| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹7.0 LAccepted-AOC | 1 | Accepted-AOC Valid lowest bidder | |
| 2 | 2₹7.6 L+₹39,160 (5.43%)Rejected-Finance NEAR SVN UNIVERSITY NARSINGHPUR ROAD SIRONJA SAUGOR MP 470228 | SAUGOR | SAGAR | MP | 470228 | 2 | Rejected-Finance Not Lowest Bidder | |
| 3 | 3₹8.3 L+₹1.1 L (15.6%)Rejected-Finance 84 A VIJAY NAGAR COLONY LALGHATI PO NAYAPURA BHOPAL 462032 | 462032 | 3 | Rejected-Finance Not Lowest Bidder |
Tender Value
₹7.9 L
EMD Value
₹15,800
Closing Date
1 Mar 2022, 6:00 pmClosed
Manash Kumar Das AE Civil
AGE I DHANA PIN 470228, DIST SAGAR, MP
SPECIAL REPAIRS/REPLACEMENT OF LT PANEL BOARD AT VARIOUS LOCATION UNDER AGE(I) DHANA AT DHANA MIL STN.
2022_MES_503666_1
8300/DH/51/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE I Dhana
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Assistant Garrison Engineer (I) Dhana
₹15,800
Yes
19 Mar 2022
1 Feb 2022
3 Mar 2022
1 Feb 2022
1 Mar 2022
15 Feb 2022
Amount
Supply, installation, testing and commissioning of LT Panel Made out of CRCA sheet 3.15mm thick sheet steel, outdoor type, factory made by CPRI approved manufacturer, totally enclosed, dust and vermin proof (protection Class IP 54), (front opening) with locking arrangement, double door duly compartmentalized with extended canopy at the top, the panel shall duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:-Incomer- MCCB 4P 315A 35kA-1No, Out going- MCCB 4P 200A 25kA-1No, MCCB 4P 100A 25kA -2Nos, MCCB 4P 63A 25kA -1No, main aluminum bus bar shall be of 400A TPN, all inter connections to outgoing feeders shall be made with TPN aluminum bus bar of rating not less than the current carrying capacity of the respective feeder, all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Digital Ammeter (0-400) with ASS-1No, Current transformer of rating 400/5A-3No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, including suitable size of cable lugs and PCC foundation complete all as specified and directed by Engr-in-Charge. Make of MCCB:- L&T, Schneider, ABB. Make of metering:- L&T, Elmeasure.
Supply installation testing and commissioning of LT Panel Made out of CRCA sheet 3.15mm thick sheet steel, outdoor type, factory made by CPRI approved manufacturer, totally enclosed, dust and vermin proof (protection Class IP 54), (front opening) with locking arrangement, double door compartmentalized with extended canopy at the top, the panel shall duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:-Incomer- MCCB 4P 400A 35kA1No, Out going- MCCB 4P 250A 25kA-1No, MCCB 4P 160A 25kA-1No, MCCB4P 100A 25kA-1No , MCCB4P 63A 25kA-1No, main aluminum bus bar shall be of 630A TPN, all interconnections to outgoing feeders shall be made with TPN aluminum bus bar of rating not less than the current carrying capacity of the respective feeder, all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Digital Ammeter(0-400) with ASS-1No, Current transformer of rating 400/5A-3No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1 No, including suitable size of cable lugs and PCC foundation complete all as specified and directed by Engr-in-Charge. Make of MCCB :- L&T, Schneider, ABB. Make of metering:- L&T, Elmeasure.
Supply installation testing and commissioning of LT Panel Made out of CRCA sheet 3.15mm thick sheet steel ,outdoor type, factory made by CPRI approved manufacturer, totally enclosed, dust and vermin proof (protection Class IP 54), (front opening) with locking arrangement, double door with extended canopy at the top, the panel shall be duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:- Incomer- MCCB 4P 200A 35kA-1No, Out going- MCCB 4P 160A 25kA-01No, MCCB 4P 100A 25kA-02 Nos, MCCB 4P 63A 25kA-01Nos, main aluminum bus bar shall be of 300A TPN, all interconnections to outgoing feeders shall be made with TPN aluminum bus bar of rating not less than the current carrying capacity of the respective feeder, all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Digital Ammeter(0-200) with ASS-1No, Current transformer of rating 200/5A-3No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1No including suitable size of cable lugs and PCC foundation complete all as specified and directed by Engr-in-Charge. Make of MCCB:- L&T, Schneider, ABB. Make of metering:- L&T, Elmeasure.
Supply installation testing and commissioning of LT Panel Made out of 2mm thick sheet steel ,outdoor type, the panel shall be duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:- Incomer- MCCB 4P 160A 35kA-1No, Out going- MCCB 4P 100A 25kA-1No, MCCB 4P 63A 25kA-1No, Change over switch onload type 63A 4Pole, main aluminum bus bar shall be of 250A TPN, all inter connections to outgoing feeders shall be made with TPN aluminum bus bar of rating not less than the current carrying capacity of the respective feeder, all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Digital Ammeter(0-200) with ASS-1No, Current transformer of rating 200/5A-3No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1No including suitable size of cable lugs and PCC foundation complete all as specified and directed by Engr-in-Charge. Make of MCCB :- L&T, Schneider, ABB. Make of metering:- L&T, Elmeasure.
Supply installation testing and commissioning of LT Panel Made out of 2mm thick sheet steel ,outdoor type, the panel shall be duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:- Incomer- MCCB 4P 200A 35kA-1No, Out going- MCCB 4P 160A 25kA-01No, MCCB 4P 100A 25kA-2No, main aluminum bus bar shall be of 250A TPN, all inter connections to outgoing feeders shall be made with TPN aluminum bus bar of rating not less than the current carrying capacity of the respective feeder, all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Digital Ammeter(0-200) with ASS-1No, Current transformer of rating 200/5A-3No,Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1No, including suitable size of cable lugs and PCC foundation complete all as specified and directed by Engr-in-Charge. Make of MCCB:- L&T, Schneider, ABB. Make of metering:- L&T, Elmeasure.
Supply installation testing and commissioning of LT Panel Made out of 2mm thick sheet steel, outdoor type, the panel shall be duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:- Incomer- MCCB 4P 160A 35kA-1No, Out going- MCCB 4P 100A 25kA-01No, MCCB 4P 63A 25kA-1No, main aluminum bus bar shall be of 300A TPN, all inter connections to outgoing feeders shall be made with TPN aluminum bus bar of rating not less than the current carrying capacity of the respective feeder, all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Digital Ammeter (0-200) with ASS-1No, Current transformer of rating 200/5A-3No,Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1No, including suitable size of cable lugs and PCC foundation complete all as specified and directed by Engr-in-Charge. Make of MCCB :- L&T, Schneider, ABB. Make of metering:- L&T, Elmeasure.
Earthing complete with galvanized iron or steel plate electrode 600 mm x 600 mm x 6 mm buried directly in ground vertically in pit of depth not less than 2.25 meter below normal ground level with top edge of the earth plate at a depth not less than 1.5 meter below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 32x6mm by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 15 mm bore dia (light grade) connected to main switch board all as shown in electrical plate No. 3 of SSR-1991 Part I and including necessary excavation and earth work, 20 mm bore light grade GI pipe for watering funnel wire mesh, PCC type C-1 chamber, CI cover and MS frame etc., complete all as specified. Note: The unit rate includes earth strip and protection pipe up to (maximum 7.5 metre from earth plate) earth point/test point.
Taking down old unserviceable LT panel complete with MCCBs and Bus Bar of any type any size complete all as specified and directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3.5 core with nominal cross sectional area of main conductor 240 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Excavation in trenches in hard/ dense soil not exceeding 1.5mtr deep and not exceeding 1.5mtr wide for laying of cables, RCC /steel tubular pole/stay and struts etc getting out including trimming sides and forming bottom surface complete all as specified and directed.
Returning, filling in including spreading, levelling, watering and well ramming excavated soil in layer not exceeding 25cm thick each back in trenches after cables have been laid and tested, poles, stays, struts have been erected and tested complete all as specified and directed.
Removal of excavated surplus material to distance not exc. 50meter away in layer not exceeding 25cm from the starting point all as directed by Engr-in-Charge.
Material & Labour for old size sub class 'B' bricks straight or curved on plan exc. 6 meter mean radius for cable cover, complete all as specified and directed.
Material & Labour for dry sand cushioning to UG cable with a layer of sand of 8 cm thick before laying of cable and 15 cm thick after laying of cable to full width of trenches complete all as specified and directed. Note:- For the purpose of payment only punned thickness will be measured.
NOTE :- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs 24,700.00 /- ]
M/S JAINENDRA KUMAR JAIN
POONAM ELECTRIC INDUSTRY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .