EE PWD Elect Dn Udaipur
EE PWD Elect Dn Udaipur
Electric Maintenance work related to Transformer at various Yard in RNT Medical College, Udaipur( Part 2)
2026_CEPWD_569660_15
NIT_01_2026-27_EE_PWD_ED_Udr
Open Tender
Electrical Works
180 days
Udaipur
As per bid
2 documents required · 2 mandatory
₹500
EE PWD Elect Dn Udaipur through Egras Challan
₹34,400
Yes
EE PWD Elect Dn Udaipur
19 Jun 2026
19 Jun 2026
2 Jul 2026
19 Jun 2026
30 Jun 2026
19 Jun 2026
24 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SITC of Microprocessor based Draw out type 3/4 pole door interlock Air Circuit Breaker (ACB) as conforming to IS/IEC 60947 P - 2 :2003 in existing LT panel suitable for LT installation 440/415 V, 50 Hz and having adjustable over load, short-circuit, Instantaneous, earth fault (LSIG) with separate LED indication or Fault details on display for each type of fault shall confirm to EMI/ EMC test , LCD/LED display, last 10 trip history, Inbuilt ZSI, Current metering, Provision for Communication, Thermal memory, trip free mechanism, modular design and suitable for ambient 50 degree and utilization catagary B. In built electrical & mechanical anti pumping feature , pollution degree 3, 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more then 30 ms. Provision for electrical & mechanical interlock between ACB sand other required accessories (Cost of accessories to be paid extra) Min.electrical operation 10000 upto 1600 A rating and 5000 for 2000 A to 4000 A. including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. | - | - | - | - |
| 2 | Manual spring charged type 4 Pole | - | - | - | - |
| 3 | 1000 A Rating , 50 kA | 1 | Each | 1,55,456 | ₹1,55,456 |
| 4 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- | - | - | - | - |
| 5 | (a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided | - | - | - | - |
| 6 | (b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. | - | - | - | - |
| 7 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) | - | - | - | - |
| 8 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. | - | - | - | - |
| 9 | (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. | - | - | - | - |
| 10 | (f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) | - | - | - | - |