Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.6 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹48.0 L+₹11.1 L (29.9%)Rejected-Finance BENGALURU URBAN KARNATAKA 560049 INDIA UDYAM KR 03 0026295 | BENGALURU URBAN | KARNATAKA | 560049 | L2 | Rejected-Finance Not Lowest | |
| 3 | Rejected-Technical H NO 1 6 5 5 PLOT NO 5 3RD FLOOR GANAPATHI ARCADE SRIRAM NAGAR COLONY KAPRA ECIL POST SECUNDERABAD MEDCHAL MALKAJGIRI TELANGANA 500062 KAPRA HYDERABAD TELANGANA 500062 UDYAM TS 09 0007678 | MEDCHAL MALKAJGIRI | TELANGANA | 500062 | - | Rejected-Technical Not recommended due to insufficient documents |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
16 Jun 2021, 6:00 pmClosed
GE I R and D Kanchanbagh
GE I R and D Kanchanbagh Kanchanbagh Post Hyderabad 500058
OUTSOURCING OF 11KV/0.433KV MANNING SERVICES AND MAINTENANCE OF SERVICE CENTRE, HT EQUIPMENT AND OTHER ELECTRICAL WORKS AT DRDO TOWNSHIP KANCHANBAGH, HYDERABAD
2021_MES_444475_1
GE I KBAGH TOKEN 04 OF 2021 2022
Open Tender
Civil Works
Item Rate
330 days
Hyderabad
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I R and D Kanchanbagh
₹98,000
Yes
29 Jun 2021
20 May 2021
18 Jun 2021
20 May 2021
16 Jun 2021
3 Jun 2021
21 May 2021 - 27 May 2021
Amount
Provision of services for attending electrical complaints lodged at MES Service Centre from users of DRDO complex,NAI and adjoining area under AGE E/M-I, GE(I) R&D Kanchanbagh by way of receiving the complaints from users and update the same as and when rectified and submitting completion report duly signed by the occupants including electrical repair work of any defective wiring in buildings, service connection cables, main switches, DB’s replacing fuses and switching on/off of street lights at DRDO complex, NAI (H) and adjoing area under AGE E/M-I,GE(I) R&D Kanchanbagh including checking repair and maintenance to LT/ HT over head lines, UG Cables, feeder pillar boxes, bus bars, GOD’s etc connected with external electric supply during the shift periods as mentioned below on all the days including Sundays and holidays complete all as directed by Engr-in-Charge for area as mentioned below :- (a) Attending all HT/LT installations as indicated above located at D type, E type and F type quarters area in DRDO township in all three shifts as follows: 1st shift from 0600h to 1400h- one Electrician(semi skilled)& one helper(unskilled). 2nd shift from1400h to 2200h- one Electrician (semi skilled)& one helper(unskilled). 3rd shift from 2200h to 0600h- one Electrician (semi skilled)& one helper(unskilled).
(b) Attending all HT/LT installations as indicated above located at A type, B type, C type quarters and any other MD ACCN area in DRDO township in three shifts as follows: 1st shift from 0600h to 1400h-one Electrician(semi skilled)& one helper (unskilled). 2nd shift from1400h to 2200h-one Electrician (semi skilled). 3rd shift from 2200h to 0600h-one Electrician (semi skilled). (c) Attending all HT/LT installations as indicated above located at common utility buildings and OTM Accn area in DRDO township in one shift from 0800Hrs to 1600Hrs - one Electrician (Semi skilled). NOTE : Contractor should depute sufficient extra workers(out of other shifts ) on emergency whenever the Break Down occurs i.e., 24/7 (Clearing the fall of trees, restoring/ restrining of OH lines insulator's / jumpers/ fuses etc.) and restore the Power Supply within one/two hours with out fail. Any delay in restorily power supply without proper reason shall liable for blacklisting of contractor, decision of accepting officer shall be final and binding. The rate quoted deemed to be included the same.
Note for manpower employed through contract : (i) In case of requirement, tradesmen provided for one area may be utilized in other areas at the discretion of the department without any extra cost to department as directed. (ii) Rate quoted shall be deemed to include for leave reserve/Off of the staff employed. (iii) The rate quoted shall be deemed to include the cost of uniform, Shoes, Helmet, Belt and insulation gloves for tradesmen employed.. (iv) The necessary Tools & Plants shall be provided by the contractor. (v) Minimum wages to the employees to be paid shall be as per minimum fair wages declared by Governement of India. (vi) Each employee should be facilitated with adhoc bonus privilage as applicable in accordance with Govt Of India and the same to be deemed to be incuded in the quoted rate.(vii) Documentry proof of individauals duly signed by contarctor/contractor's rep shall be forwaded. (viii) In case of absence of operator, double the rate quoted shall be recovered.
(ix) During operation of installations/equipments/tree trimming in respective electrical power lines/Electrical panels should be isolated properly, necessary safety measurments(like helmet,belt, insulation gloves etc..),necessary safety precautions / safety devices to be adopted and the quoted rate is deemed to be included for same & in case of any eventuality to tradesmen/Operators, the contractor is fully responsible. (x) The contractor will adhere to pay monthly payment cycle to the employees irrespective of RAR/Funds availability. (xi) Temporary laying of LTUG cable of any size and any length for restoration of supply during break down / other requirement shall be deemed to be included in the above quoted rate. (xii) Rate quoted shall be deemed to include for restoration of jumpers,HT fuses using existing resourses during short circuits due to wind/rain, to restore the supply for incoming and out going feeders. Note (i): supply only materials as required shall be measured and paid seperately under relevent items of this schedule. (ii) Rate quoted is deemed to include for taking down of supply only items refered at note No. (i) and fixing of the same.
Note: 1. Contractor shall quote cumulative of basic rate,VDA , employers contribution towards EPF liability, contribution towards ESIC, contribution towards bonus, over head and profit as applicable as per instruction in vogue including all Taxes, Cess, Levies as applicable including GST. 2. Monthly wages shall be paid by the contractor to the workers/labour only online. Proof of statutory deductions in favour of workers/labour shall be submitted by the contractor to the GE. The contractor will be required to submit copy of valid labour licence from the labour Commissioner within 15 days of commencement of the work. If the contractor fails to submit the same within this stipulated period the contact shall be liable to be cancelled and the performance Secuirty of the firm shall be forfeited accordingly. Reference is also invited to this HQ letter No.A/37696/Gen/Pol/E2W(PPC) dated 27 July 2017 as amended vide letter of even No. dated 09 May 2018.
S&F in repairs non metallic PVC conduit 20 mm dia exclusive of boxes tees, bends, elbows, reducers, tube ends and fixing accessories such as couplers, lock nuts, saddles pipe hooks etc complete all as directed.
Dismantling LT pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C1 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed.
Cutting and trimming of tree branches of any girth and of any size, touching to overhead lines and clearing the distance of1.5 mtr length on both side of OH line with a span of 35 mtrs each, disposing the same and clearing the site complete all as directed.
Material and labour for point wiring complete with ISI marked 1.5 Sqmm PVC insulated unsheathed multistranded single core cable with copper conductor (FRLS) 1100 volts grade drawn through and including PVC rigid conduit 20 mm or higher dia ISI marked as required at site including conduit accessories such as Junction Boxes, Inspection Covers etc, concealed/surface type on stone/brick masonry walls, roofs, floors etc by means of saddles and clamps etc including PVC gang boxes as required at site for concealed/surface conduit wiring and modular plates & covers as required at site for housing switches sockets, regulators etc. including providing of 1.5 Sqmm PVC insulated multistranded unsheathed FRLS copper conductor as earth continuity conductor and connecting to common earth dolly all as specified for and connecting up complete for the following:- (a) One light/ fan point controlled by one, one way switch
All as per Srl item No.05 here-in-before but for One ceiling fan point controlled by one fan regulator complete all as directed.
All as per Srl item No.05 here-in-before but for One bell point controlled by one bell push complete all as directed.
All as per Srl item No.05 here-in-before but for One 3 pin 5 Amps switch socket outlet point on independent board complete all as directed.
All as per Srl item No.05 here-in-before but for One 3 pin socket outlet 5 Amps on the same board with other switches complete all as directed.
Material and labour for point wiring complete with ISI marked 2.5 Sqmm PVC insulated unsheathed multistranded single core cable with copper conductor (FRLS) 1100 volts grade drawn through and including PVC rigid conduit 20 mm or higher dia ISI marked as required at site including conduit accessories such as Junction Boxes, Inspection Covers etc, concealed/surface type on stone/brick masonry walls, roofs, floors etc by means of saddles and clamps etc including PVC gang boxes as required at site for concealed/surface conduit wiring and modular plates & covers as required at site for housing switches sockets, regulators etc. including providing of 2.5 Sqmm PVC insulated multistranded unsheathed FRLS copper conductor as earth continuity conductor and connecting to common earth dolly all as specified including taking down old point wiring complete as directed. For Item no 5-10 Make For Copper wire : Finolex/Havells/Gloster/KEI. For PVC conduit :Sudhakar/Polyplast/ GM/Modi. NOTE : The Contractor is responisible for arranging all tools required at site.
Supply & fixing of DB SPN 8 way double door including taking down old existing unserviceable DB complete all as directed . Make : Legrand / L&T/C&S/Schneider
Supply & fixing of DB SPN 4 way double door including taking down old existing unserviceable DB complete all as directed. Make : Legrand / L&T/C&S/Schneider
Supply and fix in replacement VTPN DB 04 way (double door) sheet metal enclosure factory made suitable for MCCB 415 volts incomer and MCBs as outgoing with 250 amp rated busbar, neutral & earthing link bar, flush/surface mounting complete including taking down the existing DB of any type & size by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site as directed. Make : Legrand Cat Part:5077 40 or equivalent in L&T/C&S/Schneider
Supply and fix in replacement of MCB single pole 6-32 Amps working on 240 volts, 50 HZ AC, 10 KA 'C' curve all as specified and directed. Make: Legrand/C&S/L&T
S&F in replacement of MCB SPN 32-40 Amps working on 240 volts, 50 HZ AC, 10 KA 'C' curve all as specified and directed. Make: Legrand/C&S/L&T
Supply & fixing of MCB TP 40 Amps complete 415 V 50 Hz including taking down old un serviceable isolators complete all as directed. Make- L&T/Legrand/Havells
Supply & fixing of MCB 4 pole operating on 415V, AC supply of capacity 63 Amps including taking down old existing un serviceable isolators complete all as directed. Make- L&T/Legrand
S&F in replacmenet MCCB with rating of 125 Amps,415Volts 3 pole with 16kA breaking capacity,thermal magnetic adjustable of overload & short circuit release as per IS-13947 & IEC 60947-2 & the service short circuit breaking capacity (Ics) should be 100% of ultimate breaking capcity(Icu) with inbuilt Display for Current Metering with accuracy of class 1. MCCB should be with suitable spreaders and phase barriers for each terminals with all accessories all as specified and directed. Make;Legrand Cat Part: 4200 06 or equivalent in Siemens/Schenider
S&F in repairs AC earth plug and socket with sheet metal enclosure with MCB SP 20A complete all as directed. Make: L&T/Legrand/Schnieder/Havells
S&F in replacmenet MCCB with rating of 250 Amps,415Volts 3 pole with 25kA breaking capacity,thermal magnetic adjustable of overload & short circuit release as per IS-13947 & IEC 60947-2 & the service short circuit breaking capacity (Ics) should be 100% of ultimate breaking capcity(Icu) with inbuilt Display for Current Metering with accuracy of class 1. MCCB should be with suitable spreaders and phase barriers for each terminals with all accessories all as specified and directed. Make: Legrand Cat Part: 4200 09 or equivalent in Siemens/Schenider
S&F in replacmenet MCCB with rating of 320 Amps,415Volts 3 pole with 36 kA breaking capacity,thermal magnetic adjustable of overload & short circuit release as per IS-13947 & IEC 60947-2 & the service short circuit breaking capacity (Ics) should be 100% of ultimate breaking capcity(Icu) with inbuilt Display for Current Metering with accuracy of class 1. MCCB should be with suitable spreaders and phase barriers for each terminals with all accessories all as specified and directed. Make: Legrand Cat Part: 4220 01 or equivalent in Siemens/Schenider
S&F in replacmenet MCCB with rating of 400 Amps,415Volts 4 pole with 36 kA breaking capacity,thermal magnetic adjustable of overload & short circuit release as per IS-13947 & IEC 60947-2 & the service short circuit breaking capacity (Ics) should be 100% of ultimate breaking capcity(Icu) with inbuilt Display for Current Metering with accuracy of class 1. MCCB should be with suitable spreaders and phase barriers for each terminals with all accessories all as specified and directed. Make: Legrand Cat Part: 4203 15 or equivalent in Siemens/Schenider
S&F in replacmenet MCCB with rating of 630 Amps,415Volts 4 pole with 36 kA breaking capacity,thermal magnetic adjustable of overload & short circuit release as per IS-13947 & IEC 60947-2 & the service short circuit breaking capacity (Ics) should be 100% of ultimate breaking capcity(Icu) with inbuilt Display for Current Metering with accuracy of class 1. MCCB should be with suitable spreaders and phase barriers for each terminals with all accessories all as specified and directed. Make: Legrand Cat Part: 4220 09 or equivalent in Siemens/Schenider NOTE: The above items ie MCCBs shall be executed immediately as and when required basis.
Supply only Bell push flush type 5 Amps complete all as directed.
Supply only switch socket combination 5 pin 15 Amps multipurpose type complete all as directed.
Supply only switch piano one way 5 Amps 240 Volt complete all as directed.
Supply only lamp holder angle/ batten type complete all as directed.
Supply only ceiling rose two/three terminal surface backallite type complete all as directed.
Material and Labour for sub main wiring with 2 runs of 4 Sqmm single core PVC insulated unsheathed FRLS cable 1100 Volts grade multistranded with copper conductor drawn through and including non metallic rigid PVC conduit ISI marked 25 mm dia including conduit accessories concealed/surface type on walls, roof, floors etc including one run of 4 Sqmm PVC copper conductor as earth continuity wire including taking down unserviceable sub main wiring including conduit all as specified and directed. Make of Gang Boxes: GM/Havells/Legrand Note : 3 Runs of 4 sqmm cable and 1 run of PVC conduit shall be measured as one unit for the purpose of payment.
All as per srl item No. 29 here-in-before but 2 runs of 6 Sqmm cable and 01 run of 6 Sqmm cable for earth continuity conductor complete all as directed. Note:- 2 runs of 6 Sqmm cable and one run of 6 Sqmm earth continuty conductor shall be measured as one unit length.
Supply only Prelaminated hylum sheet top cover of size 75mm x 75mm and 3mm thick in half white or ivory colour for fixing or mounting switchs, sockets, fan regulator etc complete all as directed .
All as per srl item No.31 here-in-before but of size 175mm x 100mm
All as per srl item No.31 here-in-before but of size 250mm x 300 mm
S&F in replacment indoor industrial type surface/wall mounted LED integral batten 20W, 6500K CCT, alluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete removing unserviceable fittings all as specified and directed. Make : Havells Cat part:LUMILINEBS20WLED865SPCWH or equivalent in Philips/Wipro
S&F in replacment indoor industrial type surface/wall mounted LED integral batten 10W, 6500K CCT, alluminium extruded body and polycarbonate diffuser, <10%THD, integral elctronic driver complete fixing with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete removing unserviceable fittings all as specified and directed. Make : Havells Cat part:LUMILINEPLUSBS10WLED865SPCS or equivalent in Philips/Wipro
Earthing with GI earth plate electrode 600x600x6 mm buried directly in ground vertically to a depth of not less than 2.25 mtrs below ground level with the top edge not less than 1.5 mtrs below ground level connected to GI earth strip of size 32X6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel and GI protection pipe, 40 mm dia light grade including necessary excavation & earth work, PCC 1:3:6 type C1 Chamber, RCC 1:2:4, type B1 as in cover 50 mm thick with 8mm dia TMT bars @100 mm c/c both ways, GI water pipe 20 mm dia, medium grade, funnel, wire mesh, salt, charcoal complete all as shown in electrical plate No. 3 of MES Sch `A' Part - I incl taking out old earthing complete all as directed. NOTE: GI earth strip and GI pipe beyond 7.5m shall be measured and paid for seperately.
S&F GI earth strip of size 32 x 6mm as in earth continuity conductor or main earthing lead fixed to wall on batten or recess or buried in ground or fixed to poles or any other indicated situation, as required including taking down old unserviceable earth strip complete all as directed.
S&F in replacement for Modular socket 6A 2/3 Pin 2 module ISI marked.
S&F in replacement for Modular socket 16A 2/3 Pin 2 Module.
S&F in replacement for modular switch 1 way 6A 1 module.
S&F in replacement for modular switch 1 way 16A 1 module.
Supply only piano switch 2 way 15 Amps complete all as directed. Make for srl item Nos.48 to 52 :- Usha/ CG/Anchor/MARU
Supply only switch socket outlet 3 pin, 5 Amps, 2 in 1 operating on 230 V, 50 Hz complete all as directed.
Supply only bell ding dong, AC, 230V, single pole complete all as directed.
Supply only Buzzer, AC, 230V, single pole complete all as directed. Make for item Nos.38 to 45 :- ANCHOR/CONA/GM
Supply only fan regulator 240 V AC electronic step type complete all as directed. Make: anchor/leader/cona
Taking down unservcieable Celing fan/ exhaust fan, dismanting, overhauling, and replace the unserviceable spares, rewinding the motor etc and re-assembling the fan after complete repairs refixing the same at same location complete all as directed by Engr-in-charge. Note :- (i) Spare parts shall be measured and paid separately. (ii) Rewinding Job shall be measured & paid separately.
M&L for rewinding of ceiling fan/ exhaust fan of any make of the following sweep including removal of existing burnt out winding carefully from the slots, cleaning the slots with cleaning agents, winding with super enameled copper wire of same gauge with insulation, varnishing complete all as directed
Ceiling fans of 1200/ 1400 Sweep.
Exhaust fan of 230/ 300 Sweep.
Supply only capacitor 2.5 mfd suitable for ceiling fan.
Supply only capacitor 3.5/ 4.0 mfd suitable for Exhaust fan
Supply only bearing No.6201/6202/6203/6204 or any other No matching to the existing size and suitable for ceiling fan/exhaust fan. Make: SKF/TATA/ARB
Supply & lay XLPE insulated , armoured heavy duty electric cable with aluminium conductor , 1100 volts grade of cross- sectional area 16 sq mm 4.0 core including taking down existing cable complete all as directed.
Supply & lay for XLPE insulated , armoured heavy duty electric cable with aluminium conductor 1100 volts grade of cross- sectional area 25 sq mm 3.5 core including taking down old unserviceable cable complete all as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/dense soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick using soil complete all as directed.
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as directed.
Supply and spreading of dry clean natural river sand in trenches/ transformer yard / two pole structure yard for cable protection complete all as directed. Note:- Punned thickness only shall be measured for payment purpose.
Supply & lay common burnt bricks, sub class 'B', of size 230 x 115 x 75 mm in trenches for cable protection complete all as directed.
S&F Galvanised iron tubing 100 mm dia, light grade, laid at road crossing etc complete all as directed.
S & F MCCB of 3 Pole 100 Amps capacity 10 KA breaking capacity and 415 V complete incuding taking down old existing unserviceable MCCB complete all as directed. Make:L&T/Legrand/Schnieder
S&F in repairs LED tube 20Watt, 6500K CCT, proffesional luminaries with luminous efficiency not less than 120Lm/watt, Single side connection with < 10% THD. Make: Havells Cat part:CRYSTAL1213T8DSTL20WLED865SGL or Philips/Wipro
Global Tech Services
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .