than 20 mm as per manufacturer with approved colour and pattern with composition of finest powdered clay and colour mixtures. The clay tile shall be fixed on the suitable farming system by using continuous aluminium profiled section as per manufacturer with suitable size and spacing to withstand the structural design criteria specifled in the technical specification by using necessary HDG brackets, SS316 grade anchor bolts etc as per manufacturer specification. Cladding joints should be with open groove system. with prior approval of concerned Superitending Engineer. Ground Floor
Providing and applying laying Aggregate plaster in granite / marble stones, as decorative finish to give granite / marble like appearance to concrete, brick or block surfaces in all position including preparation of surface smoothly, evenly by racking of joints in case of Brick or block work including backing layer of 12 mm thick with cement mortar 1:3 with 2% integral cement water proofing compound, roughening for wall keying hardening and drying the surface for a minimum five days gaps including second coat of cement lime mortar into a proportion 1:4 preparing the surface for three coat of marble finish plaster giving a thin coat of white cement and two parts of course calcite powder, applying the mortar with steel float on the surface in proper evenness applying at coat of white cement and lime to set a smooth finish then applying a thin coat of slurry made of white cement and black oxide colour in required proportion by the steel float to get black streaks on the surface and curing the surface for two days including all materials and labour etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and applying Texture plaster with finishing with texture material of approved make in 3 to 4 millimeter thickness on previously plastered surface, including Plaster Groove 6mm thickness or Tape Grooves 35 to 45 mm thickness or as required, in all position including preparing the surface, scaffolding etc. complete. Ground Floor
First Floor
Providing and Fixing GRC Grill, 20 to 25 mm thick as per approved design and drawing, including preparing of mould as per design, lift lead, painting with 3 coats. Of approved paint, square pipe & 35 x 50 mm size section as per design including scaffolding ets. Complete Approved Rate Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing fine cement finish 1.5 mm thick over green plaster surface including scaffolding curing etc. complete. Ground Floor
Terrace Floor)
Providing and fixing chicken mesh of 22 gauge, with about 30 cm. width at the junction of R.C.C members and brick work, of approved quality including fixing mesh in position by necessary drilling in concrete /B.B.masonry and or tying by binding wire etc. complete.Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and laying of filter media with granular materials/ stone crushed aggregates satisfying the requirements laid down in clause 2504.2.2 of MoRTH specifications to a thickness of not less than 600 mm with smaller size towards the soil and bigger size towards the wall and provided over the entire surface behind abutment, wing wall and return wall to the full height compacted to a firm condition as per drawing and technical specifications etc. complete.MORT and H 2200 &-710.1.4 of iRC 78 Ground Floor
Providing and fixing 20 to 25 mm thick rough shahabad box type waterproofing treatment to vertical outside faces of Reinforced Cement concrete walls of basement or underground floor including filling the gap of 25 mm between rough shahabad and R.C.C. walls with cement grout mixed with water proofing liquid Algae proof or other alike with one tile lift method, brushing the joints horizontally with cement slurry mixed with water proofing liquid for width 30 to 35 mm and sloping coping over topmost tile with cement mortar 1:3, butting the bottom most with Cement concrete 1:2:4 mixed with water proofing liquid, curing, with 7 years guarantee on court fee stamp of Rs.100/- with ponding test etc complete. (excluding Cement concrete 1:3:6 base concrete) Ground Floor
Providing and fixing 20 to 25 mm thick rough shahabad box type waterproofing for basement or underground floor on a base of Cement concrete 1:3:6, including sub base of 2.50 centimeter thick Cement mortar 1:3 with conceal, secrete (RMW), Algae proof or other alike waterproofing liquids, raking of joints upto 35 mm depth, filling the joints with 6 mm size crushed metal, hand grouting with cement slurry, curing and cleaning, with 7 years guarantee on court fee stamp of Rs. 100/- with ponding test etc complete. (excluding Cement concrete 1:3:6 base concrete )Bd.J.2 Page One Number 355 Ground Floor
Providing waterproofing in W.C. and bath including brick bat coba in all position including providing and laying 12mm bedding in cement mortor 1:3 on vergin concrete slab with waterproofing compound @ 1Kilogram/per bag of cement laying brick bat coba of required thickness in cm 1:5 with waterproofing compound 1 Kilogram/bag of cement grouting and finishing the top layer with 20mm thick brick bedding in cm mortor 1:3 with waterproofing compound 1 Kilogram/per bag of cement and testing the treated portion for 48 hours by pond test and covering ten years' guarantee on requisite stamp paper including curing etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing water proof bedding for flooring of Bath and WC 25 mm thick in C.M. 1:3 including using approved water proofing compound in specified proportion as per manufacturers specifications for per bag of cement including leveling, curing and covering 10 years guarantee on court fee stamp paper of Rs.500/- including ponding test etc. complete.As directed by Engineer in charge. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing cement based water proofing treatment to terraces (Indian water proofing or alike) with brick bats laid in required slope to drain the water for any span after cleaning the base surface. Applying a coat of cement slurry admixed with approved water proofing compound and laying the brick bats on bottom layer in C.M.1:5 admixed with approved water proofing compound filling up to half depth of brick bats, curing this layer for 3 days, applying cement slurry over this layer joints of brick bats with C.M.1:3 admixed with approved water proofing compound and finally top finishing with average 20 mm. thick layers of same mortar added with jute fiber at 1Kilogramper bag including finishing the surface smooth with cement slurry admixed with approved water proofing compound. Marking finished surface with false squares of 300mm x 300 mm. making the junctions at the parapet rounded and tapered top for required height, with drip mould at the junction of plaster and parapet and curing and covering 10 years Guarantee against leakproofness on Court fee stamp paper of Rs. 500/- including ponding test etc. complete. Ground Floor
Seventh Floor
Eigh Floor
Providing and fixing in position, Double shuttered aluminium extruded powder coated openable door of specified size with aluminium door frame of powder coated section 101.60 x 44.75mm , 3.18 mm thick and shutter comprising of powder coated section having bottom and lock rail of size 150 mm x 44.5 mm x 3.00 mm thick top rails 47.62 x 44.45 mm x 3.00 mm thick , vertical style 47.62 x 44.45 mm, 3.00 mm thick and for shutter plain glass panes 5 mm thick for top panels and 12mm thick both side laminated phenol bonded particle board panels for bottom panels etc. , I.S.I. mark , heavy duty, Hydraulic floor spring of 150Kilogramcapacity , having heavy duty concealed lock, necessary beading, glazing clips, PVC gaskets, 250mm length aluminium tower bolts, 150mm dia. pad handle, etc. as per detailed design and drawing or as directed by engineer in charge including all materials , labours, and equipment etc.complete Ground Floor
Providing & fixing factory-made Single leaf 2 hour fire rated door as per IS 3614 Part 2 & BS 476 Part 20 & 22, tested to UL 10 C and conforming to NFPA 80 , tested at NTL /CBRI/ARAI of Plain Steel finish type with a.) Frame of size 143x58 mm and thickness of 1.6 mm thick skin pass galvanized iron sheet (Conform to IS 277 ) formed to single or double rebate profile b.) Shutter of 46 mm thickness and constructed from 1.2 mm thick skin pas galvanized iron sheet (Conform to IS 277) infill Rockwool / Mineral wool/ Honey comb craft paper c.) Vision glass of 5mm thick clear/wired glass Circular or Rectangular d.) Finish : Primed with zinc phosphate stoving primer and finished with Polyurethane aliphatic grade or epoxy paint as required of thickness 60 micron e.) Accessories : Min 8 Anchor fastener of HILTI make, min 3 SS Ball Bearing Butt Hinges, Mortise sash lock with lever handle, Mortise dead bolt , Mortise latch , Door closer , Panic bar and external trim lock and Flush bolts complete.Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing fiber glass reinforced polyster door shutter 35 mm thick as per IS 14856 (2000) (Reaffirmed 2006) without ventilator including chromium plated fixtures and fastening with chromium plated handles on both sides, etc complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing solid core flush door shutter in single leaf 32 mm thick decorative type of exterior grade as per detailed drawings approved face veneers 3 mm thick on both faces or as directed, all necessary beads, mouldings and lipping, wrought iron hold fasts, chromium plated fixtures and fastenings, with brass mortise lock, chromium plated handles on both sides, and finishing with French Polish etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing solid core flush door shutter in double leaf 32 mm thick decorative type of exterior grade as per detailed drawings approved face veneers 3 mm thick on both faces or as directed, all necessary beads, mouldings and lipping, wrought iron hold fasts, chromium plated fixtures and fastenings, with brass mortise lock, chromium plated handles on both sides, and finishing with French Polish etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
c) Vision Panel: 1 HR rated E Class clear high stress fire rated glass is pre fabricated strategically inside the shutter structure with 10 mm inside the shutter on all sides with U- glazing. An additional insulated powdercoated 'Z' channel of 16 swg MS sheet to be fixed for reinforcement of the joints. With clear fire resistant glass panes 11mm thick having minimum 120 minutes fire Description Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing frame with / without ventilator of size as specified with Country cut teak wood for doors and windows including chamfering, rounding, rebating, iron holdfast of size 300mm x 40mm x 5mm with oil painting, etc. complete Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing collapsible steel gate in one / two leaves with hot rolled vertical channels of 18 x 9 x 3 mm minimum size, crossings of M.S. flats of size 18 x 5 mm T or E section for runner of minimum 40 x 6 mm size for flange, M.S. flat for top runner of minimum size 40 x 12 mm with roller wheels confirming to grade F.G. 150 fitted with snap headed rivets of minimum size 6 mm max. spacing of vertical channels be 100 mm enclosed gate position and clear space of 150 mm between two sets of crossings with hold fasts, stoppers, spaces, handles, locking arrangement and one coat of red lead primer and oil painting etc. complete. (I.S. 105211983). Ground Floor
Providing and fixing of factory made uPVC Sliding window & door (White Colour) complete of 3 Track with Mesh-2 Glass Sash + 1 Mesh Sash (Each sash shall be half of width of window) (Big Series) Window frame of size 122 x 54 mm & Sash of size 64 x 47 mm, comprising uPVC multi-chambered frame having in-built uPVC roller track on top and uPVC sash with wall thickness of 2.3mm (+-0.2 mm), duly reinforced with G.I. section 1.5 mm, wherever required. uPVC window & door profile shall be made in India & shall conform to BS EN 12608 and other standards as mentioned below: S.No. Name of the test Test Method Specified Parameter 1 Tensile Impact Strength ISO 8256 - more than 700Kj/m2 2 Vicat Softening Temperature EN ISO – 306 Shall not be < 750 3 Charpy Impact Strength EN ISO – 179-2 Shall not be < 20KJ/m2 4 Flexural Modulus Elasticity EN ISO – 178 Shall not be < 2200 N/mm2 5 Mean Breaking Stress for welded corner (a) For the tensile bending test EN – 514 Shall not be < 25 N/mm2 (b) For the compression bending test Shall not be < 30N/mm2 6 Heat Reversion Test IS:4985-2000 Shall not be > 2.0 % 7 Surface Spread of flame BS : 476 - Part 7 Classification 1 8 Ignitability Evaluation BS : 476 - Part 5 'P' Not easily ignitable 9 Tensile modulus ASTM D 638 Shall not be < 35 MPa 10 Shear Modulus ASTM D 732 Shall not be < 220 MPa 11 Tensile Strength EN ISO 527 Shall not be < 30 MPa All corners of frame and sash will be fusion welded. After placing 5 mm Float Annealed glass in the sash, uPVC glazing bead, interlock, EPDM / TPE gasket, brush shall be provided including touch lock and rollers & proper drainage system shall be provided. Window / Door will be fixed to the wall with 100mm long and 8mm dia. Fasteners and complete in all respect as per direction of Engineer-In-Charge. uPVC Window and Door Profiles are warranted for a period of ten (10) years against non-uniform discoloration, wrapping and rotting under general use. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing of factory made uPVC Sliding window & door (White Colour) complete of 2 Track 2 / 4 Sash (Big Series) window frame of size 67 x 54 mm & Sash of size 64 x 47 mm, comprising uPVC multi-chambered frame having in-built uPVC roller track on top and uPVC sash with wall thickness of 2.3mm (+-0.2 mm), duly reinforced with G.I. section 1.5 mm, wherever required. uPVC window & door profile shall be made in India & shall conform to BS EN 12608 and other standards as mentioned below: S.No. Name of the test Test Method Specified Parameter 1 Tensile Impact Strength ISO 8256 - more than 700Kj/m2 2 Vicat Softening Temperature EN ISO – 306 Shall not be < 750C 3 Charpy Impact Strength EN ISO – 179-2 Shall not be < 20KJ/m2 4 Flexural Modulus Elasticity EN ISO – 178 Shall not be < 2200 N/mm2 5 Mean Breaking Stress for welded corner (a) For the tensile bending test EN – 514 Shall not be < 25 N/mm2 (b) For the compression bending test Shall not be < 30N/mm2 6 Heat Reversion Test IS:4985-2000 Shall not be > 2.0 % 7 Surface Spread of flame BS : 476 - Part 7 Classification 1 8 Ignitability Evaluation BS : 476 - Part 5 'P' Not easily ignitable 9 Tensile modulus ASTM D 638 Shall not be < 35 MPa 10 Shear Modulus ASTM D 732 Shall not be < 220 MPa 11 Tensile Strength EN ISO 527 Shall not be < 30 MPa All corners of frame and sash will be fusion welded. After placing 5 mm Float Annealed glass in the sash, uPVC glazing bead, interlock, EPDM / TPE gasket, brush shall be provided including touch lock and rollers & proper drainage system shall be provided. Window / Door will be fixed to the wall with 100mm long and 8mm dia. Fasteners and complete in all respect as per direction of Engineer-In-Charge. uPVC Window and Door Profiles are warranted for a period of ten (10) years against non-uniform discoloration, wrapping and rotting under general use. Ground Floor
First Floor
Providing and fixing of factory made uPVC Fixed Window (Big Series) frame of size 67 x 62 mm & Mullion (if required) of size 67 x 78 mm. (White Colour) comprising uPVC multi-chambered frame, Sash, & Mullion with wall thickness of 2.3mm (+-0.2 mm ), duly reinforced with G.I. section 1.5 mm, wherever required. uPVC window & door profile shall be made in India & shall conform to BS EN 12608 and other standards as mentioned below: S.No. Name of the test Test Method Specified Parameter 1 Tensile Impact Strength ISO 8256 - more than 700Kj/m2 2 Vicat Softening Temperature EN ISO – 306 Shall not be < 750C 3 Charpy Impact Strength EN ISO – 179-2 Shall not be < 20KJ/m2 4 Flexural Modulus Elasticity EN ISO – 178 Shall not be < 2200 N/mm2 5 Mean Breaking Stress for welded corner (a) For the tensile bending test EN – 514 Shall not be < 25 N/mm2 (b) For the compression bending test Shall not be < 30N/mm2 6 Heat Reversion Test IS:4985-2000 Shall not be > 2.0 % 7 Surface Spread of flame BS : 476 - Part 7 Classification 1 8 Ignitability Evaluation BS : 476 - Part 5 'P' Not easily ignitable 9 Tensile modulus ASTM D 638 Shall not be < 35 MPa 10 Shear Modulus ASTM D 732 Shall not be < 220 MPa 11 Tensile Strength EN ISO 527 Shall not be < 30 MPa. All corners of frame and sash will be fusion welded. Mullion shall be welded / screwed. EPDM / TPE Gasket shall be provided in all frame, sash & mullion, wherever necessary.Thereafter, 5 mm Float Annealed glass shall be provided in the sash with the help of uPVC glazing bead and hardware, i.e., friction hinge & single point handle (in window) & 3D Hinges & Multipoint Lock (in door) shall be provided. Window / Door shall be fixed to the wall with 100mm long and 8mm dia. Fasteners and complete in all respect as per direction of Engineer-In-Charge. uPVC Window and Door Profiles are warranted for a period of ten (10) years against non-uniform discoloration, wrapping and rotting under general use. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing of factory made uPVC Louver window (White Colour) comprising of uPVC multi-chambered with wall thickness of 2.3mm (+-0.2 mm ), duly reinforced with 1.5 mm thick G. I. Section. uPVC window & door profile shall be made in India & shall conform to BS EN 12608 and other standards as mentioned below: S.No. Name of the test Test Method Specifie Parameter 1 Tensile Impact Strength ISO 8256 - more than 700Kj/m2 2 Vicat 2 Softening Temperature EN ISO – 306 Shall not be < 750C 3 Charpy Impact Strength EN ISO – 179-2 Shall not be < 20KJ/m2 4 Flexural Modulus Elasticity EN ISO – 178 Shall not be < 2200 N/mm2 5 Mean Breaking Stress for welded corner (a) For the tensile bending test EN – 514 Shall not be < 25 N/mm2 (b) For the compression bending test Shall not be < 30N/mm2 6 Heat Reversion Test IS:4985-2000 Shall not be > 2.0 % 7 Surface Spread of flame BS : 476 - Part 7 Classification 1 8 Ignitability Evaluation BS : 476 - Part 5 'P' Not easily ignitable 9 Tensile modulus ASTM D 638 Shall not be < 35 MPa 10 Shear Modulus ASTM D 732 Shall not be < 220 MPa 11 Tensile Strength EN ISO 527 Shall not be < 30 MPa. All corners of frame shall be fusion welded. Both vertical sides of the frame, adjustable louver mechanism having one lever or fixed louver bracket shall be fitted with the of 4 mm Frosted Annealed glass. Window will be fixed to the wall with 100mm long and 8mm dia. Fasteners and complete in all respect as per direction of Engineer-In-Charge. uPVC Window and Door Profiles are warranted for a period of ten (10) years against nonuniform discoloration,wrapping and rotting under general use. a.Louver Window (Big Series) frame of size 67 x 62 mm & Mullion (if required) of size 67 x 78 mm. Ground Floor
First Floor
Second Floor
Third Floor
Forth floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing mild steel grill work for windows, ventilators, etc. 15 Kilogram/ One Square Metre as per drawing including fixtures necessary welding and painting with one coat of anticorrosive paint and two coats of oil painting complete.Ground Floor
First Floor
Second Floor
Third Floor
Fourth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Supply & Fixing of Rock / Stone Finished outdoor vitrified flooring Tiles 16 mm thick and required width wide in plain pattern including Cement float, filling joints, with neat cement slurry, Natural sand, curing and cleaning complete. with prior approval of concerned Superitending Engineer. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and laying machine cut machine Polished Kota stone flooring 25mm to 30mm thick and required width in plain/ diamond pattern on bed of 1:6 C. M. including cement float, filling joints with neat cement slurry, curing, polishing and cleaning etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing Mirror polishing to Kota Stone including using all necessary stones and equipments cleaning, washing etc. complete. For Flooring Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and laying ceramic tiles having size 30 cm. x 60 cm. confirming to corresponding I.S. for dado and skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white/ colour cement slurry cleaning curing etc. complete. Upper Ground Floor
First Floor
Second Floor
Providing and laying matt finish ceramic tiles of having size 30 cm x 30 cm confirming to I.S.15622/2006 (group D II-A) and 7 to 8 mm thick for flooring in required position laid on a bed of 1:4 cement mortar including cement float, filling joint with white/colour cement slurry cleaning curing etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and laying telephone black / Amba White / Cadburybrown / Ruby red / Ocean Brown granite stone of 18 to 20 mm thick for door frame/ dado/ window boxing etc. On C.M. 1:6 including filling joints with polymer base filler nosing/moulding the sharp edges wherever necessary, curing, etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and laying ceramic tiles of having size 30 cm. x 30 cm. and confirming to corresponding I.S. for dado and skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including filling with white/ colour cement slurry cleaning curing etc. complete Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and laying Antiskid Ceramic tiles of approved quality of size 30 cm x 30 cm and confirming to IS 15622-2006 (Group-B IIA) for antiskid flooring in required position laid on a bed of 1:4 cement mortar including cement float, filling joint with cement slurry cleaning curing etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and laying vitrified rustic matt stone finish tiles having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10mm thickness and confirming to IS. 15622-2006 (Group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and cleaning etc. complete. Terrace Floor
Providing and laying vitrified rustic matt stone finish tiles having size 590 mm to 605 mm x 590 mm to 605 mm to 8 to 10mm thickness and confirming to IS. 15622-2006 (Group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including neat cement float, filling joints, curing and cleaning. etc. complete Terrace Floor
Providing and laying in situ cement concrete M20 with tremix treatment for 100 mm thickness for flooring with groove cutting of 4mm wide and 20mm deep with necessary refilling with bitumen etc. complete Ground Floor
Providing and laying in situ cement concrete M -30 with tremix treatment for 200 mm thickness for Concrete Road is including laying plastic sheet for 125 micron thickness with groove cutting of 4 mm wide and 20 mm deep with necessary refilling with bitumen ( excluding reinforcement) with coarse and fine aggregate ( natural sand/ VSI grade finely washed crushed sand) etc. complete Upper Ground Floor
Providing and laying in position flooring of telephone black / Amba White / Cat bary brown / Ruby red / Ocean Brown granite stone of approved shade and size 18 mm to 20 mm thick on bed 1:6 cement mortar including cement floats striking joints, pointing in C.M. 1:3 curing and cleaning etc. complete. Ground Floor
Providing and fixing machine cut machine polished 18 mm to 20 mm thick telephone black / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone for treads and risers of steps and staircases of approved colour and shade with full moulding and three grooved line for the treads on bed of 1:4 Cement mortar including float filling joints with neat cement slurry curing polishing and cleaning etc. complete. Upper Ground Floor
Supply & Fixing of Rock/ Stone Finished Full Body Vitrifid Steptiles with thick Bullnose for Ready to install Treads and Risers, 16 mm thick and of required width in plain pattern including Cement float, filling joints, with neat cement slurry, Natural sand, curing and cleaning complete. with prior approval of concerned Superitending Engineer. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Supply & Fixing of Full Body Vitrifid Steptiles Ready to install Treads and Risers 16 mm thick, required width and required finish in plain pattern including Cement float, filling joints, with neat cement slurry, Natural sand, curing and cleaning etc complete. with prior approval of concerned Superitending Engineer. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and laying vitrified stone effect finish tiles having size 590 to 605 mm x 590 to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622-2006 (Group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including required position laid on a bed of 1:4 cement mortarincluding neat cement float, filling joints, curign and cleaning etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing machine cut mirror polished 18 mm to 20 mm thick telephone black granite / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone partition with full moulding the edges etc. complete . Both side polish Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and constructing granite kitchen platform with fixing of stainless steel sink 600 mm x 450 mm size as per detailed drawing including vertical both side polished kadappah stone 25 to 30 mm thick supports with kadappah top 35 to 40 mm thick and polished granite 16 to 20 mm top with side strips of granite at front and both sides of platform raised with two vertical granite supports 15 cm height and top granite of 75 x 40 cm including cutting, opening for sink of required size in kadappah as well as granite etc. complete. (Platform top size 5.00 m x 0.60 m and height is 0.75 m) Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing 1.5 mm thick polyvenyl venyl chloride flooring including leveling the base with white cement including pasting with appropriate material cleaning the surface etc. complete Ground Floor
First Floor
Second Floor
Providing leather finished polishing to Granite Stone slab by continuous grinding in 4 coats of different bits to receive rough and matt finish including buffing process before laying and fixing of stone as per drawing and design, including cleaning, washing and finishing etc. complete. Upper Ground Floor
Providing and applying Two coats of wall care Putty on plastered surface and Ceiling and Walls to prepare surface even and smooth of approved make, etc complete.
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and applying boiled linseed oil in two coats to the new wood work, including knotting, preparing the surface, scaffolding etc. complete as directed. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and applying priming coat on concrete/ masonary/ Asbestos Cement plastered surfaces including scaffolding if necessary, preparing the surface by thoroughly cleaning oil, grease, dirt and other foreign matter and sand papering as required etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and applying interior wall finish luster of approved make on internal wall surface as detailed below Scrapping the surface with emery paper and wipe clean wall primer with brush with mineral turpentine with brush 8 to 10% and oil 15 to 20% with roller and allowing to dry for a period 6 to 8 hours. wall putty with appropriate proportion of water allowing to dry for period 4 to 6 hours. Scrapping with Emery paper 180 and wipe clean. Applyingwall primer with brush with mineral turpentine 8 to 10% and oil 15 to 20% with roller Scrapping Emery paper 320 and wipe clean, interior wall finish luster 1st coat with brush/rubber/spray with mineral turpentine 7 to 9% and Oil with roller 19 to 21% After 8 hours of activity Applying 2nd coat or wall finish Lustre with mineral turpentine 7 to 9 % with brush and Oil with roller 19 to 21% after allowing dry for the period of 6 to 8 hours activity. (With prior approval of S.E.) Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and applying washable oil-bound distemper of approved colour and shade to old and new surfaces in two coats including scaffolding, preparing the surfaces. (excluding the primer coat.) etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and applying 2 coats of 100% Pure acrylic low VOC and APEO & HCHO free water based paint of approved colour that belongs to class 1 flame spread resistance of approved make Paint should provide durable and long lasting silk finish with a high crack tolerance of upto 1mm. Paint should have an oustanding washability with high resistance to wide range of bacteria and fungus. Paint has to be applied on smooth and uniform surface prepared by an acrylic copolymer low VOC & Odour putty. This surface should be primed with water based low VOC Primer. The work activity should cover all aspects of applying paints from surface preparation as directed by Engineer in charge. First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Providing and fixing 900mm high S.S.304 Grade Stainless steel railing with 40mm diameter and 1.5mm thick at top,40mm diameter and 1.5mm thick vertical supports spaced at 1.5m center to center and 8mm thick toughened glass including fabricating ,fixtures, errecting , necessary welding , grinding , finishing, buffing to stainless steel pipe etc. complete Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing mild steel grill railing weighing 15Kilogram/ One Square Metre. with PVC handrail cover and newel post for staircases, including fabricating, fixtures, drilling holes in concrete / other surface, erecting the grill work, necessary welding, fixing by nuts and bolts, fixing PVC handrail cover, with one coat of anticorrosive paint and two coats of oil painting with approved colour and shade, remaking the damaged surface, cleaning, etc. complete. Spec. One Number : As directed by Engineer in charge.Ground Floor
Providing and Fixing mat finish stainless steel (of 302 grade ) railing with top pipe of 50 mm dia. and vertical pipe of 38 mm dia at 0.60 m c/c or as required and horizontal pipes of 25 mm dia in three rows, all pipes of 2 mm thick including buffing,fabricating fixtures and fastening including pipe base of appropriate diameter and ball base of 75 mm dia above newel post of 75 mm diameter etc. complete (Prior approval of sample and brand by Ex.Engineer is necessary before use) Fifth Floor
Sixth Floor
Seventh Floor
Design, supply, fabrication & erection of approved structural glazing using specially designed Vertical Mullion & HorizontalTransoms ofRequired size & as per architect's approved Grid work with aluminium rectangular sections to be fixed in masonary at interval of eachfloor on concrete slab with 80 mm x 100 mm x 5mm thick galvanized M & Langle fixed on wall side with raw bolt size of 10 mm x 90 mm with necessary bolts & washers / nuts for the plumb the linelevels. the glass panel's shall be fixed on a specially designed architectural sub- frame using Dow Corning 995 strural sealant & GE Silicon (SSG - 4000) sub frame would be fixed on main frame grid in amanner that no aluminium frame is visible from outside & groovesbetween the glass panel shall be filled with weather sealant of Dow corning 789 / GE Sil proof to made it air tight, water proof & dustfree thus giving it a flush look outside. Glass will be of 6 mm thick Glaverbel reflective type with heat strenghthened Fifth Floor
Sixth Floor
Seventh Floor
Providing,aupplying,fabricating and fixing panel of aluminium composite panel claddingin approved shape made out of 4 mm thick ACP sheet material consisting of 3mm thick FR grade mineral core following NBC part IV Fire and life safety (having 2 hours fireresistance in accordance to ASTM E119-12 and BS476 part 6 and 7 class O) and witched between two aluminium sheets (each 0.5 mm thick of AA 5005/AA3105 grade) Thealuminium composite panel cladding sheet shall be coil coated with kynar 500 asedPVDF/Lumiflon based fluropolymer resin (having 70:30 ratio of PVDF and acrylic)coating of approved colour and sg=hade on top face and polymer (service) coating of bottom face as specified using stainless steel screws,nuts,bolts,washers,cleats,weathersilicon sealent,backer rods etc .overall weight of the ACP shall not be less than 7.5 Kilogram/ One Square Metre) Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing of retro- reflectorised informatory sign board rectangular/Square in shape having area greater than 0.9 One Square Meterr made out of 2 mm aluminum sheet bonded with white retro reflective sheeting of Class B ( Type IV High intensity micro-prismatic grade sheeting-HIP) having pressure sensitive/heat activated adhesive retoreflective specified back ground, border and back side retoreflctive symbols, letters, numerals, arrow as per IRC:67-2012 Table No 8.3, supported with back support frame 25mm x 25mm x 3mm, duly painted on back side with two coats of grey stove enamel paint and supported on two no. mild steel angle iron post 75 mm x 75 mm x 6 mm, 3.5 mt long firmly fixed to the ground by means of properly designed foundation with M25 grade cement concrete 45 cm x 45 cm x 60 cm, 60 cm below ground level as per approved drawing The angle iron post shall be duly painted with one coat of epoxy primer and two coats of epoxy finish paints having alternate black and white bands of 25 cm width including GI fixures and transportation etc.complete.The nut bolts of board with angle iron post/supporting structure after fixing at site has to be electrically welded. Class B ( Type IV High intensity micro-prismatic grade sheeting-HIP) sheeting shall have 7 years written warranty from the manufacturer and authorised distributor/convertor issued for field performance including the screen printed areas and cut-out sheeting and cut-out durable transparent overlay film and this warranty certificate in original should be submitted to the Engineer in charge by the contractor/supplier. Ground Floor
Providing and fixing 90 cm x 60 cm Marble plate engraving 10 cm. height letter, figures including painting the lefters/figures with approved colour and shade complete Ground Floor
First Floor
Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. 12.5 mm thick square edge PVC Laminated Gypsum Tile of size 595x595 mm, made of Gypsum plasterboard, manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16mm thick fire retardant PVC film on the face side and 12micron metalized polyester on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyester film so as to make the tile a completely sealed unit. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing in position Gypsum board false ceiling with 12.5 mm thick Gypsum boards, screwed/fixed to the under structure of suspended G.I. Grid constructed and suspended from the main ceiling consisting of ceiling sections of size 25 x 50 mm maximum center to center distance of 600 milimetre perimeter channel and intermediate channels at maximum center to center distance 1200 milimetre galvanized grid should be fixed to reinforced cement concrete slab. The gypsum board should be fixed to galvanized iron grid with necessary screws. The boards should be taped and filled from underside to give smooth, seamless ceiling. The rate should include necessary additional ceiling sections and intermediate channels. Additional intermediate channels should be fixed to strap hangers for additional support to prevent strapping at every 1200 milimetre item to be completed in all respect including necessary sleeves for ducts finishing of joints cut outs, painting including labour, material, lifts etc. all complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and Fixing of GI Lay in Plain metal ceiling consisting of 600x600mm Lay in tiles of pre coated galvanized steel in 0.5 mm thickness in Global white color tile to be laid on grid systems with 15mm wide T - section flanges color white having rotary stitching on the Main Runner, 1200 mm and 600 mm Cross Tees.Providing and Fixing of GI Lay in Plain metal ceiling consisting of 600x600mm Lay in tiles of pre coated galvanized steel in 0.5 mm thickness in Global white color tile to be laid on grid systems with 15mm wide T - section flanges color white having rotary stitching on the Main Runner, 1200 mm and 600 mm Cross Tees.products approved as per GRIHA and BS 476 etc. complete. Ground Floor
Providing & Fixing signage made of 15 mm thick solid white acrylic laser cut out letters for height up to 25" etc complete. Ground Floor
Providing and fixing corrugated galvanised iron sheets of 0.63mm thick (24 B.W.G.) for roofing without wind tiles including fastening with galvanised iron screws and bolts, lead and bitumen washers as per drawing etc. complete.(Weight of 5.5 Kilogram/sq.m.) Terrace Floor.
Providing and fabricating structural steel work in rolled sections, fixed with connecting plates or angle cleats in main and cross beams, hip and jack rafters, purlins connecting to truss members and the like, as per detailed designs and drawing or as directed including cutting, fabricating, hoisting, erecting, fixing in position, making riveted/ bolted/ welded connections and one coat of anticorrosive paint and over it two coats of oil painting of approved quality and shade etc. complete. Upper Ground Floor
Providing and fixing Ball cock for 20 mm dia medium type with PVC float including sockets and necessary fittings and tested as per municipal requirement etc. complete.Ground Floor
Providing and fixing Ball cock 25mm dia.P.V.C.FLOAT medium type with PVC float including sockets and necessary fittings and tested as per municipal requirement etc. complete. Ground Floor
Providing and fixing Ball cock for 32mm dia medium type with PVC float including sockets and necessary fittings and tested as per municipal requirement etc. complete. Ground Floor
Providing and fixing Ball cock 40mm dia. medium type with PVC float including sockets and necessary fittings and tested as per municipal requirement etc. complete. Ground Floor
Providing and fixing Ball cock 50mm dia.P.V.C.FLOAT medium type with PVC float including sockets and necessary fittings and tested as per municipal requirement etc. complete Ground Floor
Providing and fixing 40 mm. dia Ball Cock medium type with PVC float including sockets and necessary fittings and tested as per municipal requirements etc. complete. Ground Floor
Providing and fixing 40 mm diameter Water Meter with non-return valve including strainer, sockets / union nut and including water meter box making locking arrangements and lock. [Without Chamber].Ground Floor
Providing and fixing 45 cm wide mild steel Ladder of 40mm x 6 mm mild steel flat stringers and steps of 18 mm dia. mild steel bar for water tank including fixing it in (1:2:4) M-15 cement concrete block 60cm x 30cm x 30cm and painting the ladder complete. (Anti Corossive Paint) Ground Floor
Terrace Floor
Providing and fixing 15cm x 10cm salt glazed stoneware Gully Trap in cement concrete 1:4:8 outside the building including cast iron grating in the sink, connecting glazed stoneware pipe, brick masonry chamber with cast iron lid and cast iron grating for the gully trap. Ground Floor
Providing and constructing Brick Masonry Inspection Chamber 60cm x 45cm x 90cm including 1:4:8 cement concrete foundation 1:2:4 cement concrete channels half round G.S.W. pipes, Brick Masonry, plastering from inside and with frame fixed in cement concrete with RCC Cover medium duty 140 Kilograms with frame etc. complete. Ground Floor
Providing and fixing reinforced cement concrete cover of size 60 cm x 45 cm with frame over inspection chamber etc. complete. Heavy duty (160 Kilogram) Ground Floor
Providing and constructing Brick Masonry Inspection Chamber 90cm x 45cm x 90cm including 1:4:8 cement concrete foundation 1:2:4 cement concrete channels half round G.S.W.pipes, Brick Masonry, plastering from inside and with frame fixed in cement concrete with R.C.C. Cover medium duty 140 kg with frame etc complete Ground Floor
Providing and fixing reinforced cement concrete cover of size 90 cm x 45 cm with frame over inspection chamber etc. complete. Heavy duty (225 Kilogram) Ground Floor
Providing and fixing on walls/ceiling/floor 20 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing on walls/ ceiling/ floor 25 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing on walls/ ceiling/ floor 32 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing on walls /ceiling/ floor 40 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
Providing and fixing on walls/ ceiling/ floor 50 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete.First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Terrace Floor
SProviding and making ISI Mark ferrule connection of 40 mm dia. to water main including ferrule coupling cast iron bell mouth cover, built in non return valve and fixing including excavation and reinstatement complete. Ground Floor
Providing and fixing in position sewer trap in last Chamber. Ground Floor
Providing and fixing C.P.wall mixer with provision for overhead shower with 115mm long bend pipe and wall flange jaquar make continental (Cat.No. CON-273UPR) including necessary sockets/union nut etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing C.P.Towel rail 24" jaquar make continental (Cat. No. ACN 1111N )including necessary sockets/union nut etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing White glazed with bottle trap earthenware Wash Hand Basin of 55x40 cm size including cold water piller taps, brackets, rubber plugs and brass chain, stop tap, chromium plate bottle trap and necessary pipe connections including UPAC waste pipe and trap upto the outside face of the wall, making good the damaged surface, testing etc. complete.Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing C.P.Angular stop cock jaquar make continental (Cat.No. CON-053) including necessary sockets/union nut etc. complete Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing 450mm x 550mm size superior type Belgium mirror with 16mm dia. nickel plated towel rod etc. complete Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and laying in trenches 32 mm dai. CPVC pipe including necessary excavation, fittings. Refilling trenches etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.Ground Floor
Providing and laying in trenches 40mm dai. CPVC pipe including necessary excavation, fittings. Refilling trenches etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete Terrace Floor
Providing and fixing 75 mm dia stabiliser pipe / P.V.C. soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps etc. complete Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing 100 mm dia stabiliser pipe / P.V.C. soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing C.P.2-way bib cock jaquar make continental (Cat.No. CON-041) including necessary sockets / union nut etc. complete as directed by Engineer in charge. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing 1st class white glazed earthenware Orissa Type W.C. Pan 580 mm dia including P or S trap cast iron soil and vent pipe upto the outside face of the wall (1:5:1 0) cement concrete bedding 15 mm thick, 10 liter P.V.C. flushing cistern with all necessary pipe connection etc. complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing 8 cm rigid PVC Nahani trap including PVC grating ,bend, connecting piece of UPVC pipe up to the outside face of wall ,making the good damaged surface and testing etc. complete ( Prior approval of sample and brand by Ex. Engr. is necessary before use) Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing European type white glazed earthen ware water closet pan with UPVC seat and lid with chromium plated brass hinges and rubber buffers including UPVC and vent pipe upto the outside face of wall 10 litre enameled low level flushing cistern with fittings pipe stop tap brackets for fixing cistern 32 mm dia. UPVC flush pipe with fittings and clamps, 20 mm dia. UPVC over flow pipe, mosquito proof couplings G.I. chain and pulley, with water Jet and fitting including cutting and making good to the walls and floors testing etc. complete. (prior approval of sample and brand by Ex. Engineer is necessary before use) Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing C.P.Handshower (health faucet) 1m.PVC tube with wall hook jaquar make (Cat. No. ALD 563 ) including all accessories etc complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing in position UPVC ultra violet stabilized 110 mm outer diameter cowl dome confirming to I.S.-4985 including making joints with solvent cement etc. complete Ground Floor
Providing and fixing C.P.Bib cock (ISI) jaquar make continental (Cat.No. CON-037) No. including necessary sockets/ union nut etc. complete.Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing C.P.sink cock with swinging casted spout jaquar make continental (Cat.No. CON- 347)(Wall Mounted Model) with wall flange with approved make incluidng other necessary fitting, etc. complete as directed by Engineer in charge. Ground Floor
Providing and fixing Stainless Steel sink of size 610 x 460 x 200 mm of nirali or equivalent make wall flange with approved make incluidng other necessary fitting, etc. complete as directed by Engineer in charge.Ground Floor
Providing and fixing white glazed urinal of size 710x460x300mm with sensotronic concealed type flushing valve for urinal with complete kit having fittings, inlet pipe with stop tap, brackets for fixing the cistern, 32mm diameter P.V.C. flush pipe with fitting and flushing arrangement including lead soil pipe, lead trap & soil pipe connection upto the outside face of wall etc complete. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
RWH - Shallow Percolation Pit providing, constructing 2.0m deep shallow depthpercolation pit comprising of 1.0m dia pre-cast RCC rings, 300mm thick side filling around outside of RCC rings (annular space) with 40mm size boulders including filling of percolation pit up to 0.5m depth (from bottom up) with 25-75mm clean washed gravels followed by 0.5m depth of 10-25mm of clean washed stones followed by 0.5m of washed river fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) including netlon mesh between each gravel/fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) media layer including covering with RCC slab, manhole frame & cover, PVC rungs etc. including arrangement for inlet & outlet pipe, excavation & backfilling as shown in the drawing. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels. All material should be of approved make. All works complete as per the drawing, technical specification and direction of the Engineer in charge. Ground Floor
Supplying & erecting cast iron double flange butterfly valve of size 50 mm dia. complete as per specification no. FFVL/BFV Ground Floor
Providing and laying cement concrete pipe of IS 458:2003 NP-2 class of 450mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. Ground Floor
Providing and laying cement concrete pipe of IS 458:2003 NP-2 class of 600mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. Ground Floor
Public Seating Chair. - 3 Seater Providing and Fixing 3 seater Public seating chair made of complete metal with Legs in Crome finish and seates in silver powder coating finish. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Free Standing Table @ 1500Lx600Dx750HT Providing and fixing Table of Size 1500 x 600 x 750 mm. Top: made from 25 mm Prelaminated Particle board. All edges are covered by 2 mm. Thk. PVC edge bands glued by hot melt glue applied by auto edge banding machine. Legs : C Shape made from CRCA Sheet with Powder Coat finish. Modesty panel : Made from 18mm both side prelaminated particle boards.All edges are covered by 0.8mm PVC edge bands glued by hot melt glue applied by auto edge banding machine.KEYBOARD TRAY ( WITHOUT MOUSE TRAY ) :- Metal Powder Coated - Black Color, CPU TROLLEY :- Metal Powder Coated - Black Color, 3 DRAWER PEDESTAL UNIT having overall size 392L x 450D x 680Ht. mm. with central lock and key. Drawers and body are complete metal with powder coat finish, facia in 18 mm prelaminated particleboard, Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Full Height Steel Storage @ 750Lx450Dx2100HT Providing and fixing Openable Steel Storage of 750 x 450 x 2100Ht, with 4 adjustable shelves, Complete body & shutter made in 0.8 mm thick & Top in 2 mm thick CRCA, 4 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns as as per drawing. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Medium Height Steel Storage @ 750Lx450Dx1200HT Providing and fixing Openable Steel Storage of 750 x 450 x 1200Ht, with 2 adjustable shelves, Complete body & shutter made in 0.8 mm thick & Top in 2 mm thick CRCA, 2 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns. with 25 mm. thk. as per drawing. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Multiple Compartment Lockers @ 1140Lx 457D x 1830 mm. Ht. Providing and fixing Multiple Compartment Lockers @ 1140Lx 457D x 1830 mm. Ht. with 12 Compartments , Complete body & shutter made of CRCA Sheet with powder coated finish as per approved color Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Sofa Set 3+1+1 Providing & fixing Sofa Set 3+1+1 Brown and Cream leather DIMENSION Length: 182.5 (cms) Breadth (cms): 100 (cms)Height (cms): 100 (cms) Weight (Kilograms): 66 (Kilogram) Seating Capacity: Five Seat Ground Floor
Third Floor
Stool for Lab and Class-IV Providing and fixing 4 legged Lab stool, Legs made of 16 Guage 45 MM Outer dimension MS Pipe, Duly painted, With a 304 Grade Stainless steel 12 inch wide seat with a 1 inch collar, Height adjustment via a screw. as per design and drawing and instructions of Engineer in charge. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing & Arrangemnt of Mid Back, ECO CTS Mechanism , Fixed Armrest , Gaslift for Seat height adjustment, Standard 5-prong P/Nylon Base with Fabric Upholstery Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing & Arrangemnt of High Back, Synchronized Mechanism with Multiple Locking, Adjustable Armrest, Gaslift for Seat height adjustment, Standard 5-prong P/Nylon Base with Leatherite Upholstery First Floor
Forth Floor
Conference Table @ 3600Lx1400Dx750HT Providing & Fixing of Main Table @ 3600Lx1400Dx750HT - made up of 18+18mm Thick MDF top with PVC Membrane finish and waterfall edge profile. Aluminium Anodizied finish beeding of 4mm thich is running all over the table top edge. Gable ends is Aerofoiled Shape with front edges in PVC Membrane finish and rest in Prelaminated MDF with batton structure. Gable ends should be hollow from inside for the provision of passing electrical and Data wiring. , MODESTY PANEL:- to be made of 18 mm thick Prelaminated particle board with PVC edge band Access Flap:- For Wire manager 2 Nos Forth Floor
Executive's Table @ 1800Lx900Dx750HT Providing & Fixing of Table @ 1800Lx900Dx750HT - TOP & GABLE END to be made of Membrane finish with soft water fall edges & curved panel & Decorated Anodized section MODESTY PANEL to be made of 18 mm thick Prelaminated particle board with PVC edge band as per drawing First Floor
Forth Floor
Directional signage-Design, supply, fabrication and fixing acrylic multilingual Braille (raised dots) signboards of size 6"x 9" for room titles, designed as per the drawings issued and having 4mm thick blue acrylic base plate with Upper Case San Serif words made of white acrylic non glare cut out letters of height 15mm raised not less than 0.8mm above base plate and the equivalent word/s written in Hindi with Devnagri non glare acrylic letters of height 15mm raised not less than 0.8mm above base plate. Grade 2/ Grade 1 Braille to be integral with the sign face and be raised 0.5mm above base plate.Each signboard to be fixed as per manufacturers specifications on the wall adjoining the respective room door at a height of 1200mm from FFL and as per the directions by the engineer in charge.As directed by Engineer-in-charge
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Floor Directories Providing and fixing acrylic multilingual Braille (raised dots)ADA compliant modular floor directories system on all floors of size1.5' x 2' , showing the floor plan and the list of rooms on that floor, to be installed on each floor near the staircase, designed as per standards and having 4mm thick blue acrylic base plate with Upper Case San Serif words and symbols made of white acrylic non glare cut out letters of height 20mm raised not less than 0.8mm above base plate and the equivalent word/s written in Hindi with Devnagri non glare imported acrylic letters of height 15mm raised not less than 0.8mm above base late. Grade 2/ Grade 1 Braille to be integral with the sign face and be raised 0.5mm above base plate. Each directory to be fixed as per manufacturers specifications on the wall at the approved location at a height of 1200mm from FFL and as per the directions by the engineer in charge. As directed by Engineer-in-charge Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
ADA compliant modular Multilingual and tactile Emergency evacuation map of each floor indicating the current position of the viewer saying "YOU ARE HERE" of 15mm height letters in red with white bacKilogramround, indicating the emergency exits, locations of fire extinguishers etc. Signs shall have a solid header with the text ―EVACUATION PLAN‖ in contrasting uppercase letters no less than 3/4" in height. The size of the board shall be 2ft x 2ft and shall be installed at a height of 1200mm from FFL and shall be oriented to the position of the viewer as per the direction of the site engineer.As directed by Engineer-in-charge Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Fire exit and floor identification signage as per manufacturer's specifications, ADA compliant and modular system.As directed by Engineer-in-charge Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Acrylic tactile audio map-Design, supply, fabrication and fixing of acrylic, non glare, tactile audio pictorial building layout as per the approved size, design and make, having 6mm thick acrylic non glare base plate of the approved colour and non glare acrylic cut out symbols and upper case Sans Serif letters of 12mm height, raised 3mm above base plate and Grade 2/ Grade 1 Braille to be integral with the sign face and be raised 0.5mm above base plate. The map to be installed at the specified location as per accessibility standards, shall be oriented to the position of the viewer and to be installed at a height of 800 mm from the finished ground/ floor level and using the necessary hardware specified by the manufacturer and to be installed up to the satisfaction of the engineer in charge..As directed byEngineer-in-charge Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing SS Braille buttons in the elevator of the approved brand and make to be installed using the specified adhesive and as per the instructions given by the manufacturer.As directed by Engineer-in-charge Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and fixing of high intensity reflective conspicuity tape 25 to 50mm width, on edges of treads in staircase including, cutting, pasting etc. of make 3M or equivalent brand as per the direction of engineer in charge.As directed by Engineer-in-charge Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Providing and Fixing Rollar Blinds AMI Make or approved make & shade of 38mm round Aluminium channel with Blackout fabric & telting with chain (Ball) system with all necessary fixtures and fitting etc. complete. (Sample to be final by Engineer In-charge prior execution of work) Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Reception Table -Providing and fixing in position Reception Table of size 4.05 x 0.75x1.20m ht as per drawing,Table by using 19mm &19mm ply patti for 38mm thk top with 16 mm polished granite counter and 19 mm thick plywood for all other horizontal and vertical members, front box, top box (as per drawing) Telescopic channel CPU Stand/ ready made Keyboard tray with mouse pad shall be provided of approved model and make. Footrest made in 18mm ply as per dwg. Table is having Storage of 0.45 x0.63 x0.45 3 no with 1 drawer & 1 shutter as per drawing shall be provided . Drawer Fascia to be made in 19mm ply with 1mm thk aminate from outside 0.8 mm thk laminate from inside and sides & back of drawer is to be made in 12mm ply & bottom in 6mm ply finished with 0.8mm thk laminate laminate from bothside . Shutter in 19 mm ply inished by 1 mm thk laminate fixed by 2 no of W-hinges, 2 no of 4” handles (Stainless Steel finish) and telescopic channels(18”/16) as per approval & drawing . All exposed plywood surfaces are to be finished with 1 mm thick laminate(range @ Rs.615/ sqm.) & all internal exposed surfaces in 0.8 mm thk laminate (range @ Rs.260/ sqm.)( ) of approved make & shade and all exposed edges of plywood to have 25mm x6mm , 0mm x 6 mm thk for top edge BTC lipping. All internal exposed wooden sections to be MELAMINE POLISH in matching colour of laminate. Rate inclusive anti termite treatment to the wooden &plywood material. tem to include all necessary hardware and fittings in Stainless Steel matt finish, handle , locks& shutter lock including magnetic ball catcher,tower bolts, chain(1 no for each shutter)(1 no for each shutter),hinges,3” .s matt wire manager , fevicol, screws etc.,as per instruction of site engineer in -charge , complete in all respects. Note: This item includes table (4.05 x 0.75 x1.20m ht 1 no with storage 0.45x0.60x0.75m ht),( foot est-0.6 x 0.3 x 0.1m ht x 1no)Spec. No.: As directed by Engineer in charge. Upper Ground Floor
NURSE STATION WITH SIDE UNIT-Providing and fixing in position Table of size 2.50 x 0.60x1.20m ht as per drawing…,Table by using 19mm &19mm ply patti for 38mm thk top with 16 mm polished granite counter and 19 mm thick plywood for all other horizontal and vertical members, front box, top box (as per drawing) Telescopic channel CPU Stand/ ready made Keyboard tray with mouse pad shall be provided ofapproved model and make. Footrest made in 18mm ply as per dwg. Table is having Storage of 0.45 x 0.60 x 0.45 ht 2 no with 1 drawer & 1 shutter as per drawing shall be provided &.Side unit of 1.45 x 0.60 x0.75 m ht with 2 drawer & 2 shutter as per drawing shall be provided. Drawer Fascia to be made in 19mm ply with 1mm thk laminate from outside 0.8 mm thk laminate from inside and sides & back of drawer is to be made in 12mm ply & bottom in 6mm ply finished with 0.8mm thk laminate laminate from bothside . Shutter in 19 mm ply finished by 1 mm thk laminate fixed by 2 no of W-hinges, 2 no of 4” handles (Stainless Steel finish) and telescopic channels(18”/16) as per approval & drawing .All exposed plywood surfaces are to be finished with 1 mm thick laminate(range @ Rs.615/ sqm.) & all internal exposed surfaces in 0.8 mm thk laminate (range @Rs.260/ sqm.)( ) of approved make & shade and all exposed edges of plywood to have 25mm x6mm , 50mm x 6 mm thk for top edge BTC lipping. All internal exposed wooden sections to be MELAMINE POLISH in matching colour of laminate. Rate inclusive anti termite treatment to the wooden &plywood material. Item to include all necessary hardware and fittings in Stainless Steel matt finish, handle , locks& shutter lock including magnetic ball catcher,tower bolts, chain(1 no for each shutter)(1 no for each shutter),hinges,3” s.s matt wire manager, , fevicol, screws etc.,as per instruction of site engineer in -charge , complete in all respects. Note: This item includes table (2.50 x 0.60 x1.20 1 no with storage 0.45x0.60 x0.45m ht) , Side unit (1.45 x 0.60 x 1.20m ht x 1 no),( foot rest-0.6 x 0.3 x 0.1 m ht x 2 no) Spec. No.: As directed by Engineer in charge. Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
NURSE STATION WITHOUT SIDE UNIT-Providing and fixing in position Table of size 2.41 x 0.60x1.20m ht as per drawing…,Table by using 19mm &19mm ply patti for 38mm thk top with 16 mm polished granite counter and 19 mm thick plywood for all other horizontal and vertical members, front box, top box (as per drawing) Telescopic channel CPU Stand/ ready made Keyboard tray with mouse pad shall be provided ofapproved model and make. Footrest made in 18mm ply as per dwg. Table is having Storage of 0.45 x 0.60 x 0.45 ht 2 no with 1 drawer & 1 shutter as per drawing shall be provided Drawer Fascia to be made in 19mm ply with 1mm thk laminate from outside 0.8 mm thk laminate from inside and sides & back of drawer is to be made in 12mm ply & bottom in 6mm ply finished with 0.8mm thk laminate laminate from bothside . Shutter in 19 mm ply finished by 1 mm thk laminate fixed by 2 no of W-hinges, 2 no of 4” handles (Stainless Steel finish) and telescopic channels(18”/16) as per approval & drawing .All exposed plywood surfaces are to be finished with 1 mm thick laminate(range @ Rs.615/ sqm.) & all internal exposed surfaces in 0.8 mm thk laminate (range @Rs.260/ sqm.)( ) of approved make & shade and all exposed edges of plywood to have 25mm x6mm , 50mm x 6 mm thk for top edge BTC lipping. All internal exposed wooden sections to be MELAMINE POLISH in matching colour of laminate. Rate inclusive anti termite treatment to the wooden &plywood material. Item to include all necessary hardware and fittings in Stainless Steel matt finish, handle , locks& shutter lock including magnetic ball catcher,tower bolts, chain(1 no for each shutter)(1 no for each shutter),hinges,3” s.s matt wire manager, , fevicol, screws etc.,as per instruction of site engineer in -charge , complete in all respects. Note: This item includes table (2.41 x 0.60 x1.20 1 no with storage 0.45x0.60 x0.45m ht) ,( foot rest-0.6 x 0.3 x 0.1 m ht x 2 no) Spec. No.: As directed by Engineer in charge.Ground Floor
First Floor
Second Floor
Third Floor
Forth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Electric Works Supplying, installing, testing and commissioning of SF 6 Insulated 22kV 630A 16kA/3sec 1 way outdoor extensible motorised SCADA compatible RMU internal arc tested as per electric supply company specification consisting of 1 no. feeder with 1 VCB compliant to IEC 62271 -100 200 and 102 as per specification no. SW-HTS/RMU SCADA [5-9-22]
Supplying and erecting HT CT multifunction DLMS compliance of accuracy of class 0.5 3x63.5V 50 Hz with optical & RS 232 port backlit LCD measures kWh kVAh V I kW 6 months history of energy load survey & displays trivector energy load survey TOD tamper detection & logging power ON /OFF events instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box. [6-3-6]
Supplying, erecting, testing and commissioning of 22KV HT metering cubical (compact type) approved by MSEDCL / licensee fabricated with 2 mm (14 SWG) M.S. sheets with supporting angle painted with powder coating / epoxy paint of required shade copper bus bar size 25 x 6 mm heavy duty mechanical lock with counter meter for measuring no. of times the opening of meter door top side cover (CT PT cover) interlock with meter door epoxy casted 3 nos. CT having required ratio between 5/5A to 25/5A VA 10 or 15 Class 0.5S epoxy casted 3 nos. PT having ratio 22000/V3/110/V3 VA 50 Class 0.5 suitable for provided trivector meter and provision for incoming and outgoing cables complete duly tested by licensee with necessary test certificates and erected on provided plinth/ cc foundation. [6-4-3]
Supplying and erecting LT current transformer with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates. [6-5-2]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL (DOUBLE RUN) [7-1-24]
Supplying, erecting & terminating XLPE insulated galvanised steel formed wire armoured (strip) cable 22 kV(E) 3 x 185 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT [7-3-19]
Providing and erecting Heat shrinkable indoor termination kit for 11 kV (UE)/ 22 kV ( E ) XLPE HT cable 3x120 to 185 sq. mm. with necessary material as per specification no. CB-JT/HT [7-5-13]
Providing and erecting Heat shrinkable outdoor termination kit for 11 kV (UE)/ 22 kV ( E ) XLPE HT cable 3x120 to 185 sq. mm. with necessary material as per specification no. CB-JT/HT [7-5-16]
Supplying and erecting G.I. pipe ‘A’ class 75 mm dia. erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE [7-6-4]
Supplying and laying (including excavation) half round reinforced cement concrete pipe of IS 458 2003 NP-2 class of 150 mm internal diameter in proper line level and slope including providing and fixing collars in cement mortar 1 2 and curing etc. complete. [7-6-6]
Supplying and laying (including excavation) of suitable width & depth up to 90 cm) 160 mm outside dia double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface to required depth complete. [7-6-14]
Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ [8-1-13]
Supplying and erecting MS pole bracket for guarding/LT OH line fabricated from ISM channel 75x40x6mm and 550mm long for necessary nos. of provided insulators and erecting on pole with 50x6mm clamp complete as per specification no. OH-PL/BKT [8-3-3]
Supplying and erecting 100 x 50 x 6 mm with 4.7 mm thick web and 7.5 mm thick flange channel iron cross arm of suitable length for 2.4 m wide DP structure and erecting on DP with 50x6mm clamp complete as per specification no. OH-PL/BKT [8-3-11]
Supplying and erecting ACSR conductor of size 6/1-2.59 mm complete. (Weasel) (127.7 kg/km) as per specification No. OH-CON/ACSR [8-4-7]
Supplying and erecting porcelain disc type insulator 70KN with necessary hardware suitable for 22kV line complete as per specification no. OH-INS/DI [8-5-7]
Supplying and erecting distribution class 22 kV thyrite type lightening arrester with nut bolts on provided MS channel as per specification no. OH-INS/LA [8-5-16]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials testing & recording the results as per specification no. EA-EP (TRANSFORMER NEUTRAL-4 DG NEUTRAL-4 METRING KIOSK-3 FENSING-1 LA-1) [9-1-1]
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials testing & recording the results as per specification no. EA-EP ( TRANSFORMER BODY-4 DG BODY-4 RMU-4 PANEL-1) [9-1-2]
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP. [9-2-2]
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. [9-2-3]
Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete. [9-2-5]
Supplying, installing, testing and commissioning of 3 phase 22/0.433 kV 50 Hz. 500 kVA Mineral oil immersed and naturally cooled outdoor type Copper wound Non-sealed transformer delta/star connected with additional neutral brought out on load side temperature rise should not exceed 45? by thermometer in oil and 50? by the resistance method in winding at full load rating using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5% having 7 number of tap positions with standard accessories complete with test certificate with losses below 1586 Watts at 50% load 4515 Watts at 100% load as per IS 1180 ((part 1) 2014 with necessary permissions of Electrical Inspector as per specification no SS- TR-NSL. [10-1-20]
Supplying and erecting 22 kV outdoor type gang operated air break triple pole switch 200 A capacity with 3 post pin type insulator per phase mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of C class G.l. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp. [10-6-3]
Supplying and erecting 22 kV outdoor type drop out fuse with insulator complete with fuse holders fuse barrel with metal fitting fuse element mounted on M.S. channel with working current of 15A capacity complete erected on provided cross arm. [10-6-6]
Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG [10-6-18]
Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class GI pipe with angle iron supports chain link wire mesh (jali) complete supported on channel iron erected in foundation and painted complete as per specification no SS-AS/DLD [10-6-20]
Providing printed instruction chart for treating persons suffering from electric shock printed in English & Marathi and duly laminated complete. [10-6-22]
Supplying standard first aid box with necessary antiseptic cream medicine for use on wounds due burn crepe bandage gauge bandage medicated ready to use bandage (Band-Aid) adhesive tape for medicinal use scissors anti-septic solution etc. (All above contents shall be of standard makes) [10-6-24]
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class C insulation conforming to IS 15652 – 2006 tested having 3mm thickness up to 33 kV [10-6-27]
Supplying, erecting, testing and commissioning of diesel generating set with alternator of 380/400 kVA output continuous rating 3 Phase 415 V 50c/s 0.8 p. f. A.C supply a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours along with standard accessories self-excited self-regulated screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 % with performance class G2 and maximum fuel consumption 65.5 Ltr/hr 75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters switchgears indicators connected with suitable wires/cables the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet sound absorbing material to restrict sound level up to 75 dB at 1.0 m provided with first filling of oil diesel not less than 450 Ltr etc. on provided M20 Grade CC Foundation and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG [11-1-20]
Supplying, erecting, testing and commissioning of Microprocessor based AMF panel suitable for Diesel Generating Set of above 320 kVA up to 400 kVA capacity Three phase 415 Volts 50Hz A.C. with all standard features safeties etc as per specification no. GEN-AMF. (by NOTE OF 10% of rate of new AMF panel/SYNC panel.) [11-2-17]
Supplying, installing, testing and commissioning of FR XLPE armoured cable 4 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU [13-9-11]
Excavating hard Rock or bituminous road by chiselling for preparing pit for pole / stay/earth plate / for laying cable/ pipe & clearing the site by removing debris & making the site as required complete.(5.3*4*1.7) [16-1-5]
second class Burnt Brick masonry with conventional /I.S. type bricks in cement mortar 1 6 in foundation sand plinth of inner walls /in plinth external walls including bailing out water manually striking joints on unexposed faces raking out joints on exposed faces and watering etc. Complete. [16-2-1]
Supplying and spreading stone metal 25 mm size for 100 mm depth above the ground level complete. [16-2-3]
Providing and fixing reinforced cement concrete cover of size 60 cm x 45 cm with frame over inspection chamber etc. complete of medium duty (100 Kilogram). [16-2-4]
Making transformer plinth (1.5 x 1.5 x 1.5) m in size with necessary excavation in ground with 150 mm. thick M- 10 PCC at the bottom and top and 250 mm. thick burnt brick wall constructed at periphery and remaining hollow portion shall be filled with 40mm hard broken aggregate. External surface duly plastered by 12 mm thick including watering etc complete. [16-3-1]
Making cement concrete foundation in 1 2 4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps).(5.3*4) [16-3-5]
Supplying and erecting triple pole mini feeder pillar with 500V 300A FPMCCB as incomer and 3 outgoing circuits with HRC fuse base and cartridge of 100A with aluminium bus bar erected in 14 SWG CRCA sheet box with supporting angles self locks gasket having IP54 IK10 protection and slanting top to be erected on provided foundation as per specification no. SW-SWR/MFP [5-2-2]
Providing and erecting 4 Pole MCCB 415V 200A rated short-circuit breaking capacity 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-2]
Providing and erecting 4 Pole MCCB 415V 250A rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-3]
Providing and erecting 4 Pole MCCB 415V 400A rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure /panel as per specification no. SW-SWR/MCCB [5-5-4]
Providing and erecting 4 Pole MCCB 415V 630A rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-5]
Supplying and erecting terminal spreaders suitable for 4 pole above 400A up to 630A MCCB (Set of 8) [5-11-9]
Supplying and erecting terminal spreaders suitable for 4 pole above 100A up to 250A MCCB (Set of 8) [5-11-7]
Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes panel boards etc. including cutting bending drilling welding riveting treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete. [6-1-1]
Supplying and erecting iron work sheet metal work consisting of CRCA sheets various sections of iron plates chequered plates rods bars MS pipes etc. for panel board or any other purpose with bending cutting drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. [6-1-19]
Supplying and erecting of any size electrolyte aluminium patti or bar in bus bar chamber / in panel or any other purpose 500 V with require capacity 99.9% aluminium purity with E91E Grade as per IS 5082 & Current Density 0.8 A per sq. mm. with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no. BCP-BB [6-2-11]
Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC [1-1-10]
Supplying and erecting HMS PVC conduit FRLS grade 32 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No WG-MA/CC [1-1-11]
Supplying and erecting PVC box trunking of size 50x16/20 mm. with accessories on wall/ceiling as per specification No WG-MA/BOX [1-2-10]
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting green colour earthing with 1x 1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-2]
Supplying and erecting green colour earthing with 1x 2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-2]
Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-3]
Supplying and erecting green colour earthing with 1x 4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-3]
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete. [1-6-1]
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete. [1-6-2]
Supplying and erecting modular type 3 pin 6A multi socket with safety shutter duly erected on provided plate and box with wiring connections complete. [1-6-10]
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter duly erected on provided plate and box with wiring connections complete. [1-6-11]
Supplying and erecting modular type bell indicator duly erected on provided plate and box with wiring connections complete. [1-6-18]
Supplying and erecting modular type buzzer 220 / 250V duly erected on provided plate and box with wiring connections complete. [1-6-19]
Supplying and erecting modular type (two module) electronic step regulator for fan duly erected on provided plate and box with wiring connections complete. [1-6-23]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 1 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-34]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-36]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 12 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-40]
Point wiring for light/bell concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/CW [1-7-5]
Point wiring for ceiling fan concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/CW [1-7-6]
Point wiring for light/bell hybrid type (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/HW [1-7-15]
Point wiring for ceiling fan (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/HW [1-7-16]
Wiring for plug on board with Switch socket surface/concealed type copper wiring and earthing and with modular accessories as per specification No WG-PW/CW [1-7-26]
Supplying and erecting LED square / circular Max. 14 W down lighter/Panel Light having pressure die-cast aluminium housing polystyrene diffuser having system lumens output of Min. 1500 Lumens min. efficacy of 110 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. max. ripple of 5% THD<10% p.f. >0.95 operating range of 120-270V surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. [2-1-4]
Supplying and erecting LED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing polystyrene diffuser having system lumens output of Min. 2000 Lumens min. efficacy of 110 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. max. ripple of 5% THD<10% p.f. >0.95 operating range of 120-270V surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. [2-1-5]
Supplying and erecting LED Panel Light(600mm X 600mm) Max. 30 W having CRCA powder coated housing polystyrene diffuser having system lumens output of Min. 3600 Lumens min. efficacy of 120 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. max. ripple of 5% THD<10% p.f. >0.95 operating range of 120-270V surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. [2-1-7]
Making suitable size recess in any type of false ceiling for erection of flush type down lighter and finishing the background to match the original surface upto 20W. [2-1-13]
Making suitable size of recess in any type of false ceiling for erection of flush type LED panel light 600mm x 600mm/1200x300mm and finishing the background to match the original ceiling surface. [2-1-14]
Supplying and erecting anodized aluminium corridor / passage / mirror light LED fitting (2 feet) Max. 12W with high transitivity diffuser with min. system lumens output of 1200 lumens min. efficacy of 100 lumen/W CRI>80 CCT upto 6000K Beam Angle of 110 deg. Ripple<5% THD<10% p.f. >0.95 operating range of 200-270V surge protection of 2 kV Life class of 50 000 Hrs. at L70B50 including driver with end caps on provided PVC Block / wooden board with 3 years warranty. [2-1-16]
Supplying and erecting anodized aluminium corridor / passage light LED fitting (4 feet) Max. 22W with high transitivity diffuser with system lumens output of Min.2200 lumens min. efficacy of 100 lumen/W CRI>80 CCT upto 6000K Beam Angle of 110 deg. Ripple<5% THD<10% p.f. >0.95 operating range of 200-270V surge protection of 2 kV Life class of 50 000 Hrs. at L70B50 including driver with end caps on provided PVC Block / wooden board with 3 years warranty. [2-1-18]
Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens min. efficacy of 110 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. THD<10% p.f. >0.95 operating range of 140-260V in built surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver IP66 IK09 rated on provided PVC Block / wooden board with 3 years warranty. [2-1-15]
Supplying and erecting inverter LED batten 20W tube light fitting with polycarbonate housing heat sink integrated HF electronic driver Min. 2600 mAh Lithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt CRI>80 CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty. [2-1-22]
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 225mm. 1400 RPM rust proof body & blades wire mesh duly erected complete. [2-10-14]
Supplying and erecting exhaust fan heavy duty 230 V A.C. 50 cycles 375/380 mm. 900 RPM complete erected in position as per specification no. FG-FN/EXF [2-10-16]
Supplying and erecting regular/ standard model ceiling fan of 900 /1050 mm. sweep complete erected in position as per specification no. FG-FN/CF [2-10-2]
Supplying and erecting energy saving ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF [2-10-21]
Supplying and erecting fan hook box of 10 mm M.S. round bar bounded to the R.C.C. bars upto 50 mm length each side and pierced through a 16 S.W.G. thick aluminium/M.S. Bowl 100 mm dia. or equivalent square size and having depth upto 75 mm complete erected with duly painted by one coat of red oxide paint and two coats of paint erected in position and without any leakage of slurry of cement concrete on either side of the box and positioned to the bottom level of the slab. [2-11-5]
Supplying and erecting ‘B’ class G.I .pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire. [2-11-6]
Supplying, erecting, testing and commissioning of self contained water cooler 230/250V 50Hz nominal cooling capacity of 150 litres per hour and storage capacity 150 litres with partially stainless steel body as per specification no. AP-WCR/WC [3-3-10]
Supplying and erecting ultra violet storage type water purifier (RO+UV+UF) with softener for safe drinking water consisting of UV germicidal tube of 8W capacity choke made of copper wire and two indicator lamps with output of purified water minimum 0.33 litre/min with activated carbon filter and softener operating on 230V single phase A.C. supply with UV fail & filter change indication system .(for TDS more than 200) [3-5-1]
Supplying and erecting storage type water heater 25 litres capacity having standing loss <0.511kWh/24hour/45°C high impact resistance engineering plastic body with anti corrosive high grade steel inner tank heating element having hard water & corrosion protection with minimum 3 safety protections (i.e. thermostat & thermal function cut-out valve) with total pressure 8 bar withstanding capacity duly tested and marking sr. no. and date of erection complete. specification no. AP-WH/STWH [3-1-2]
Supplying, installing, testing and commissioning of 6kVA capacity online pure sine wave with backup time of 1 hrs. PWM & IGBT based UPS with 0.9 to unity output pf single phase input & 1 phase output complete with all protections as per specification no. AP-UPS [3-7-4]
Supplying, installing, testing and commissioning of 10kVA capacity online pure sine wave with backup time of 1 hrs. PWM & IGBT based UPS with 0.9 to unity output pf 3 phase input & 3 phase output complete with all protections as per specification no. AP-UPS [3-7-7]
Supplying, installing, testing and commissioning of 20kVA capacity online pure sine wave with backup time of 1 hrs. PWM & IGBT based UPS with 0.9 to unity output pf 3 phase input and 3 phase output complete with all protections as per specification no. AP-UPS [3-7-8]
Supplying and erecting 12V/42Ah SMF battery with battery terminal wire duly charged with 24 months warranty complete [3-8-10]
Supplying and erecting 12 V/65Ah SMF battery with battery terminal wire duly charged complete with 24 months warranty complete [3-8-11]
Supplying and erecting 12V/100Ah SMF battery with battery terminal wire duly charged with 24 months warranty complete. [3-8-12]
Supplying, erecting and marking SPMCB 6A to 32A C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-2]
Supplying, erecting and marking SPMCB 6A to 32A B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-3]
Supplying, erecting and marking DPMCB 6 A to 32 A B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-7]
Supplying, erecting and marking TPMCB 6A to 32A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-10]
Supplying, erecting and marking TPMCB 40A to 63A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-11]
Supplying, erecting and marking FPMCB 40A to 63A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-13]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SPMCB of 4 ways/phase (12 poles) with door 1.2mm thickness surface/flush mounted IP 43 protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB [5-4-1]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SPMCB of 8 ways / phase (24 poles) with door 1.2mm thickness surface/ flush mounted IP 43 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB [5-4-2]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SP/TP MCBs total 8 ways /24 poles with door 1.2mm thickness surface/flush mounted IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB [5-4-5]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SP/TP MCBs total 4 ways /12 Poles with door 1.2mm thickness surface/flush mounted IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB [5-4-4]
Supplying and erecting single pole and neutral distribution board (SPNDB) with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs with door 1.2mm thickness surface / flush mounted IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB [5-4-8]
Supplying and erecting single pole and neutral distribution board (SPNDB) with 2 ways for incoming and 10 ways (10 poles) for outgoing SP MCBs with door 1.2mm thickness surface / flush mounted IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB [5-4-9]
Supplying and erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame. [5-4-13]
Supplying and erecting triple pole and neutral distribution board (TPNDB) 3 pole/4 pole MCCB as incomer & outgoing SP MCB (24 poles) or TP MCB of 8 ways (24 poles) with door 1.2mm thickness surface/flush mounted on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1 [5-4-16]
Providing and erecting 4 Pole MCCB 415 V 100A rated short-circuit breaking capacity 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and fixed magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-1]
Providing and erecting 4 Pole MCCB 415V 200A rated short-circuit breaking capacity 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-2]
Providing and erecting 4 Pole MCCB 415V 250A rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-3]
Providing and erecting 4 Pole MCCB 415V 400A rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure /panel as per specification no. SW-SWR/MCCB [5-5-4]
Providing and erecting 4 Pole MCCB 415V 630A rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-5]
Supplying, Erecting and Commissioning of 2 pole RCCB 16/25A electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB [5-6-1]
Supplying, Erecting and Commissioning of 4 pole RCCB 40A electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB [5-6-5]
Supplying, Erecting and Commissioning of 4 pole RCCB 63A electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB [5-6-6]
Supplying, Erecting and Commissioning of 4 pole RCCB 16/25A electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB [5-6-4]
Supplying, fixing, and commissioning 2 pole RCBO 6/10/16/20/25A with overcurrent rated short-circuit breaking capacity (10 kA) and earth leakage protection with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO [5-6-9]
Supplying, erecting and marking SPMCB 0.5A to 5A C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-1]
upplying and erecting terminal spreaders suitable for 4 pole above 250A up to 400A MCCB (Set of 8) [5-11-8]
Supplying and erecting terminal spreaders suitable for 4 pole above 400A up to 630A MCCB (Set of 8) [5-11-9]
Supplying and erecting terminal spreaders suitable for 4 pole above 100A up to 250A MCCB (Set of 8) [5-11-7]
Supplying and erecting extended rotary handle for MCCB with adjustable telescopic rod suitable for up to 250A MCCB. [5-11-14]
Supplying and erecting extended rotary handle for MCCB with adjustable telescopic rod suitable for above 250A up to 630A MCCB. [5-11-15]
Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes panel boards etc. including cutting bending drilling welding riveting treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.( crca sheet 718 for panel & 506 for battery rack) [6-1-1]
Supplying and erecting iron work sheet metal work consisting of CRCA sheets various sections of iron plates chequered plates rods bars MS pipes etc. for panel board or any other purpose with bending cutting drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.( crca rod 135 for panel & 275 for battery rack) [6-1-19]
Supplying and erecting of any size electrolyte aluminium patti or bar in bus bar chamber / in panel or any other purpose 500 V with require capacity 99.9% aluminium purity with E91E Grade as per IS 5082 & Current Density 0.8 A per sq. mm. with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no. BCP-BB [6-2-11]
Supplying and erecting panel mounting type digital ammeter having three and half digit LED display external CT operated calibrated for suitable to operate on 500V 0 to 1000A having accuracy class of 0.5 AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer. [6-3-7]
Supplying and erecting panel mounting type digital voltmeter having three and half digit LED display calibrated for 0 to 750V AC suitable to operate on 500V having accuracy class of 0.5 AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer. [6-3-8]
Supplying and erecting LT current transformer with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates. [6-5-2]
Supplying and erecting LED type indicating pilot lamp with LED colours red / yellow / green 230 / 250V on provided box / panel with necessary material wiring & connections etc. [6-5-5]
Supplying and erecting LED type indicating pilot lamp with LED colour blue 230 / 250 V on provided box / panel with necessary material wiring & connections etc. [6-5-6]
Supplying and erecting 150 kVAr 440 V 3 phase 50 Hz. Contactor Logic & Intelligent Relay micro APFC passive filter panel consisting of suitable steps of APP/MPP type capacitor units with Detuned (harmonic filter) reactors of suitable rating APFC panel shall be compliance to IEC 61439 and power quality IEC 61921 standard as per specification no CP-ED/APFC [6-7-7]
Providing and erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 100 mm height comprising all required standard accessories. [7-11-1]
Providing and erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 200 mm width & 100 mm height comprising all required standard accessories. [7-11-2]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials testing & recording the results as per specification no. EA-EP [9-1-1]
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials testing & recording the results as per specification no. EA-EP [9-1-2]
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP. [9-2-2]
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. [9-2-3]
Supplying and erecting conventional spike type air termination suitable to carry lightning stroke made up of heavy gauge 40 mm dia copper pipe of standard length with 5 Nos. copper spikes fixed on copper ball as air terminals duly threaded in copper pipe erected on provided foundation complete. [9-3-1]
Supplying erecting & terminating XLPE HFFR armoured cable - 4 core 4 sq.mm copper conductor c ontinuous 5.48 sq.mm ( 12 SWG) GI earth wire complete erected with glands & lugs on wall / trusses/ pole or laid in provided trench/ pipe as per specifications no. CB-LT.CU NON CSR [1-1-23]
Supplying erecting & terminating XLPE HFFR armoured cable - 4 core 6 sq.mm copper conductor c ontinuous 5.48 sq.mm ( 12 SWG) GI earth wire complete erected with glands & lugs on wall / trusses/ pole or laid in provided trench/ pipe as per specifications no. CB-LT.CU ( Non CSR ) [1-1-24]
Supplying erecting & terminating XLPE HFFR armoured cable - 4 core 10 sq.mm copper conductor c ontinuous 5.48 sq.mm ( 12 SWG) GI earth wire complete erected with glands & lugs on wall / trusses/ pole or laid in provided trench/ pipe as per specifications no. CB-LT.CU (NON CSR) [1-1-25]
Supplying erecting & terminating XLPE HFFR armoured cable - 4 core 16 sq.mm copper conductor c ontinuous 5.48 sq.mm ( 12 SWG) GI earth wire complete erected with glands & lugs on wall / trusses/ pole or laid in provided trench/ pipe as per specifications no. CB-LT.CU ( Non CSR) [1-1-26]
Supplying, erecting & terminating HFFR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL (WITH NOTE OF RATE RISE BY 14% FOR HFFR) [7-1-17]
Supplying, erecting & terminating HFFR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½ core 95 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL(WITH NOTE OF 14 % RATE RISE FOR HFFR) [7-1-19]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-20]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½core 240 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-23]
Supplying, erecting, testing and commissioning of 10kW 3 x 3.3 KW AC Electric Vehicle charger (suitable for 2/3/4 wheeler) having minimum IK08/IP 54 Protection suitable for three phase 415V AC 50Hz incoming and 3 nos. output as per IEC 60309 industrial sockets having capacity of output current of 16A 240V AC at each socket with 3.5 TFT touch screen for human interface & LED Light for status indication and metering for measurement of consumed energy having metering accuracy +/-1% one hour battery backup for communication emergency push stop button and having short circuit over & under voltage overload over temperature earth leakage protection and enclosure made of minimum 1.5mm duly RAL7035 Coated M.S Erected on iron/GI frame on provided cement concrete foundation complete with one year on site warranty confirming to IS 17017 Series as per specification. [4-7-1]
Supplying, erecting, testing and commissioning of 15 KW DC Electric Vehicle Charger (suitable for 4 wheeler)having minimum IK08 & IP54 protection suitable for three phase 415V AC 50Hz incoming supply and 1 no. output charger interface GB/T with 40-100VDC supply and 15 kW capacity interlocking arrangement with minimum 5 meter charging cable length 7 LCD touch screen for human interface & LED light for status indication metering for measurement of consumed energy having metering accuracy +/-1% One hour battery backup for communication emergency push stop button. User interface by mobile application/QR Code/RIFD Card/Password Login with payment options and having short circuit over & under voltage surge protection earth leakage protection and enclosure made of minimum 1.5mm duly RAL7035 coated M.S erected on iron/GI frame on provided cement concrete foundation complete with one year on site warranty confirming to IS 17017 Series as per specification [4-7-3]
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No WG-MA/CC [1-1-9]
Supplying and erecting modular type T.V. socket single outlet duly erected on provided plate and box with wiring connections complete. [1-6-14]
Supplying and erecting modular type telephone socket one gang with safety shutter duly erected on provided plate and box with wiring connections complete. [1-6-15]
Supplying and erecting modular type blanking plate one module duly erected on provided plate & box. [1-6-24]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-35]
Supplying and erecting 2 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation polyester taped Nylon Rip Cord & grey colour sheathed with FR PVC conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW [1-8-1]
Supplying and erecting 10 pair 0.5 mm dia. jelly filled armoured telephone copper cable with poly-al laminate moisture barrier polythene sheathed G.S.Tape armoured polythene jacketed having laid in provided trench as per specification No. WG-TW [1-8-13]
Supplying and erecting co-axial copper cable low voltage grade tri-shielded RG-11 as per specification No. WG-TW [1-8-18]
Supplying, Erecting and Commissioning of MDF Box 50x50 pairs made from min. 1.5mm thick MS sheet as per specification no. WG-TW [1-9-1]
Supplying, Erecting and Commissioning of 10 pairs FR junction box with moulded plastic enclosure as per specification no. WG-TW [1-9-11]
Supplying, Erecting and Commissioning of 10 pair module for connection & disconnection of telephone cable as per specification no. WG-TW [1-9-18]
Supplying, Erecting and Commissioning of digital (hybrid) type EPABX of 6 x 32 extensions suitable upto 96 extensions complete. [1-9-26]
Supplying, Erecting and Commissioning of push button telephone instrument desk top/wall mount with caller ID & Speaker unit as per specification complete. [1-9-29]
Supplying, Erecting and Commissioning of IP telephone instrument as per specification complete. [1-9-30]
Supplying and installing cat-6 cable suitable for networking as per specification no. WG-COC/NC [1-10-1]
Supplying and installing cat-6 armoured cable with ECCS tape suitable for networking as per specification No. WG-COC/NC [1-10-7]
Supplying and fixing 1 m UTP patch cord of Cat 6 type in position as per specification No. WG-COC/PC [1-10-16]
Supplying, fixing, and configuring 24 ports with 4 (SFP+) port ethernet managed switch with web view/CLI 6KV surge protection on ethernet port and console port for management in provided rack as per specification no. WG-NWC/GBS [1-11-4]
Supplying, installing & testing UTP connector (RJ-45) as per specification No. WG-NAS/UTPC. [1-12-1]
Supplying and fixing tool-less shutter keystone jack (RJ-45) in provided patch panel complete as per specification no. WG-NAS/KJ [1-12-3]
Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no. WG-NAS/PP [1-12-4]
Supplying and fixing 9U wall mount rack (Dimension-DxWxH – 500x600x500 mm) as per specification No. WG-NAS/RAK [1-12-18]
Supplying, fixing, and configuring broadband ADSL router with all accessories on provided rack as per specification No. WG-NWC/ADSL [1-11-17]
Supplying, installing, testing and commissioning of storage type Mild Steel mixing water tank of capacity 3000 ltrs. tested to a pressure of 8 kg/cm2 insulated with 50 mm thick rock wool with wire mesh around and cladded with 26 SWG aluminium of dish end type with working pressure of 6 kg/cm2 fabricated with 6 mm thick MS plate and dished ends with 8 mm thick plates complete with man hole cover inner side of the tank coated with FRP coating of 3 mm thickness withstand temperature of 90°C provided with collars of 2 BSP for provision to install 6 numbers of electrical heating coils if required with thermal sensors for automatic operation and integrated into the electrical circuits of the circulation pumps and the heat pump with safety valve drain inlet and outlet nozzle pressure gauge with all necessary accessories complete. [4-6-6]
Supplying, installing, testing and commissioning of storage type Mild Steel mixing water tank of capacity 5000 ltrs. tested to a pressure of 8 kg/cm2 insulated with 50 mm thick rock wool with wire mesh around and cladded with 26 SWG aluminium of dish end type with working pressure of 6 kg/cm2 fabricated with 6 mm thick plate and dished ends with 8 mm thick plates complete with man hole cover inner side of the tank coated with FRP coating of 3 mm thickness withstand temperature of 90°C provided with collars of 2 BSP for provision to install 6 numbers of electrical heating coils if required with thermal sensors for automatic operation and integrated into the electrical circuits of the circulation pumps and the heat pump with safety valve drain inlet and outlet nozzle pressure gauge with all necessary accessories complete. [4-6-7]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 4 core 6 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-32]MA/BOX [1-2-10]
Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes panel boards etc. including cutting bending drilling welding riveting treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete. [6-1-1]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3 core 4 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [ FOR JOCKEY PUMP] [7-2-15]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½ core 150 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [ FOR MAIN FIRE PUMP] [7-2-26]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½core 240 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [ FOR FIRE PANEL] [7-2-28]
Providing and erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware. [7-11-8]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials testing & recording the results as per specification no. EA-EP [ FOR FIRE PANEL-2 SPINKLER PUMP-2 HYDRANT PUMP-2] [9-1-1]
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. [9-2-3]
Supplying, installing, testing and commissioning of main fire pump(MFP / EP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by electric motor 415 volts 3 phase 50 Hz AC supply of 75kW or of suitable kW capacity for manual/automatic operation and consisting of following (a) Horizontal type single stage centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade) mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor TEFC synchronous speed 3000 RPM suitable for operation with IP 55 protection for enclosure horizontal foot mounted type with Class-'F' insulation conforming to IS-325. (c) M.S. fabricated common base plate coupling coupling guard foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-MFP/SSC/EP [13-1-6]
Supplying, installing, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 110 to 90 m head driven by electric motor 415 volts 3 phase 50 Hz AC supply of 11 kW or of suitable kW capacity for manual/automatic operation and consisting of following (a) Horizontal/vertical type multi stage centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade) mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor TEFC synchronous speed 3000 RPM suitable for operation with IP 55 protection for enclosure horizontal foot mounted type with Class-'F' insulation conforming to IS-325. (c) M.S. fabricated common base plate coupling coupling guard foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-MFP/JP [13-2-3]
Supplying, installing, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by 110 HP or suitable HP capacity diesel engine at required working speed suitable for automatic operation and consisting of following (a) Horizontal type single stage centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade) mechanical seal conforming to IS 1520. (b) Water cooled with radiator diesel engine conforming to relevant IS standard complete with auto starting mechanism 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v 50Hz AC supply diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding residential silencer instruments and protection as per standard specification stop solenoid for auto stop in the event of fault with audio indications etc. as required. (c) M.S. fabricated common base plate coupling coupling guard foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete as per specification no. FF-MFP/SSC/DP [13-4-3]
Supplying and erecting G.I. pipe ‘C’ class ERW 25 mm dia with necessary fittings complete as per specification no. FF-PP [13-6-2]
Supplying and erecting G.I. pipe ‘C’ class ERW 50 mm dia with necessary fittings complete as per specification no. FF-PP [13-6-3]
Supplying and erecting G.I. pipe ‘C’ class ERW 65 mm dia with necessary fittings complete as per specification no. FF-PP [13-6-4]
Supplying and erecting G.I. pipe ‘C’ class ERW 75/80 mm dia with necessary fittings complete as per specification no. FF-PP [13-6-5]
Supplying and erecting G.I. pipe ‘C’ class ERW 100 mm dia with necessary fittings complete as per specification no. FF-PP [13-6-6]
Supplying and erecting G.I. pipe ‘C’ class ERW 150 mm dia with necessary fittings complete as per specification no. FF-PP [13-6-7]
Providing G.I. pipe ‘C’ class ERW 200 mm dia with necessary fittings complete as per specification no. FF-PP [13-6-8]
Providing coating of bitumen paint & 4mm thick wrapping for underground 150 mm ring main of fire fighting system. [13-6-10]
Supplying and erecting 200 mm dia Cast Iron end line strainer of Y-type flanged end pattern PN16 pressure rating screen of SS end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS [13-7-8]
Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating as per specification no. FF-VL/SV [13-7-14]
Supplying and erecting 150 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating as per specification no. FF-VL/SV [13-7-15]
Supplying and erecting 200 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating as per specification no. FF-VL/SV [13-7-16]
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating as per specification no. FF-VL/BFV [13-7-17]
Supplying and erecting 65 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating as per specification no. FF-VL/BFV [13-7-18]
Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating as per specification no. FF-VL/BFV [13-7-19]
Supplying and erecting 100 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating as per specification no. FF-VL/BFV [13-7-20]
Supplying and erecting 150 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating as per specification no. FF-VL/BFV [13-7-21]
Supplying and erecting 100 mm dia cast iron double flange NRV complete with PN16 pressure rating as per specification no. FF-VL/NRV [13-7-24]
Supplying and erecting 150 mm dia cast iron double flange NRV complete with PN16 pressure rating as per specification no. FF-VL/NRV [13-7-25]
Supplying and erecting 200 mm dia cast iron double flange NRV complete with PN16 pressure rating as per specification no. FF-VL/NRV [13-7-26]
Supplying and erecting stainless steel double outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV [13-7-37]
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV [13-8-2]
Supplying and erecting 63mm dia reinforced rubber lined (R.R.L.) hose pipe 15m in length fitted with necessary accessories complete as per specification no. FF-FFA/RRL [13-8-4]
Supplying and erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ [13-8-8]
Supplying and erecting 150 mm dia fire brigade header suitable for supplying water in fire tank complete as per specification no. FF-FA/FBC [13-8-10]
Supplying and erecting 300 mm dia 1.5m in height air vessel / tank fabricated from min 5mm thick M.S. sheet complete as per specification no. FF-FFA/ACT [13-8-12]
Supplying and erecting 20/25mm dia gun metal air release cock with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV [13-8-13]
Supplying and erecting 100 mm dia. pressure gauge 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve erected with provided G.I. pipe elbow etc. complete as per specification no. FF-FFA/PG [13-8-14]
Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve G.I. nipple elbow etc complete as per specification no. FF-FFA/PS [13-8-15]
Supplying and erecting brass orifice plate having 6 mm. thickness 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP [13-8-16]
Supplying and erecting M.S./CRCA cabinet for housing Fire Brigade / SIEMESE connections (size 1250 x 400 x 300 mm.) made from 16 SWG sheet and angle iron 25 mm. x 25 mm. x 4 mm. having front doors with viewing glass (8 x 6 ) and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) [13-8-19]
Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve hose pipe hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8 x6 ) and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) [13-8-20]
Supplying, installing, testing and commissioning of remote response indicators suitable to operate on 5 - 28 V dc supply having FR Polymer ABS Housing complete as per specification no. FF-FAAS/RRI [13-9-9]
Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel central processing unit with the 1 loop capacity and capable of supporting upto 250 devices and detectors per loop with on-board LCD display with min 16 lines of text operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition suitable provision for network connectivity interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908 2021 IS 2189 2008 EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP. [13-10-1]
Supplying, erecting and marking SPMCB 6A to 32A C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-2]
Supplying, installing, testing and commissioning of addressable optical smoke detector single/twin LED’s with 360 degree view suitable for low voltage 15 to 32 V DC two wires supply in-built locking mechanism to check the removal and pilferage of the detector in built isolation mode start up current 300µA and alarm condition current shall be maximum 6.5 mA operating temperature 0°C to 50°C humidity 0-95% RH IP 41 conforming to IS 2189 2008 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF-AFAS/SD . [13-10-6]
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors in built isolation mode suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS 2175 - 1988 reaffirmed 2000 IS 15908 2021 standards FF-AFAS/SD. [13-10-7]
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type) made of addressable break glass plastic square in shape surface/flush mounted with Break Glass massage embedded on the glass complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP. [13-10-9]
Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) 1982 reed relays EN 54 or UL Listed FF-AFAS/CRM [13-10-10]
Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) 1982 Reed relays FF-AFAS/MM [13-10-11]
Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) 1982 Reed relays FF-AFAS/ISM [13-10-12]
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908 2021 with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54 conforming to IS 2189 2008 IS 15908 2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH. [13-10-13]
Supplying, erecting, testing and commissioning of 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF-PA/AFR [10/30w =300/120=2.5) [13-11-1]
Supplying, erecting, testing and commissioning of 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC [13-11-2]
Supplying, erecting, testing and commissioning of stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector stereo jack complete as per specification no. FF-PA/MIC [13-11-3]
Supplying, erecting, testing and commissioning of rust free microphone floor stand of chrome plating/powder coating or S.S. material 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete. [13-11-4]
Supplying, erecting, testing and commissioning of 1.5 sq. mm speaker wire complete. [13-11-10]
Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler 15 mm (½ ) dia. NBCM Body chrome finished 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR. [13-12-1]
Supplying, erecting, testing and commissioning of vane type water flow detector 75/80 mm dia. with 1) Visual switch activation 2) Rugged switch assembly 3) Heavy duty aluminium pipe saddles 4)Durable metal enclosure 5) Steel U bolts for secure mounting 6) Two SPDT ( Single pole double track ) synchronised switches 7) serviceable without draining pipes. [13-12-2]
Supplying and erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete. [13-15-1]
Excavating hard Rock or bituminous road by chiselling for preparing pit for pole / stay/earth plate / for laying cable/ pipe & clearing the site by removing debris & making the site as required complete. [16-1-5]
Excavating hard murum / stone metal road by chiselling for preparing pit for poles stay or earth plates or for laying cables pipes & clearing the site by removing debris & making the site as required complete. [16-1-6]
Making cement concrete foundation in 1 2 4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps). [16-3-5]
Providing and fixing high-density polyethylene (HDPE) container one piece moulded triple layer water tank made out of high density polyethylene and built corrugated inclusive of delivery up to destination hoisting and fixing of accessories such as inlet outlet overflow pipe inclusive of all tanks capacity up to 20000 litres. [4-8-7]
Carrying out core cutting of size 3 to 5 dia x 15 length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. (with note) [3-11-77]
Supplying and installing auto glow (Viewing up to 15 mtr length) fire signages in PVC/Vinyl 4/6mm thick sheet or as per sample approved by client viz fire hydrant fire hydrant fire extinguishers fire exists fire door fire hose box fire & Electrical & safety etc size 300mm* 100 mm (Rates are taken from previously sanctioned estimate D1104512022-23 Mumbai subdivision vide letter no 173/2022-23 ) [NON CSR] [999-1-1]
Supplying and erecting ABC powder type fire extinguisher as per IS 13849 /15683 of 6 kg capacity with necessary clamp for erection on wall. [NON CSR] [999-1-2]
Supplying and installing auto glow (Viewing up to 15 mtr length) fire signages viz fire hydrant fire hydrant fire extinguishers fire exists fire door fire hose box fire & Electrical & safety etc size 450mm* 150 mm (Rates are taken from previously sanctioned estimate D1104512022-23 Mumbai subdivision vide letter no 173/2022-23 ) [NON CSR] [999-1-3]
Supply & Eracting 1000 mm long 25 mm dia. Stainless steel corrugated flexible pipe (hose)nfor dropping sprinkler below false ceiling pipe shall have 16 bar rating and with union/reducer coller clamps etc. as required.(Rates are taken from previously sanctioned estimate D1104512022-23 Mumbai subdivision vide letter no 173/2022-23 ) [NON CSR] [999-1-4]
Supply lnstaltation testing & commisrioning of flow switches in 80/100/150 mm dia pipe with all acceslories as required. [999-1-5]
Supplying and erecting green colour earthing with 1x 1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete. [1-6-2]
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter duly erected on provided plate and box with wiring connections complete. [1-6-11]
Supplying and erecting PVC Surface modular switch box with double mounting plate for 4 module duly erected. [1-6-29]
Point wiring for light/bell concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/CW [1-7-5]
Point wiring for ceiling fan concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/CW [1-7-6]
Point wiring for light/bell/exhaust fan in 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire modular type switch earthing and required accessories as per specification No WG-PW/SW. [1-7-12]
Wiring for plug on board with Switch socket surface/concealed type copper wiring and earthing and with modular accessories as per specification No WG-PW/CW [1-7-26]
Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens min. efficacy of 110 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. THD<10% p.f. >0.95 operating range of 140-260V in built surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver IP66 IK09 rated on provided PVC Block / wooden board with 3 years warranty. [2-1-15]
Supplying and erecting anodized aluminium corridor / passage light LED fitting (4 feet) Max. 22W with high transitivity diffuser with system lumens output of Min.2200 lumens min. efficacy of 100 lumen/W CRI>80 CCT upto 6000K Beam Angle of 110 deg. Ripple<5% THD<10% p.f. >0.95 operating range of 200-270V surge protection of 2 kV Life class of 50 000 Hrs. at L70B50 including driver with end caps on provided PVC Block / wooden board with 3 years warranty. [2-1-18]
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades wire mesh duly erected complete. [2-10-13]
Supplying and erecting energy saving ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF [2-10-21]
Supplying and erecting 22 SWG G.I sheet metal cawl sector shaped with 25 x 25 x 3 (mm) angle iron frame metal mesh to avoid birds entry with necessary material suitable for exhaust fan of 300 mm as per specification no FG-FAS/MSC [2-11-14]
Supplying, erecting and marking DPMCB 6 A to 32 A B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-7]
Supplying, erecting and marking TPMCB 40A to 63A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-11]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SP/TP MCBs total 4 ways /12 Poles with door 1.2mm thickness surface/flush mounted IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB [5-4-4]
Supplying and erecting single pole and neutral distribution board (SPNDB) with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs with door 1.2mm thickness surface / flush mounted IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB [5-4-8]
Supplying and erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame. [5-4-13]
Supplying, Erecting and Commissioning of 4 pole RCCB 40A electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB [5-6-5]
Supplying, fixing, and commissioning 2 pole RCBO 6/10/16/20/25A with overcurrent rated short-circuit breaking capacity (10 kA) and earth leakage protection with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO [5-6-9]
Supplying, fixing, and commissioning 4 pole RCBO 32/40A with overcurrent rated short-circuit breaking capacity (10 kA) and earth leakage protection with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO [5-6-13]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 2 core 2.5 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-8]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 2 core 4 sq mm copper conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-9]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 4 core 10 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-33]
Providing earthing with copper earth plate size 60 x 60 x 0.315 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover with minimum 25 kg Carbon based environment friendly back fill Ground Enhancing compound complete with all materials testing & recording the results as per specification no ESE -LA [9-1-6]
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP. [9-2-2]
SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with Rated capacity - 20 Passenger/1360Kg Floors - G+7 floor (8 Stops/8 Landings) Travel - 21 to 29.4 mtrs Location of Lift Machine - MR/MRL Rated speed - 1.5mps VS Car/Landing door clear opening of 1100/1200 mm wide x 2000 mm high · Clear Car size of 1300 mm wide x 2400 mm deep x 2250mm high · Lift shaft available having clear size of 1900 mm wide x 3000 mm deep 2400 mm Pit depth 4200 mm Overhead. · Doors type - COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). · Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm thick with hairline finish with frame made from MS girders bracing of adequate size with minimum safety factor of 5 with Toe Guard Apron with necessary false ceiling with adequate LED lights blower/fan for ventilation & SS chequered plate flooring handrails mirror emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. · COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI scrolling UP/DN LED indicator & with / without attendant key switch OWD with audio-visual alarm VAS in Marathi Hindi & English with intercom system with telephone instrument in Lift car LMR & FCC/ground floor. · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI Lift car arrival & next travel direction audio-visual indication at all landings. · Lift controller of simplex full collective based on microprocessor/ PLC with VVVF Drive having closed loop control system with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent overvoltage over speed overheat for all devices including lift motor and travel direction protection protection for phase loss at input or output etc. various operation modes such as maintenance change direction by attendant full load bypass VIP call operation self levelling operation call cancel facility auto return to home landing fireman evacuation operation earthquake operation door open/close operation from COP etc. The system can record information for minimum 30 latest faults with real-time clock management and handheld keypad with LCD screen for view and setting of parameters The control panel duly wired with proper size & strength copper wire for power & control circuit with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. · ARD complete with necessary SMF VRLA batteries. · Fireman controller having fireman switch at fire Landing. · CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min. 20 FHD TV monitor to be kept in FCC/LMR as directed by Engineer In Charge. · Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory) with Traction pulley OSG electromagnetic brakes entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves suspension wire ropes/belts of adequate size & strength. · Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners counter weight frame with necessary blocks buffers with necessary support arrangement MS pit ladder etc. erected with necessary steel work. · Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill header hole pass etc complete with plaster finish civil work for erection buffers erection of lift machinery adequate size core cuts if required & scaffolding for erecting guide rails providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT. · General - Job includes entire procedure of obtaining all necessary erection permissions & License to Work the Lift from Electrical Inspector(Lifts) with submission to the Engineer In Charge. · The above rate includes Fully Comprehensive AMC for one year from the date of commissioning. [17-1-20]
SITC of Duplex Lift control system for two nos. microprocessor/PLC based simplex lift controllers along with necessary software with programming and hardware e.g. logic board necessary communication/control/data cabling laying in rigid PVC conduits/trunking etc. complete. [17-1-21]
Supplying and erecting modular type (two module) electronic step regulator for fan duly erected on provided plate and box with wiring connections complete. [1-6-23]
Supplying, erecting, testing and commissioning of 6HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant for minimum cooling capacity as delivering 100% capacity at 47° C non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00 modular type horizontal hot air discharge suitable for longer piping range upto 1000m operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area rain protection cover built in oil separator accumulator and oil receiver copper tube aluminium fin air cooled condenser condenser fan with motor suitable for 415V±10% 50 Hz 3 phase power supply (all suitable for high ambient conditions) internal copper refrigerant piping internal wiring and refrigerant etc. all housed in powder coated weather proof cabinet complete. [3-11-1]
Supplying, erecting, testing and commissioning of 10HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant for minimum cooling capacity as delivering 100% capacity at 47° C non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00 modular type vertical hot air discharge suitable for longer piping range upto 1000m operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area rain protection cover built in oil separator accumulator and oil receiver copper tube aluminium fin air cooled condenser condenser fan with motor suitable for 415V±10% 50 Hz 3 phase power supply (all suitable for high ambient conditions) internal copper refrigerant piping internal wiring and refrigerant etc. all housed in powder coated weather proof cabinet complete. [3-11-3]
Supplying, erecting, testing and commissioning of 12HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant for minimum cooling capacity as delivering 100% capacity at 47° C non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00 modular type vertical hot air discharge suitable for longer piping range upto 1000m operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area rain protection cover built in oil separator accumulator and oil receiver copper tube aluminium fin air cooled condenser condenser fan with motor suitable for 415V±10% 50 Hz 3 phase power supply (all suitable for high ambient conditions) internal copper refrigerant piping internal wiring and refrigerant etc. all housed in powder coated weather proof cabinet complete. [3-11-4]
Supplying, erecting, testing and commissioning of 16HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant for minimum cooling capacity as delivering 100% capacity at 47° C non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00 modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area rain protection cover built in oil separator accumulator and oil receiver copper tube aluminium fin air cooled condenser condenser fan with motor suitable for 415V±10% 50 Hz 3 phase power supply (all suitable for high ambient conditions) internal copper refrigerant piping internal wiring and refrigerant etc. all housed in powder coated weather proof cabinet complete. [3-11-6]
Supplying, erecting, testing and commissioning of 18HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant for minimum cooling capacity as delivering 100% capacity at 47° C non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00 modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/ digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area rain protection cover built in oil separator accumulator and oil receiver copper tube aluminium fin air cooled condenser condenser fan with motor suitable for 415V±10% 50 Hz 3 phase power supply (all suitable for high ambient conditions) internal copper refrigerant piping internal wiring and refrigerant etc. all housed in powder coated weather proof cabinet complete. [3-11-7]
Supplying, erecting, testing and commissioning of 20HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant for minimum cooling capacity as delivering 100% capacity at 47° C non stop cooling even at 56°C and coefficient of performance (COP) 3.00 to 4.00 modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area rain protection cover built in oil separator accumulator and oil receiver copper tube aluminium fin air cooled condenser condenser fan with motor suitable for 415V±10% 50 Hz 3 phase power supply (all suitable for high ambient conditions) internal copper refrigerant piping internal wiring and refrigerant etc. all housed in powder coated weather proof cabinet complete. [3-11-8]
Supplying, erecting, testing and commissioning of 26HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant for minimum cooling capacity as delivering 100% capacity at 47° C non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00 modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area rain protection cover built in oil separator accumulator and oil receiver copper tube aluminium fin air cooled condenser condenser fan with motor suitable for 415V±10% 50 Hz 3 phase power supply (all suitable for high ambient conditions) internal copper refrigerant piping internal wiring and refrigerant etc. all housed in powder coated weather proof cabinet complete. [3-11-11]
Supplying, erecting, testing and commissioning of 28HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant for minimum cooling capacity as delivering 100% capacity at 47° C non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00 modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area rain protection cover built in oil separator accumulator and oil receiver copper tube aluminium fin air cooled condenser condenser fan with motor suitable for 415V±10% 50 Hz 3 phase power supply (all suitable for high ambient conditions) internal copper refrigerant piping internal wiring and refrigerant etc. all housed in powder coated weather proof cabinet complete. [3-11-12]
Supplying, erecting, testing and commissioning of VRF/VRV based Hi-wall type room/indoor unit (IDU) of nominal cooling capacity 1.0TR (358 cfm) to 1.25TR (417 cfm) having EER as per BEE standards and specifications with multiple speed evaporator fan with motor copper tube aluminium fin evaporator coil washable air filter insulated drain tray in built drain pump expansion device cordless remote control with necessary controls and electrical terminal to receive power supply etc. IDU shall have anti-corrosive coating suitable for coastal area. Unit shall be of decorative slim dimension suitable indoor wall mounting. The indoor unit shall also have an electronic control console. The unit shall be suitable for wall mounting and provided with suitable mounting brackets with any additional refrigerant and oil charge as per requirement during installation complete. [3-11-14]
Supplying, erecting, testing and commissioning of VRF/VRV based Hi-wall type indoor unit (IDU) of nominal cooling capacity 1.3TR (421 cfm) to 1.7TR (586 cfm) having EER as per BEE standards and specifications with multiple speed evaporator fan with motor copper tube aluminium fin evaporator coil washable air filter insulated drain tray expansion device cordless remote control with necessary controls with 3-core copper flexible cord of required length and electrical terminal to receive power supply etc. IDU shall have anticorrosive coating suitable for coastal area. Unit shall be suitable for indoor wall mounting having an electronic control console provided with suitable mounting brackets with any additional refrigerant and oil charge as per the requirement during installation connected to the system complete. [3-11-15]
Supplying, erecting, testing and commissioning of VRF/VRV based Hi-wall type indoor unit (IDU) of nominal cooling capacity 1.8TR (594 cfm) to 2.2TR (655 cfm) having EER as per BEE standards and specifications with multiple speed evaporator fan with motor copper tube aluminium fin evaporator coil washable air filter insulated drain tray expansion device cordless remote control with necessary controls with 3-core copper flexible cord of required length and electrical terminal to receive power supply etc. IDU shall have anticorrosive coating suitable for coastal area. Unit shall be suitable for indoor wall mounting having an electronic control console provided with suitable mounting brackets with any additional refrigerant and oil charge as per the requirement during installation connected to the system complete. [3-11-16]
Supplying, installing, testing and commissioning of split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor room air conditioning unit 1.0TR to 1.2TR capacity having ISEER minimum 3.8 to maximum 4.39 suitable to operate on 250V 50 Hz A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser minimum 2.5PM filter self diagnosis feature stabilizer free operation & temperature display on indoor unit noise level maximum 50dBA at position as per specification no. APAC/ WAC [3-2-8]
Supplying, installing, testing and commissioning of split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor room air conditioning unit 1.3TR to 1.6TR capacity having ISEER minimum 3.8 to maximum 4.39 suitable to operate on 250V 50 Hz A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser minimum 2.5PM filter self diagnosis feature stabilizer free operation & temperature display on indoor unit noise level maximum 50dBA at position as per specification no. APAC/ WAC [3-2-10]
Supplying, installing, testing and commissioning of split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor room air conditioning unit 1.7TR to 2.0TR capacity having ISEER minimum 3.8 to maximum 4.39 suitable to operate on 250V 50 Hz A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32 having copper condenser minimum 2.5PM filter self diagnosis feature stabilizer free operation & temperature display on indoor unit noise level maximum 50dBA at position as per specification no. APAC/ WAC [3-2-12]
Supplying, installing, testing and commissioning of split type room air conditioning unit 2.5TR to 2.7TR capacity with refrigerant R32 415V 50 Hz A.C. supply having 1 no of air handling unit (Mega split) mounting type complete with temperature display on indoor unit noise level maximum 50dBA at position as per specification no. AP-AC/WAC [3-2-15]
Supplying, erecting, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact / standard size) of nominal cooling capacity 3.0TR (1100 cfm) to 3.2TR (1165 cfm) having EER as per BEE standards and specifications suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements fan refrigerant liquid and refrigerant piping cordless remote control and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase 230V 50Hz AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation. [3-11-22]
Supplying, erecting, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact / standard size) of nominal cooling capacity 3.3TR (1165 cfm) to 4.0TR (1218 cfm ) having EER as per BEE standards and specifications suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements fan refrigerant liquid and refrigerant piping cordless remote control and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase 230V 50Hz AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation. [3-11-23]
Supplying, erecting, testing and commissioning of VRF/VRF based concealed split ductable type high static room/indoor unit (IDU) having nominal cooling capacity of 0.8TR (280 cfm) to 1.1TR (400 cfm) having EER as per BEE standards and specifications with evaporator fan with motor copper tube aluminium fin evaporator coil washable air filter insulated drain tray in built drain pump expansion device cordless remote control with necessary controls and electrical terminal to receive power supply etc. IDU shall have anti-corrosive coating suitable for coastal area. Unit shall be of decorative slim dimension suitable for ceiling suspended having an electronic control console with providing any additional refrigerant and oil charge as per requirement during installation complete. [3-11-36]
Supplying, erecting, testing and commissioning of VRF/VRF based concealed split ductable type high static room/indoor unit (IDU) having nominal cooling capacity of 1.8TR (600 cfm) to 2.0TR (800 cfm) having EER as per BEE standards and specifications with evaporator fan with motor copper tube aluminium fin evaporator coil washable air filter insulated drain tray in built drain pump expansion device cordless remote control with necessary controls and electrical terminal to receive power supply etc. IDU shall have anti-corrosive coating suitable for coastal area. Unit shall be of decorative slim dimension suitable for ceiling suspended having an electronic control console with providing any additional refrigerant and oil charge as per requirement during installation complete. [3-11-38]
Supplying, erecting, testing and commissioning of VRV/VRF based ceiling suspended 4.0TR treated fresh air (TFA) (3310 cfm) room/IDU with evaporator fan with motor copper tube aluminium fin evaporator coil washable air filter insulated drain tray in built drain pump expansion device cordless remote control with necessary controls and electrical terminal to receive power supply etc. having anti-corrosive coating suitable for coastal area with decorative slim dimension suitable ceiling suspended arrangement and an electronic control console with any additional refrigerant and oil charge as per requirement during installation complete. [3-11-57]
Supplying, erecting, testing and commissioning of fresh air intake system ductable circular inline fresh air fan inlet unit having 1000 cfm capacity with maintaining the static pressure minimum 20mm suitable to operate on 1ph 230 V 50Hz A.C. supply complete. [3-11-61]
Supplying, erecting, testing and commissioning of air curtain of 6 feet width having air throw velocity of 21 m/sec low noise level up to 38 to 46dBA suitable for door height upto 9 feet working on 1 phase 230V 50Hz A.C. supply. [3-11-76]
SITC OF HEPA Plenum withSS 304 Diffuser grill & Terminal HEPA Filters For Ophthalmic OT Plenum designed as per NABH standards 1.Plenum MOC Stainless steel 304 2.Plenum Size 2620mm x2620mm [8 ft x 8 ft] 3.Plenum Diffuser Grill The high quality S.S.304 Diffuser grill for securing unidirectional air flow according to EN ISO 14644. SS 304 grill designed to deliver uniform air velocity across the entire HEPA plenum to maintain uniform air displacement on the OT table. 4.Central Opening Plenum design with opening for OT lamp nor more than 300*300 with cover plate 5.Filter housing and pressure chamber MOC stainless steel 304 matt polish thickness 1.2 mm. 6.Filter section - Mini-pleat (H14) grade HEPA Filters placed as Terminal Filters NON CSR [999-1-7]
Supply installation testing and comissiong of Return Air Risers made out from SS 304 perforated grilles not less than 70% free area for air passage hidden nut & bolt flanges all corner well covered etc.front face of grille shall be flushed with wall complete arrangement shall be leakproof with volume control dampers filters etc. complete as required. (NON CSR) [999-1-8]
Carrying out core cutting of size 3 to 5 dia x 15 length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. [3-11-77]
Supplying, erecting, testing and commissioning of wireless remote control having colour LCD panel real time clock temperature limitation (16 to 30° C functions like filter clean reminder timer suitable to communicate with wired controller complete. [3-11-78]
Supplying, erecting, testing and commissioning of centralised programmable remote control panel (HMI) touch manager controls minimum 16 system of 64 ODU's can be controlled and up to 992 IDU's can be individually mounted and controlled indoor units having colour min 200mm size LCD touch panel yearly schedule power proportional distribution function temperature limitation history function complete erected on wall integrated with provided fire alarm system. [3-11-79]
Supplying and installing of high pressure grade required size copper connection Y or T- Joints/refnet complete erected on wall/ceiling with supports/raceways Nitrile rubber insulation painting etc. with brazing and testing for leakages confirming the normal operation of the VRV/VRF air conditioning system. [3-11-86]
Providing vaccumising the airconditioner system to 200 micron and charging with refrigerant R32 for AC unit. [3-10-24]
Supplying, laying / fixing, testing and commissioning of of appropriate nominal refrigerant copper pipe of 34.9mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports hangers clamps vibration isolators and fittings such as bends tees valves gauges strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages fungal growth flame spread water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete. [3-11-90]
Supplying, laying / fixing, testing and commissioning of of appropriate nominal refrigerant copper pipe of 28.6mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports hangers clamps vibration isolators and fittings such as bends tees valves gauges strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages fungal growth flame spread water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete. [3-11-91]
Supplying, laying / fixing, testing and commissioning of of appropriate nominal refrigerant copper pipe of 22.2mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports hangers clamps vibration isolators and fittings such as bends tees valves gauges strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages fungal growth flame spread water permeance and ultraviolet radiation with OEM standards of VRV/VRF air conditioning system complete. [3-11-92]
Supplying, laying / fixing, testing and commissioning of of appropriate nominal refrigerant copper pipe of 19.1mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports hangers clamps vibration isolators and fittings such as bends tees valves gauges strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages fungal growth flame spread water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete. [3-11-93]
Supplying, laying / fixing, testing and commissioning of of appropriate nominal refrigerant copper pipe of 15.9 mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports hangers clamps vibration isolators and fittings such as bends tees valves gauges strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages fungal growth flame spread water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete. [3-11-94]
Supplying, laying / fixing, testing and commissioning of of appropriate nominal refrigerant copper pipe of 12.7mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports hangers clamps vibration isolators and fittings such as bends tees valves gauges strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages fungal growth flame spread water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete. [3-11-95]
Supplying, laying / fixing, testing and commissioning of of appropriate nominal refrigerant copper pipe of 9.5 mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports hangers clamps vibration isolators and fittings such as bends tees valves gauges strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages fungal growth flame spread water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete. [3-11-96]
Supplying, laying / fixing, testing and commissioning of of appropriate nominal refrigerant copper pipe of 6.4mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports hangers clamps vibration isolators and fittings such as bends tees valves gauges strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages fungal growth flame spread water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete. [3-11-97]
Supplying and erecting GI sheet 0.6 mm (24 SWG) having zinc coating of 275 microns with galvanization process compliance to IS 2629 1985 to be used for fabrication of boxes panel boards etc. including cutting bending drilling welding riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint. [6-1-2]C
Supplying and erecting GI sheet 0.8 mm (22 SWG) having zinc coating of 275 microns with galvanization process compliance to IS 2629 1985 to be used for fabrication of boxes panel boards etc. including cutting bending drilling welding riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint. [6-1-3]
Supplying and erecting GI sheet 1 mm (20 SWG) having zinc coating of 275 microns with galvanization process compliance to IS 2629 1985 to be used for fabrication of boxes panel boards etc. including cutting bending drilling welding riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint. [6-1-4]
Supplying, erecting, testing and commissioning of volume control box with collar for control damper of required sizes in GI construction with operating mechanism mounting arrangement rubber refrigerant kits etc. complete. [3-11-81]
Supplying and installing of high pressure grade required size copper connection Y or T- Joints/refnet complete erected on wall/ceiling with supports/raceways Nitrile rubber insulation painting etc. with brazing and testing for leakages confirming the normal operation of the VRV/VRF air conditioning system. [3-11-86]
Supplying and erecting aluminium powder coated linear grill of suitable size for width length without collar dampers having matching colour with the existing false ceiling and suitable for deflection of 15/30/45°. [3-11-88]
Supplying and erecting 25/32 mm (ID/OD) Chlorinated polyvinyl chloride pipe (CPVC) thickness 3.2 mm conforming to IS 15778 (CTS Series) with necessary CPVC fittings and solvent cement for Solar Water Heater System as per specification No. ESD-HWP/CPVC [4-2-19]
Supplying and erecting 32/40 mm (ID/OD) Chlorinated polyvinyl chloride pipe (CPVC) thickness 3.8 mm conforming to IS 15778 (CTS Series) with necessary CPVC fittings and solvent cement for Solar Water Heater System as per specification No. ESD-HWP/CPVC [4-2-20]
Supplying and erecting elastomeric nitrile rubber / foam tube type sleeves for coating and insulating on provided PC / copper pipes having 9 mm thickness and inner diameter / sizes 22 mm for solar water heater/AC system. [4-2-12]
Supplying and erecting elastomeric nitrile rubber / foam tube type sleeves for coating and insulating on provided PC / copper pipes having 9 mm thickness and inner diameter / sizes 28 mm for solar water heater/AC system. [4-2-13]
Supplying and erecting elastomeric nitrile rubber / foam tube type sleeves for coating and insulating on provided PC / copper pipes having 9 mm thickness and inner diameter / sizes 32 mm for solar water heater/AC system. [4-2-14]
Supply, fabrication, installation and testing of flexible canvas connections constructed between ductable unit/dampers/ducting of suitable size with fire resist flexible double canvas sleeve complete. [3-11-82]
Providing adhesive thermal insulation for supply return air duct with 19mm nitrile rubber insulation having R-value as per the prevailing provisions in ECBC-2017. [3-11-83]
Providing & applying of acoustic insulation for air ducts with 25mm thick 48 kg/cu.m fiber glass faced with RP tissue and covered with 26 SWG perforated aluminium sheets complete. [3-11-84]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SP/TP MCBs total 8 ways /24 poles with door 1.2mm thickness surface/flush mounted IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB [5-4-5]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SP/TP MCBs total 4 ways /12 Poles with door 1.2mm thickness surface/flush mounted IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB [5-4-4]
Supplying and erecting single pole and neutral distribution board (SPNDB) with 2 ways for incoming and 10 ways (10 poles) for outgoing SP MCBs with door 1.2mm thickness surface / flush mounted IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB [5-4-9]
Supplying, fixing, and commissioning 4 pole RCBO 32/40A with overcurrent rated short-circuit breaking capacity (10 kA) and earth leakage protection with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO [5-6-13]
Supplying, erecting and marking TPMCB 6A to 32A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-10]
Supplying, erecting and marking SPMCB 6A to 32A C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-2]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 4 core 6 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-32]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 4 core 10 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-33]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 4 core 16 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-34]
Supplying and erecting PVC insulated PVC round sheathed 1.5 sq.mm (30 no. x 0.25 mm dia.) 3 core flexible multi stranded copper Industrial cable for voltage grade up to 1.1 kV [1-3-14]
Supplying and erecting 12V/100Ah SMF battery with battery terminal wire, duly charged with 24 months warranty complete.
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No WG-MA/CC [1-1-9]
Supplying 16 amp. 3 pin plug Top bakelite type of 230 V. A.C. supply. [1-5-17]
Providing and erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware. [7-11-6]
Supplying, installing & testing maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete and recording the results Specification no. EA-MOBI [9-1-5]
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. [9-2-3]
Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete. [9-2-5]
Supplying and erecting integrated LED street light fitting 40 to 50W IP65 & IK08 class having single piece pressure die-cast aluminium housing having system lumens output of Min. 4400 Lumens min. efficacy of 110 lumen/W CRI>70 CCT upto 6500K THD<10% p.f. >0.95 operating range of 140-270V inbuilt surge protection of 10 kV Life class of 50 000 Hrs. at L70B50 including driver complete with 3 Years warranty as per specification No FG-ODF/FLS2. [2-4-4]
Supplying and erecting PVC insulated PVC round sheathed 1.5 sq.mm (30 no. x 0.25 mm dia.) 3 core flexible multi stranded copper Industrial cable for voltage grade up to 1.1 kV [1-3-14]
Supplying, erecting and marking SPMCB 6A to 32A B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-3]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 4 core 6 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-27]
Supplying and laying (including excavation) of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface to required depth complete. [7-6-9]
Providing and erecting 6 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL [8-2-12]
Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT [8-2-21]
Providing and erecting galvanised 1000mm double arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT [8-2-22]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials testing & recording the results as per specification no. EA-EP [9-1-1]
Providing pipe type earthing with 40mm. dia. G.I. pipe or 20 mm dia. G.I. Rod complete with all materials testing and recording the results as per specification no. EA-EP [9-1-4]
Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5 m depth including supply of steel concrete excavation and fixing provided nut bolts with the help of template duly plastered as per design complete (for 6m to 8m high octagonal /conical GI pole). [16-3-9]
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. [9-2-3]
Supplying, erecting and marking DPMCB 6A to 32A C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-6]
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with PVC accessories on wall /ceiling as per specification No WG-MA/CON. [1-2-4]
Supplying, erecting and marking TPMCB 6A to 32A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-10]
Supplying, erecting and marking FPMCB 40A to 63A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-13]
Supplying, fixing, and commissioning MCB type change over switch 4 pole 25A with 3 positions (I-O-II) with centre off position as per specification no. SW-SWR / MCBCOS [5-3-24]
Supplying and erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame. [5-4-13]
Supplying and erecting marine (Waterproof) plywood 18/19 mm thick fixed to wall or on provided panel board with necessary materials such as screws wall fasteners supports nut bolts etc. complete with compliance to IS 720 2010 [6-1-14]
Supplying and erecting iron work sheet metal work consisting of CRCA sheets various sections of iron plates chequered plates rods bars MS pipes etc. for panel board or any other purpose with bending cutting drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. [6-1-19]
Supplying and erecting minimum Three & above star rated 3 phase 415 V 50 Hz submersible pump set of 7.5 KW/10HP suitable for erection on open well pump having delivery head from 72 to 28 m and discharge from 120 to 840 litres. per minute & pipe of Suction 65 mm/Delivery 50 mm diameter erected with necessary H type clamps as per specification No. WP-OSP [12-3-7]
Supplying and erecting flat flexible 3 core 2.5 sq.mm PVC sheathed submersible type copper cable suitably clamped at fixed intervals with column pipe assembly complete. [12-4-8]
Supplying and erecting Water level controller 230/415 V A.C. Four way under ground & Over head tank operation only. [12-4-15]
Supplying and erecting PVC coated 5 mm dia. Brass sensor/ electrode duly wired with nuts & bolts complete (Set of 3 Nos) [12-4-16]
Supplying and erecting automatic control panel for 3 Ph 415 volt A.C. Submersible/centrifugal pump set up to 7.5 HP - 10 H.P. consisting of DOL starter having relay range 13-21 AMP S.P.P. Combined ammeter/voltmeter phase indicating lamp enclosed in CRCA powder coated Vibration proof enclosure with IP 54 protection. Control Panel should offer single phasing phase reversal phase imbalance etc. [12-4-18]
Supplying and erecting ISI mark GI pipe 50 mm dia.‘B’ class at position with accessories complete as per specification no. CW-PLB/GP. [16-5-6]
Supplying and erecting 50 mm dia. gun metal sluice valve at position with necessary materials complete. [16-6-15]
Supplying and erecting non return valve 50 mm dia in position made of gun metal complete. [16-6-21]
Supplying and laying HMS PVC conduit FRLS grade 32mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC [1-1-12]
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting green colour earthing with 1x 1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete. [1-6-1]
Supplying and erecting modular type 3 pin 6A multi socket with safety shutter duly erected on provided plate and box with wiring connections complete. [1-6-10]
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected. [1-6-28]
Supplying and installing cat-6 cable suitable for networking as per specification no. WG-COC/NC [1-10-1]
Supplying and installing cat-6 armoured cable with ECCS tape suitable for networking as per specification No. WG-COC/NC [1-10-7]
Supplying, fixing, and configuring 8-ports 1 G unmanaged gigabit POE switch erected in provided rack complete. [1-11-1]
Supplying, installing & testing UTP connector (RJ-45) as per specification No. WG-NAS/UTPC. [1-12-1]
Supplying and fixing 9U wall mount rack (Dimension-DxWxH – 500x600x500 mm) as per specification No. WG-NAS/RAK [1-12-18]
Supplying and erecting 12V/42Ah SMF battery with battery terminal wire duly charged with 24 months warranty complete [3-8-10]
Supplying, installing, testing and commissioning of 2kVA capacity online pure sine wave with backup time of ....... hrs. PWM & IGBT based UPS with 0.8 to unity output pf single phase input & 1 phase output complete with all protections as per specification no. AP-UPS [3-7-2]
Supplying & erecting 8 TB internal Surveillance HDD suitable for SATA Port of NVR interface transfer rate 6 GB/S maximum sustained transfer rate 210 MB/Sec to 213 MB/S. Drive bay supported 08+ Cameras supported up to 64 Cache (MB) 256 Load/Unload Cycle -3000000 Work Load Rating per Year 180TB MTBF 1000000 Hrs. HTTPS. RoHS UL CE certified duly erected in position in provided NVR as per specification no. CCTV-HDD (NON CSR) [2-1-14]
Supplying installing testing & commissioning of 64/80 Ch Network Video Recorder (NVR) suitable connect Min. 64 IP Cameras up to 5 Megapixel Resolution with HDMI 1/VGA 1 and HDMI 2/VGA 2 outputs provided Atleast one HDMI output of 4K resolution atleast one VGA output with output up to 1920 × 1080 Support H.265 or higher H.264 MJPEG Supports Redundant Dual Power Incoming Bandwidth 320 Mbps with minimum 8 SATA Hard Disks ANR Technology 8 SATA interfaces for 8 HDDs and capacity of each HDD up to 8TB minimum 02 USB port Alarm I/O 16/4 RJ-45 10/100/ 1000 Mbps self adaptive Ethernet interface support multi brand network Cameras ONVIF conformance Multiple network monitoring Web viewer . support protocol TCP/IP DHCP DNS DDNS NTP SADP SMTP NFS iSCSI UPnP™ HTTPS. RoHS UL CE FCC certified. duly erected in provided U Rack with wiring connections tagging and programming etc. complete as per specificationss no. CCTV-NVR (NON CSR) [2-1-16]
Supplying & erecting of High definition 4/5 Megapixel IP IR PTZ Camera with following features Image Sensor minimum 1/2.8 Progressive Scan CMOS Video Resolution inimum 2880 x 1620 Video Compression H.264 H.265 or higher at least Three individually configurable stream Frame Rate minimum 30 fps at all resolutions WDR minimum 120 dB Wide Dynamic Range ONVIF profile conformant. Auto Tracking Pre-set Tour Settings Pan 360° endless Tilt From -15° to 90° (auto-flip 180°) minimum Pan Speed - from 0.1°/s to 160°/s minimum Preset Speed 240°/s minimum Tilt Speed - from 0.1°/s to 120°/s minimum Preset Speed 200°/s Min Presets- 250 Min IR distance 150m Lens Type minimum 4.3 - 12.5mm Lens min 16 x digital zoom min 30 x optical Zoom. Focus Mode Auto/Zooming/One Push Manual Lux sensitivity- minimum 0.2 Lux at color minimum 0.05 Lux at Black & White 0.0 Lux (IR) Night Vision Distance Min IR- 50m Power Supply support 12/24 VDC 24 VAC & PoE IP67/IP66 IK10 built in micro D/SDHC/SDXC card slot minimum 256 GB built in microphone. minimum Input/Output Audio in × 1 Audio Out × 1 Alarm in× 1 Alarm Out × 1. Image Settings Rotate mode saturation brightness contrast sharpness gain white balance. Image Enhancements Day/Night-Auto (ICR)/Color/Black & White 3D Digital Noise Reduction Automatic White Balance Automatic Gain Control Backlight Compensation Highlight Compensation (NON CSR) [2-1-20]
Supplying & erecting of High definition 4/5 Megapixel IP IR Dome Camera with following features Image Sensor minimum 1/2.8 Progressive Scan CMOS Video Resolution minimum 2592 x 1520 Video Compression H.264 H.265 or higher at least Three individually configurable stream Frame rate minimum 25 fps at all resolutions WDR minimum 120 dB Wide Dynamic Range ONVIF profile conformant minimum IR distance 50m Lens Type 2.8/4/6 mm Lens fixed focal Field of View 2.8 mm horizontal FOV 107° vertical FOV 57° diagonal FOV 129° 4 mm horizontal FOV 86° vertical FOV 47° diagonal FOV 102° 6 mm horizontal FOV 55° vertical FOV 29° diagonal FOV 65° Lux sensitivity - minimum 0.2 Lux at color minimum 0.05 Lux at Black & White 0.0 Lux (IR) Night Vision Distance minimum IR - 50m. Camera minimum Adjustment Angles - Pan 350° Tilt 72° Rotate 350°. Power Supply Support 12VDC & PoE IP67 IK10 - Vandal Resistant. Built in micro SD/SDHC/SDXC card slot of minimum 128 GB Built in microphone. minimum Input/Output - Audio in × 1 Audio Out × 1 Alarm in × 1 Alarm Out × 1. Image Settings Rotate mode saturation brightness contrast sharpness gain white balance. Image Enhancements Day/Night-Auto (ICR)/Color/Black & White 3D Digital Noise Reduction Automatic White Balance Automatic Gain Control Backlight Compensation Highlight Compensation. Events Privacy Masking Motion detection Scene change detection Face capture Video tampering audio exception detection Region entrance detection Region exiting detection. Operating temperature ( -30 to 60° C ) . Security - User account and password protection HTTPS IP filter IEEE 802.1X digest authentication user access log TLS1.2 AES - 256 SSH/Telnet closed FTP disabled. Protocol - DHCP UDP HTTP HTTPS NTP DNS RTP RTSP SMTP SSL/TLS TCP/IP Secure Real-Time Transport Protocol (SRTP) Bonjour SNMP and Secure shell (SSH) supported protocol. RoHS WEEE ISO-14001 and REACH compliant UL/EN OR equivalent BIS/TECH/STQC or any indian standards as applicable CE FCC certified. duly erected in position on wall/ceiling/false ceiling/provided pole (mounting height not more than 5 meter) etc with all accessories etc complete as per specification no. CCTV-CAM. (NON CSR) [30-1-475]
Supplying & erecting of High definition 4/5 Megapixel IP IR Bullet Camera with following features Image Sensor minimum 1/2.8 Progressive Scan CMOS Video Resolution minimum 2592 x 1520 Video Compression H.264 H.265 or higher at least Three individually configurable stream Frame rate minimum 25 fps at all resolutions WDR minimum 120 dB Wide Dynamic Range ONVIF profile conformant minimum IR distance 50m Lens Type 2.8/4/6 mm Lens fixed focal Field of View 2.8 mm horizontal FOV 107° vertical FOV 57° diagonal FOV 129° 4 mm horizontal FOV 86° vertical FOV 47° diagonal FOV 102° 6 mm horizontal FOV 55° vertical FOV 29° diagonal FOV 65° Lux sensitivity - minimum 0.2 Lux at color minimum 0.05 Lux at Black & White 0.0 Lux (IR) Night Vision Distance minimum IR - 50m. Camera minimum Adjustment Angles - Pan 350° Tilt 72° Rotate 350°. Power Supply Support 12VDC & PoE IP67 IK10 - Vandal Resistant. Built in micro SD/SDHC/SDXC card slot of minimum 128 GB Built in microphone. minimum Input/Output - Audio in × 1 Audio Out × 1 Alarm in × 1 Alarm Out × 1. Image Settings Rotate mode saturation brightness contrast sharpness gain white balance. Image Enhancements Day/Night-Auto (ICR)/Color/Black & White 3D Digital Noise Reduction Automatic White Balance Automatic Gain Control Backlight Compensation Highlight Compensation. Events Privacy Masking Motion detection Scene change detection Face capture Video tampering audio exception detection Region entrance detection Region exiting detection. Operating temperature ( -30 to 60° C ) . Security - User account and password protection HTTPS IP filter IEEE 802.1X digest authentication user access log TLS1.2 AES - 256 SSH/Telnet closed FTP disabled. Protocol - DHCP UDP HTTP HTTPS NTP DNS RTP RTSP SMTP SSL/TLS TCP/IP Secure Real-Time Transport Protocol (SRTP) Bonjour SNMP and Secure shell (SSH) supported protocol. RoHS WEEE ISO-14001 and REACH compliant UL/EN OR equivalent BIS/TECH/STQC or any indian standards as applicable CE FCC certified. duly erected in position on wall/ceiling/false ceiling/provided pole (mounting height not more than 5 meter) etc with all accessories etc complete as per specification no. CCTV-CAM (NON CSR) [30-1-477]
Supplying & erecting 55 professional LED display with 1920 *1080 ( Full HD) Display suitable for 32/64 channel NVR and following features Brightness minimum 500 Cd/m2 Contrast Ratio minimum 1000 1 Viewing angle 178/178 deg. Response time maximum 8 ms Inputs HDMI VGA BNC USB Audio In Built-in speakers maximum 10 W Suitable to operate on 100-240 V 50 Hz AC supply and 24/7 Duty Cycle duly erected on wall or table top with standard accessories like wall mount stand and wiring connections etc. complete as per specifications no. CCTV-MON [NON CSR] [2-1-15]
Supplying and erecting 3m HDMI cord low voltage grade minimum 4k compliant to be laid in provided conduits with male/female 19 pin HDMI connectors complete. [1-8-21]
Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes panel boards etc. including cutting bending drilling welding riveting treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete. [6-1-1]
Supplying and erecting iron work sheet metal work consisting of CRCA sheets various sections of iron plates chequered plates rods bars MS pipes etc. for panel board or any other purpose with bending cutting drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. [6-1-19]
Supplying, installing, testing and commissioning of 20 kWp ON-GRID Solar PV System / Plant consisting Solar PV Poly Crystalline Panel (335 Wp X 60 Nos.) and Solar ON-GRID Inverter of similar capacity (THD<3%) with interconnecting wires / cables up to solar ON GRID inverter proper base plate canopy box to house Inverter and necessary accessories i.e. ACDB/ DCDB MCB etc. wiring up to solar Inverter in casing and capping display board sign board two distinct earthing lightning arrester liaisoning charges remote monitoring system with maintaining card/chip for 5 years including net charges for RMS System complete up to net meter installation and export to the grid with 5 year ON-SITE warranty and fully comprehensive maintenance contract as per Specification no. ESD-RT-ONG. [4-5-5]
Supplying and installing of Solar PV Module cleaning unit consisting of nozzles spray necessary pipes valves post electronic panel board concealed with weather proof cabinet spreading water periodically for removal of dust related motor pump controller timer and nozzles set suitable for covering 5 KW Solar PV Module. (Approx. 35 Sq. Mtr. PV Module area). [4-8-8]
Supplying and erecting SS enclosure for MCCB suitable for up to 100A MCCB. [5-11-17]
Providing and erecting 4 Pole MCCB 415 V 100A rated short-circuit breaking capacity 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and fixed magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-1]
metal work in CRCA sheet including Iron work for supports with fabrication of boxes panel boards etc. including cutting bending drilling welding riveting treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete. [6-1-1]
Supplying and erecting bus bar chamber triple pole with neutral with four aluminium bars 500V 100A having 15mm (Width) X 3 mm (Thickness) with 99.9 % aluminium purity as per E91E Grade & Current Density 0.8 A per sq. mm. compliance to IS 5082 and Enclosure fabricated with 16 SWG CRCA sheet and epoxy paint with suitable number of ways and with SMC/DMC Insulators and accessories of suitable rating complete as per specification no. CP-BB [6-2-1]
Supplying and erecting AC three phase LT CT multifunction net meter DLMS compliance of accuracy class 0.5 3 x 240V 50Hz with backlit LCD display optical port & RS 232 port (measures import kWh kVAh export kWh kVAh Net kWh kVAh V I kW 6 months history of energy load survey TOD tamper detection & logging power ON/OFF events instantaneous parameters of rating 1/5A with display in absence of power) with wiring connections and mounting hardware on provided panels complete with calibration certificate from manufacturer. [6-3-14]
Supplying and erecting LT current transformer with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates. [6-5-2]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 4 core 25 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-35]
Supplying, installing & testing maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete and recording the results Specification no. EA-MOBI [9-1-5]
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP. [9-2-2]
Making cement concrete foundation in 1 2 4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps). [16-3-5]
MSEDCL charges
Relcon Infraprojects Ltd
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf